Plan Review Details - Permit 22030285
Plan Review Stops For Permit 22030285
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By jwitmer Date 2022-05-04 Time 14:04 Rev Time 0.00
Received By jwitmer Date 2022-05-04 Time 11:12 Sent To  
Notes
2022-05-04 14:04:22COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By jwitmer Date 2022-05-04 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2022-05-04 Time 11:11 Sent To  
Notes
2022-05-04 11:11:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030285
 ADD: 1400 ELIZABETH AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 04TH/ 2022
 ACTION: DENIED
  
 1) PLEASE BE AWARE THIS BUILDING IS LOCATED IN A AE
 FLOOD ZONE. THE BASE FLOOD ELEVATION IS (BFE 12.1 FEET
 NAVD88). THE BUILDING WAS BUILT IN 1950 MAKING THE
 BUILDING A PRE-FIRM BUILDING. THE PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE (2021 TAX YEAR) LIST THE
 TOTAL MARKET VALUE OF $506,387.00 DOLLARS, LAND AT
 $174,168.00 DOLLARS AND IMPROVEMENT VALUE OF $332,210
 DOLLARS OF VALUE. THE DOLLAR AMOUNT FOR THIS PERMIT
 VALUE IS $500,000.00 DOLLARS IN VALUE MAKING THIS A
 SUBSTANTIAL IMPROVEMENT.
  
 WEST PALM BEACH MUNI CODE. SUBSTANIAL IMPROVEMENT.
 SECTION 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION.
 (A)(3) ANY ALTERATION, REPAIR, RECONSTRUCTION, OR
 IMPROVEMENTS TO A PROPERTY WHICH THE CUMULATIVE COST
 FOR ANY FIVE YEAR PERIOD EQUALS OR EXCEEDS 50 % OF THE
 BUILDING VALUE AT THE COMMENCEMENT OF THE FIVE YEAR
 PERIOD SHALL MEET THE REQUIREMENTS OF NEW CONSTRUCTION
 AS CONTAINED IN THIS ARTICLE.
 YOU MAY WAN TO REVIEW FEMA PUBLICATION FEMA P-758
 SUBSTANTIAL IMPROVEMENT/ SUBSTANTIAL DAMAGE DESK
 REFERENCE, AND REVIEW PAGE 6-9.
 YOU MAY ALSO WANT TO GET A CERTIFIED APPRAISER DONE OF
 THE BUILDING (IMPROVED VALUE) TO SEE IF THIS
 RENOVATION/ REMODEL WOULD NO LONGER CLASSIFY AS A
 SUBSTANTIAL IMPROVEMENT. THE OTHER ISSUE THAT MAY OCCUR
 IS THE OLD DOCKING STATION WITHIN THE BUILDING AND
 LOWER FLOOR LEVEL. YOU WILL NEED TO ESTABLISH THE FLOOR
 ELEVATIONS HIGH AND LOWER FLOOR LEVELS IN NAVD 88. ANY
 ATTENDANT UTILITIES INCLUDING A/C COMPRESSORS AND OR
 ELECTRICAL GENERATORS WILL ALSO BE SHOWN ON THE SURVEY.
 DEPENDING ON THE OUTCOME OF THE SURVEY ANOTHER FEMA
 PUBLICATION TECHNICAL BULLETIN TB 3-93 FOR
 NON-RESIDENTIAL FLOOD PROOFING REQUIREMENTS &
 CERTIFICATION.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST-FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. W.
 P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
 2020 FBC-BUILDING SECTION 1612 FLOOD ZONES, AND ASCE 24
 MANUAL.
  
 2) SHEET A0.01:
  
 2A) PLEASE PROVIDE A SURVEY OF THE PROPERTY THE
 PROPERTY APPRAISERS OFFICE PICTURE OF BUILDING PROPERTY
 LINES DOES NOT SHOW A OFFSET IN THE RIGHT SIDE OF THE
 BUILDINGS. BUILDINGS CAN NOT TRANSGRESS PROPERTY LINES.
 2020 W. P. B. ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN
 REVIEW CRITERIA SURVEY.
  
 2B) THE FRONT OF THE BUILDING THERE ARE IS A STAIR
 ENTRY, WITHIN THE BUILDING LOWER FLOOR LEVEL STAIRS AND
 THE REAR OF THE BUILDING AGAIN THE REAR EXIT STAIRS.
 PLEASE SHOW COMPLIANCE WITH 2020 FBC-ACCESSIBILITY CODE
 SECTION 201.1.1 VERTICAL ACCESSIBILITY.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 202.4.2 ACCESSIBILITY FEATURES IN THE EVENT OF
 DISPROPORTIONALITY ($500,000.00 X 0.20= $100,000.00
 DOLLARS). WHEN THE COST OF THE ALTERATIONS NECESSARY TO
 MAKE THE PATH OF TRAVEL TO THE ALTERED AREAS FULLY
 ACCESSIBLE IS DISPROPORTIONATE TO THE COST OF THE
 OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE MADE
 ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE ACCESSIBLE
 WITHOUT INCURRING DISPROPORTIONATE COST. IN CHOOSING
 WHICH ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO
 THOSE ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS,
 IN THE FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT
 LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM; (IV) ACCESSIBLE TELEPHONES: (V)
 ACCESSIBLE DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE,
 ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS PARKING,
 STORAGE, AND ALARMS.
  
