Plan Review Details - Permit 22030297
Plan Review Stops For Permit 22030297
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-07-12 Cont ID  
Sent By cpuell Date 2022-07-12 Time 12:17 Rev Time 0.00
Received By cpuell Date 2022-07-12 Time 12:17 Sent To  
Notes
2022-07-12 12:18:18UNITS IDENTIFIED AS 101 103 201 203 & 301

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By cpuell Date 2022-07-12 Time 07:54 Rev Time 0.00
Received By cpuell Date 2022-07-12 Time 07:54 Sent To  
Notes
2022-07-12 07:59:08PLEASE IDENTIFY THE UNIT NUMBERS THAT THIS SCOPE OF
 WORK IS FOR, AS IN THE ADDRESSES FOR THE 5 UNITS.
 PLEASE RESPOND TO [email protected] OR 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 13:56 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 16:48 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 14:40 Sent To  
Notes
2022-04-13 16:49:38PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 17:06 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 14:40 Sent To  
Notes
2022-04-13 17:06:53REMODEL UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT
 DIMENSION FROM THE FLOOR TO THE "REFLECTIVE SURFACE"
 FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2) PLEASE SHOW THAT THE DOORS HAVE A 32" CLEAR OPENING
 - FBC A 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3) DRAWINGS A200 AND A201 SHOW SHOWER GRAB BAR HEIGHTS
 TO THE CENTER OF THE GRAB BAR - SHOULD BE SHOWN TO THE
 TOP OF THE GRIPPING SURFACE - FBC A 609.4 POSITION OF
 GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 4) PLEASE SHOW THE SHOWER BENCH DETAILS AND DIMENSIONS
 TO COMPLY WITH FBC A 610.3
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE PARKING LOT
 RESTRIPING - PLEASE ACKNOWLEDGE THIS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-07-08 Cont ID  
Sent By mpeterso Date 2022-07-08 Time 15:45 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-24 Cont ID  
Sent By mpeterso Date 2022-06-24 Time 11:44 Rev Time 0.00
Received By mpeterso Date 2022-06-24 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-06-24 Cont ID  
Sent By mpeterso Date 2022-06-02 Time 15:15 Rev Time 0.00
Received By mpeterso Date 2022-06-02 Time 15:15 Sent To  
Notes
2022-06-24 11:51:47SEE SIGNATURE REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By mpeterso Date 2022-04-11 Time 10:28 Rev Time 0.00
Received By mpeterso Date 2022-04-11 Time 08:06 Sent To  
Notes
2022-04-11 10:36:41ELECTRIC REVIEW FAILED
 1) THE CODE ANALYSYS SHEET STATES THIS IS A LEVEL 1
 ALTERATION, IT APPEARS FROM THE WORK SCOPE THAT THIS IS
 A LEVEL 2 ALTERATION. PLEASE CLARIFY . FBC EXISTING
 BUILDING 602.1 AND 603.1
 2) IF CLASSIFIED AS A LEVEL 2 THEN ARC FAULT CIRCUIRT
 PROTECTION SHALL BE REQUIRED AS WELL AS OTHER
 REQUIREMENTS OF THE NEC AS REQUIRED. NEC 210.12 AND NEC
 2017
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-14 Cont ID  
Sent By   Date 2022-07-14 Time   Rev Time 0.00
Received By bdolan Date 2022-07-14 Time 11:13 Sent To  
Notes
2022-07-14 11:14:151) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-22 Cont ID  
Sent By   Date 2022-03-22 Time   Rev Time 0.00
Received By bdolan Date 2022-03-22 Time 11:21 Sent To  
Notes
2022-03-22 11:21:421) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-14 Cont ID  
Sent By mpeterso Date 2022-07-14 Time 17:45 Rev Time 0.00
Received By jgomez Date 2022-07-01 Time 08:24 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-24 Cont ID  
Sent By mpeterso Date 2022-06-24 Time 11:54 Rev Time 0.00
Received By mpeterso Date 2022-06-10 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-02 Cont ID  
Sent By mpeterso Date 2022-06-02 Time 15:16 Rev Time 0.00
Received By mpeterso Date 2022-05-17 Time 18:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-29 Cont ID  
Sent By asangele Date 2022-04-29 Time 10:29 Rev Time 0.00
Received By asangele Date 2022-04-29 Time 10:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 17:07 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 17:07 Sent To  
Notes
2022-04-13 17:07:44NOT A CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-07-05 Cont ID  
Sent By medwards Date 2022-07-05 Time 15:45 Rev Time 0.00
Received By medwards Date 2022-07-05 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 06:54 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 06:54 Sent To  
Notes
2022-06-21 06:55:163RD REVIEW FMC
 PERMIT: 22030297
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEE PREVIOUS COMMENT BELOW. EITHER PROVIDE A DETAIL
 SHOWING THAT THE DRYER DUCT IS NOT PENETRATING THE
 FLOOR/CEILING ASSEMBLY OR SHOW HOW IT WILL BE FIRE
 RATED ACCORDING TO THE LAST PART OF FMC 504.2 AND FMC
 607.6.2 COPIED BELOW FOR YOUR CONVENIENCE. NOTE: FMC
 607.6.2 WOULD BE THE ONLY ONE THAT APPLIES OF THE 3
 REQUIREMENTS AS THE OTHER 2 ONLY APPLY WHERE GRILLE IS
 PENETRATING THE CEILING OF A FLOOR/CEILING ASSEMBLY.
  
