Plan Review Details - Permit 22030266
Plan Review Stops For Permit 22030266
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By scwelter Date 2022-05-18 Time 13:44 Rev Time 0.00
Received By scwelter Date 2022-05-18 Time 13:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-06-13 Cont ID  
Sent By lmarchan Date 2022-06-13 Time 14:56 Rev Time 0.00
Received By lmarchan Date 2022-06-13 Time 14:56 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 10:06 Sent To  
Notes
2022-06-09 10:08:35THE LETTER NEEDS TO BE SIGNED AND WORDED AS SHOWN -
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY".
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 11:56 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 10:47 Sent To  
Notes
2022-04-04 11:56:47PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 08:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 12:36 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 10:46 Sent To  
Notes
2022-04-04 12:35:50COMMERCIAL REMODEL AND ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING DEMOLITION NEEDS TO BE ON A SEPARATE
 PERMIT.
  
 2) PLEASE SHOW THE RESTROOM WALL FINISH TO COMPLY WITH
 FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR - (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) PLEASE SHOW RESTROOM BASE BOARD (SHOULD NOT BE WOOD)
 TO COMPLY WITH FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By jleahy Date 2022-06-01 Time 16:31 Rev Time 0.00
Received By jleahy Date 2022-06-01 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By mpeterso Date 2022-04-21 Time 12:26 Rev Time 0.00
Received By mpeterso Date 2022-04-21 Time 12:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By rrossano Date 2022-03-23 Time   Rev Time  
Received By rrossano Date 2022-03-23 Time   Sent To  
Notes
2022-03-23 14:18:04PASSED WITH PROVISOS:
  
 CALL 811 FOR UTILITY LOCATES.
  
 ON CIVIL SHEET C-1, INDICATE PROTECTION OF STORMWATER
 INLETS ALONG PROJECT FRONTAGE ON KANUGA AND DIXIE.
  
 THANKS,
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By cwalker Date 2022-05-03 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-05-03 09:45:49FIRE PROVISO COMMENTS:
 NFPA 101, LIFE SAFETY CODE
 (1) 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE
 EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO
 HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED
 THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43
 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
 7.2.1.5.5.2 THE ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1
 SHALL BE
 PERMITTED TO BE REVOKED BY THE AUTHORITY HAVING
 JURISDICTION
 FOR CAUSE.
 (2) 37.3.5.3 PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED IN ALL
 MERCANTILE OCCUPANCIES IN ACCORDANCE WITH SECTION 9.9.
  