 2C) THE BREAK ROOM SINK DOES NOT INDICATE IF THIS IS
 GOING TO BE A FRONT APPROACH OR SIDE APPROACH, NOT
 SHOWN ON THE PLANS. 2020 FBC-ACCESSIBILITY CODE 606.2
 CLEAR FLOOR SPACE.
  
 2D) THE FLOOR PLAN SHOWS TABLE AND CHAIRS IN THE BREAK
 ROOM BUT NOT COMPLIANCE WITH 2020 FBC-ACCESSIBILITY
 CODE SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2E) 2020 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2F) 2020 FBC-ACCESS. CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 2G) IT APPEARS THERE MAYBE A SINGLE WATER FOUNTAIN IN
 FRONT OF THE RESTROOMS, IN THE CORRIDOR. SHEET A1.01
 SHOWS A DETAIL MARKER DETAIL 8/ A6.01 WHICH IS FOR
 STADIUM SEATING? DISCREPANCY IN PLANS. 2020
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3) SHEET A1.01:
 3A) SHEET A1.01 SHOW DETAIL 5/ A6.01 FOR GUARDRAIL AT
 LOWER FLOOR LEVEL, BUT AGAIN WRONG DETAIL DETAIL 5 IS
 FOR RESTROOM ELEVATION. DISCREPANCY IN PLANS. NOTE
 THERE ARE NO DETAILS OF FRONT AND REAR STAIRS, GUARD/
 HAND RAILS. 107.2.1.2. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET M3.1 SHOWS THE INSTALLATION OF ROOF TOP
 CONDENSERS BUT NO ACCESS TO THE ROOF IS SHOWN ON EITHER
 THE LIFE SAFETY PLAN NOR A1.01. 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN
 HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN
 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT
 SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE USE OF
 PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER
 PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP
 OF THE PARAPET WALL.
  
 5) SHEET M7.1 SHOWS ROOF TOP PRE-ENGINEERED ROOF
 STANDS, MISSING THE PRODUCT APPROVAL FOR ROOF STANDS.
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS
  
 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 11:51 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 11:51 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 11:51 Sent To  
Notes
2022-05-06 11:52:25VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-28 Cont ID  
Sent By cwalker Date 2022-03-28 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-28 10:24:31FIRE PROVISO COMMENTS:
 ANY WORK ON ANY LIFE SAFETY SYSTEM (INCLUDING FIRE
 ALARM AND/OR FIRE SPRINKLERS) WILL REQUIRE SEPARATE
 PERMITS AND SHOP DRAWINGS.
 EXIT DOOR ASSEMBLIES SHALL COMPLY WITH NFPA 101,
 7.2.1.5
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 11:54 Rev Time 0.00
Received By jleahy Date 2022-03-28 Time 05:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By jwitmer Date 2022-05-04 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2022-05-04 Time 11:12 Sent To  
Notes
2022-05-04 14:05:58IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-02 Cont ID  
Sent By medwards Date 2022-05-02 Time 17:12 Rev Time 0.00
Received By medwards Date 2022-05-02 Time 17:12 Sent To  
Notes
2022-05-02 17:12:351ST REVIEW FMC
 PERMIT: 22030285
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC 101.5.1.1.2
  
 2) PLEASE SHOW THAT THE CONDENSING UNITS ARE A MINIMUM
 OF 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARDS. FMC
 304.11
  
 3) PLEASE SHOW THE ROOF ACCESS. FMC 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By rwbrown Date 2022-04-26 Time 10:14 Rev Time 0.00
Received By rwbrown Date 2022-04-26 Time 10:14 Sent To  
Notes
2022-04-26 10:14:181ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE P2.1 - V7 FPC 410.3 - A HIGH/LOW DRINKING
 FOUNTAIN IS REQUIRED.
  
 2. PAGE P0.1 - 2020 FPC - 607.1.1 TEMPERATURE LIMITING
 MEANS ? THE THERMOSTAT CONTROL ON THE WATER HEATER
 CANNOT BE THE LIMITING DEVICE FOR HOT WATER DELIVERY.
 PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE
 PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR
 PUBLIC HAND-WASHING 607.1.2/419.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 11:54 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 11:54 Sent To  
Notes
2022-05-02 17:14:26MECHANICAL DIGITAL SIGNATURES APPROVED. ME

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-05 Cont ID  
Sent By vbroglia Date 2022-04-05 Time 16:39 Rev Time 0.00
Received By vbroglia Date 2022-04-05 Time 16:39 Sent To  
Notes
***NONE***