  
 2) PROVIDE A DETAIL DRAWING OF THE NEW DRYER DUCT BEING
 INSTALLED AS IT CANNOT PASS THROUGH THE RATED
 FLOOR/CEILING ASSEMBLY. FMC 607.6.2
  
 FMC 504.2 EXHAUST PENETRATIONS. WHERE A CLOTHES DRYER
 EXHAUST DUCT PENETRATES A WALL OR CEILING MEMBRANE, THE
 ANNULAR SPACE SHALL BE SEALED WITH NONCOMBUSTIBLE
 MATERIAL, APPROVED FIRE CAULKING OR A NONCOMBUSTIBLE
 DRYER EXHAUST DUCT WALL RECEPTACLE. DUCTS THAT EXHAUST
 CLOTHES DRYERS SHALL NOT PENETRATE OR BE LOCATED WITHIN
 ANY FIREBLOCKING, DRAFTSTOPPING OR ANY WALL,
 FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY THE FLORIDA
 BUILDING
 CODE, BUILDING TO BE FIRE-RESISTANCE RATED, UNLESS SUCH
 DUCT IS CONSTRUCTED OF GALVANIZED STEEL OR ALUMINUM OF
 THE THICKNESS SPECIFIED IN SECTION 603.4 AND THE
 FIRE-RESISTANCE
 RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FIRE DAMPERS, COMBINATION
 FIRE/SMOKE DAMPERS AND ANY SIMILAR DEVICES THAT WILL
 OBSTRUCT THE EXHAUST FLOW
 SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS.
  
 [BF] 607.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR
 TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS, IN
 ACCORDANCE WITH SECTION 603, THAT PENETRATE THE CEILING
 MEMBRANE OF A FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/ CEILING ASSEMBLY SHALL BE PROTECTED WITH ONE OF
 THE FOLLOWING:
 1. A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713 OF
 THE FLORIDA BUILDING CODE, BUILDING.
  
 2. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF A
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING.
  
  
 3. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DIFFUSER WITH NO DUCT ATTACHED
 PENETRATES THE CEILING OF A FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 15:18 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 15:18 Sent To  
Notes
2022-05-24 15:50:39PROVIDE ANSWER TO PREVIOUS COMMENT BELOW:
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030297
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 2) PROVIDE A DETAIL DRAWING OF THE NEW DRYER DUCT BEING
 INSTALLED AS IT CANNOT PASS THROUGH THE RATED
 FLOOR/CEILING ASSEMBLY. FMC 607.6.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 16:15 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 16:15 Sent To  
Notes
2022-03-28 16:15:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030297
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE NEW MECHANICAL SYSTEMS.
  