 C. WALKER
 561-804-4762
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-15 Cont ID  
Sent By cwalker Date 2022-03-15 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-15 12:03:41FIRE PROVISO COMMENTS
 (1) DOOR HARDWARE, NFPA 101 LIFE SAFETY CODE
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE
 EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO
 HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED
 THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43
 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
 7.2.1.5.5.2 THE ALTERNATIVE PROVISIONS OF 7.2.1.5.5.1
 SHALL BE
 PERMITTED TO BE REVOKED BY THE AUTHORITY HAVING
 JURISDICTION
 FOR CAUSE.
 (2) PORTABLE FIRE EXTINGUISHERS, NFPA 101 LIFE SAFETY
 CODE
 37.3.5.3 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
 IN ALL
 MERCANTILE OCCUPANCIES IN ACCORDANCE WITH SECTION 9.9.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By fmittner Date 2022-04-01 Time 15:49 Rev Time 0.00
Received By fmittner Date 2022-04-01 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-15 Cont ID  
Sent By mpeterso Date 2022-06-15 Time 15:04 Rev Time 0.00
Received By mpeterso Date 2022-06-15 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 10:09 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-01 Cont ID  
Sent By medwards Date 2022-06-01 Time 14:02 Rev Time 0.00
Received By jleahy Date 2022-05-02 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-22 Cont ID  
Sent By aoliver Date 2022-04-22 Time 07:36 Rev Time 0.00
Received By aoliver Date 2022-03-11 Time 15:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By aoliver Date 2022-06-29 Time 11:37 Rev Time 0.00
Received By aoliver Date 2022-06-16 Time 14:52 Sent To  
Notes
2022-06-28 17:04:17RECEIPT MU-2022-028410 - $3761.21 PAID
2022-06-16 14:52:226/16/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 12:41 Sent To  
Notes
2022-04-04 12:41:12PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 14:01 Rev Time 0.00
Received By medwards Date 2022-05-23 Time 14:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 10:19 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 10:19 Sent To  
Notes
2022-04-11 10:19:391ST REVIEW FMC
 PERMIT: 22030266
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY CALCULATIONS: PAGE 19 OF 27 CALLS OUT THE
 AREA FOR AHU-1 AS 913 SQ.FT. AND THE AREA FOR THE RTU-1
 IS 1460. PAGE 1 OF 2 FOR THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS CALLS OUT 1318 SQ. FT. FOR THE
 AHU-1 AND PAGE 2 OF 2 CALLS OUT 1460 SQ. FT. OF AREA
 FOR THE RTU-1. PLEASE CORRECT THIS AS EACH SHOULD BE
 BASED ON THE SAME SQ. FT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-09 Cont ID  
Sent By rwbrown Date 2022-06-09 Time 08:39 Rev Time 0.00
Received By rwbrown Date 2022-06-09 Time 08:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 13:44 Rev Time 0.00
Received By rwbrown Date 2022-05-18 Time 13:05 Sent To  
Notes
2022-05-18 13:43:581ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. V7 FPC 607.1.1 - YOU HAVE ADDED A DETAIL FOR A WATER
 HEATER ON P0.1 DETAIL NO. 6. THIS DOES NOT SHOW THE
 SAME THERMOSTATIC MIXING DEVICE REQUIRED. PLEASE AMMEND
 THE DETAIL.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By rwbrown Date 2022-04-05 Time 06:16 Rev Time 0.00
Received By rwbrown Date 2022-04-05 Time 06:14 Sent To  
Notes
2022-04-05 06:15:051ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. V7 FPC 403.1 MINIMUM NUMBER OF FIXTURES. A SERVICE
 SINK IS REQUIRED. WHEN PROVIDING HOT WATER TO THE
 SERVICE SINK, PLEASE PROVIDE IN COMPLIANCE WITH V7 FPC
 607.1.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 11:55 Sent To  
Notes
2022-04-04 11:55:58ROOFING SYSTEM TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-06-15 Cont ID  
Sent By mpeterso Date 2022-06-15 Time 15:04 Rev Time 0.00
Received By mpeterso Date 2022-06-15 Time 15:04 Sent To  
Notes
2022-06-15 15:07:246/15/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 10:05 Sent To  
Notes
2022-06-09 10:06:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ARCHITECTURAL DRAWINGS AND STRUCTURAL DRAWINGS DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 08:20 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 08:20 Sent To  
Notes
2022-05-18 08:20:25SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ARCHITECTURAL DRAWINGS, STRUCTURAL DRAWINGS AND
 MECHANICAL EQUIPMENT TIE DOWN DRAWINGS FROM DOUGLAS J.
 RUGGIANO P.E. DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By rmcphers Date 2022-04-04 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 12:50 Sent To  
Notes
2022-04-04 12:53:36SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ARCHITECTURAL DRAWINGS, STRUCTURAL DRAWINGS AND
 MECHANICAL EQUIPMENT TIE DOWN DRAWINGS FROM DOUGLAS J.
 RUGGIANO P.E. DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-05-17 Cont ID  
Sent By vbroglia Date 2022-05-17 Time 16:59 Rev Time 0.00
Received By vbroglia Date 2022-05-17 Time 16:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-13 Cont ID  
Sent By vbroglia Date 2022-05-13 Time 09:45 Rev Time 0.00
Received By vbroglia Date 2022-05-13 Time 09:45 Sent To  
Notes
2022-05-13 09:46:285/13/2022 FAILED
  
 PLEASE APPLY FOR A LANDSCAPE PERMIT TO ALLOW THIS
 PERMIT TO MOVE FORWARD
  
 PLEASE SEE PREVIOUS COMMENTS
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-18 Cont ID  
Sent By vbroglia Date 2022-03-18 Time 13:22 Rev Time 0.00
Received By vbroglia Date 2022-03-18 Time 13:22 Sent To  
Notes
2022-03-18 14:22:493/18/2022 FAILED
 THE VALUE OF THE CONSTRUCTION ($350,000.00) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($292,487) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 SEPARATE PERMIT FOR LANDSCAPE IS REQUIRED AND MUST BE
 SUBMITTED TO ALLOW STAFF TO MOVE FORWARD
  
 SEPARATE PERMIT IS REQUIRED FOR PARKING SPACES, PAVING
 AND NEW ASPHALT. PLEASE FOLLOW THE STALL PAINTING
 DETAIL PROVIDED IN SECTION 94-845 (J) OF THE ZLDR
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  