 2) PROVIDE A DETAIL DRAWING OF THE NEW DRYER DUCT BEING
 INSTALLED AS IT CANNOT PASS THROUGH THE RATED
 FLOOR/CEILING ASSEMBLY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-07-06 Cont ID  
Sent By ccole Date 2022-07-06 Time 10:25 Rev Time 0.00
Received By ccole Date 2022-07-06 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-13 Cont ID  
Sent By ccole Date 2022-06-13 Time 15:38 Rev Time 0.00
Received By ccole Date 2022-06-13 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-24 Cont ID  
Sent By ccole Date 2022-05-24 Time 14:25 Rev Time 0.00
Received By ccole Date 2022-05-24 Time 09:04 Sent To  
Notes
2022-05-24 14:26:342ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22030297
 5/24/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CORRECTED PLAN SHEETS A200 & A201: PROVIDE THE
 FOLLOWING DETAILS PER FBC ACC:
  
 A) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 B) THE LENGTH MEASUREMENTS OF THE WATER CLOSET GRAB
 BARS- SEC. 604.5.
  
 C) THE CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND
 FIGURE 604.7.
  
 D) THE HEIGHT MEASUREMENTS OF THE ROLL-IN SHOWER
 THRESHOLD- SEC. 608.7. PLEASE NOTE THE SUBMITTAL FOR
 THE SHOWER SHOWS A 4-INCH-HIGH THRESHOLD HOWEVER THE
 MAXIMUM HEIGHT ALLOWABLE IS 1/2-INCH. THE SUBMITTAL
 ALSO DOES NOT INDICATE THE SHOWER IS AN ADA COMPLIANT
 MODEL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By ccole Date 2022-03-21 Time 13:02 Rev Time 0.00
Received By ccole Date 2022-03-18 Time 16:51 Sent To  
Notes
2022-03-21 13:03:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22030297
 3/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) G102 & G103: THE FLORIDA ACCESSIBILITY CODE 7TH
 EDITION 2020 IS THE GOVERNING CODE LISTED ON G103
 HOWEVER THE FOLLOWING ITEMS ON G102 ARE NOT CONSISTENT
 WITH THE CODE.
 A) WATER CLOSET GRAB BAR HEIGHTS MEASURED TO THE
 CENTERLINE OF THE GRAB BARS AND NOT THE TOPS OF THE
 GRIPPING SURFACES- SEC. 609.4.
 B) MIRROR MEASUREMENT TO THE FRAME AND NOT THE
 REFLECTIVE SURFACE- SEC. 603.3.
 C) TYPE A LAVATORY OVERLAP IS NOT A TERM USED IN THE
 FBC ACC CODE HOWEVER THE DETAIL IS CONSISTENT WITH SEC.
 604.3.2.
  
 2) G102, G103, A200 & A201: THE APPLICATION FOR THE
 PROJECT INDICATES MODIFICATIONS OF 5 UNITS TO MEET UFAS
 STANDARDS, HOWEVER THERE IS NO REFERENCE TO THE UFAS ON
 THE PLANS AND NO DETAILS- SEC. 107.2.1 WPB. PLEASE
 PROVIDE MORE INFORMATION OR DOCUMENTS TO CLARIFY HOW
 THE SCOPE OF THE ACCESSIBILITY WORK WAS DETERMINED.
  
 3) A200 & A201: PROVIDE THE FOLLOWING LIST OF FBC ACC
 COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) THE REAR GRAB BAR FOR THE WATER CLOSET TO BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE- SEC. 604.5.2. (SEE
 DETAIL ON G102).
 D) DIMENSIONS OF THE SHOWER- SEC. 608.2.2.
 E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.2.1.
 F) SHOWER GRAB HEIGHTS MEASURED TO THE CENTERLINE OF
 THE GRAB BARS AND NOT THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4.
 G) HEIGHT OF THE SHOWER SEAT- SEC. 610.3
 H) DIMENSIONS AND CLEARANCES FOR THE SEAT- SEE SEC.
 610.3, AND SEC. AND FIGURE 610.3.2.
  
 4) A200 & A201: FHA TYPE B BATHROOMS ARE SPECIFIED
 HOWEVER THE LAYOUTS WILL NOT PROVIDE THE REQUIRED CLEAR
 FLOOR SPACE APPROACH FOR THE BATHTUB AS SHOWN IN
 FIGURES 7(B) FHAG- FBC ACC, AND AS SHOWN ON PAGE 7.53
 FHA DESIGN MANUAL- SPECIFICATION B. THE CURRENT LAYOUT
 SHOWING THE WATER CLOSET BY THE BATHTUB IS CONSISTENT
 WITH A SPECIFICATION A COMPLIANCE.
 A) PLEASE SHOW THE TOTAL WIDTH AND LENGTH MEASUREMENTS
 OF THE TYPE B BATHROOMS.
 B) SHOW THE CLEAR FLOOR DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- PAGE 7.43- 7.44 FHA DESIGN MANUAL, AND
 FIGURE 6A FHAG- FBC ACC.
 C) SHOW THE CLEAR FLOOR DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- PAGE 7.47- 7.52 FHA DESIGN MANUAL, AND
 FIGURE 6C FHAG- FBC ACC.
 D) PROVIDE A DETAIL FOR THE REMOVABLE LAVATORY CABINET-
 PAGE 7.49 FHA DESIGN MANUAL.
 E) SHOW THE FUTURE GRAB BAR LOCATIONS FOR THE WATER
 CLOSET AND BATHTUB AND PROVIDE REINFORCEMENT DETAILS-
 SEE PAGES 6.1- 6.9 FHA DESIGN MANUAL, AND FIGURES 3 & 4
 FHAG- FBC ACC.
  
 5) A200 & A201: PROVIDE A DETAIL FOR THE REMOVABLE
 KITCHEN SINK FRONT- PAGE 7.12 FHAG- FBC ACC.
  
 6) P101: PROVIDE WASTE AND VENT ISOMETRIC DRAWINGS FOR
 THE KITCHEN SINKS- SEC. 107.3.5.1.3 WPB.
  
 7) P101: CORRECT THE NOTE AT ISOMETRIC- 2 DETAIL- THE
 2-INCH FIXTURE DRAIN FOR THE WASHING MACHINE SHALL
 CONNECT TO A MINIMUM 3-INCH DIAMETER BRANCH OR STACK-
 SEC. 406.2 FBC P.
  
 8) P101: SHOW WATER HAMMER ARRESTOR LOCATIONS- SEC.
 604.9 FBC P.
  
 9) P101: PROVIDE A SHOWER PAN DETAIL- SEC. 421.5-
 412.5.2.6 FBC P.
  
 10) P101: PROVIDE SLAB REPAIR AND FIRESTOPPING DETAILS
 FOR PIPE PENETRATIONS- SEC. 107.2.1 WPB, AND SEC. 315.1
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-08 Cont ID  
Sent By rmcphers Date 2022-07-08 Time 14:45 Rev Time 0.00
Received By rmcphers Date 2022-07-08 Time 14:44 Sent To  
Notes
2022-07-05 15:46:28DIGITAL SIGNATURE FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-06-24 Cont ID  
Sent By mpeterso Date 2022-06-24 Time 11:52 Rev Time 0.00
Received By mpeterso Date 2022-06-24 Time 11:52 Sent To  
Notes
2022-06-24 11:54:01SIGNATURE REVIEW FAILED
  
 SHEETS COVER SHEET,A-200 AND A-201 DO NOT HAVE A
 DIGITAL SIGNATURE
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-24 Cont ID  
Sent By rmcphers Date 2022-05-24 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 14:00 Sent To  
Notes
2022-05-24 14:03:10SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS M101, E101 AND P101 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE A VERIFIABLE ELECTRONIC OR DIGITAL SIGNATURE -
 YOU CAN DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 17:11 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 17:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By asangele Date 2022-05-24 Time 11:45 Rev Time 0.00
Received By asangele Date 2022-05-24 Time 11:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-29 Cont ID  
Sent By asangele Date 2022-04-29 Time 09:55 Rev Time 0.00
Received By asangele Date 2022-04-29 Time 09:55 Sent To  
Notes
2022-04-29 10:29:104/29/2022
 FAIL
 PLEASE APPLY FOR TWO DIFFERENT PERMITS FOR THE PARKING
 MODIFACTIONS/CHANGES AND BUILDING INTERIOR CHANGES
 REQUIRED PARKING SUMMARY IS INCORRECT PLEASE UPDATE SEE
 TO THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 SECTION 94-486
 * EFFICIENCY: 1.5 PER UNIT1 BR: 1.75 PER UNIT? 2 BR: 2
 PER UNIT, 1 PER 10 UNITS FOR GUESTS
  
  
 PLEASE EMAIL ME WITH ANY QUESTION!
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  
  
  