| Plan Review Stops For Permit 22030245 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-04-11 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-04-11 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2022-04-11 16:22:12 | A SECOND ADDRESS WILL NEED TO BE ASSIGNED IF ZONING | | | ALLOWS ANOTHER UNIT, PLEASE CONTACT [email protected] OR | | | CALL 561-805-6659 ONCE THE WORK HAS BEEN APPROVED BY | | | THE ZONING DEPARTMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2022-04-30 08:41:30 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 | | | FBC, FOR THE PROPOSED WINDOWS AND DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | NOTICE: VERIFY EGRESS AT NEW SLEEPING ROOM. | | | | | | R310.2.1MINIMUM OPENING AREA. | | | | | | EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET | | | CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530 | | | M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS | | | SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF | | | THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE | | | INSIDE. THE NET CLEAR HEIGHT OPENING SHALL BE NOT LESS | | | THAN 24 INCHES (610 MM) AND THE NET CLEAR WIDTH SHALL | | | BE NOT LESS THAN 20 INCHES (508 MM). | | | | | | EXCEPTION: GRADE FLOOR OR BELOW GRADE OPENINGS SHALL | | | HAVE A NET CLEAR OPENING OF NOT LESS THAN 5 SQUARE FEET | | | (0.465 M2). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-04-08 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-04-08 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2022-04-08 14:48:57 | ELECTRIC REVIEW FAILED | | | 1) ELECTRIC RISER DOES NOT MATCH DETAILS ON ELECTRIC | | | DRAWING. ELECTRIC DRAWING DETAILS A METER. PLEASE | | | PROVIDE CORRECT DRAWING MATCHING CONDITIONS ON SITE. | | | FBC 107.2 | | | 2) LOAD CALCULATION DETAILS A 3000 WATT TANKLESS WATER | | | HEATER AND PANEL SCHEDULE DETAILS A 50 AMP BREAKER. | | | PLEASE PROVIDE TANKLESS WATER HEATER SPECS AND CORRECT | | | DRAWING ACCORDINGLY. FBC 107.2 | | | 3) DRYER IN LOAD IS LISTED AT 1,800 WATTS. NEC STATES | | | DRYER LOAD SHALL BE 5,000 WATTS OR NAME PLATE WHICH | | | EVER IS LARGER.PLEASE CORRECT AS PER NEC 220.54 | | | 4) ELECTRIC RISER DETAILS A 175-AMP MAIN BREAKER IN A | | | 150- AMP RATED PANEL . OVER CURRENT PROTECTION FOR A | | | PANEL BOARD CANNOT BE GREATER THAN THE PANEL BOARD | | | RATING. NEC 408.36 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-05 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2022-04-30 08:16:50 | IMPACT FEE QUESTIONNAIRE | | | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-11 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-11 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2022-04-11 06:52:24 | 1ST REVIEW FMC | | | PERMIT: 22030245 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IS THIS THE MAIN HOUSE ON THIS PROPERTY? IF NOT | | | IDENTIFY ON THE DRAWINGS WHERE THIS STRUCTURE IS | | | LOCATED ON THE PROPERTY. FBC 107.2.1 | | | | | | 2) PROVIDE THE ENERGY CALCULATIONS. FEC R402 | | | | | | 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7 | | | | | | 4) THE APPLICATION STATS THERE IS TO BE NEW HVAC, | | | PROVIDE A MECHANICAL DRAWING SHOWING THIS NEW HVAC. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-06 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-06 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2022-04-30 08:15:36 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-11 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-04-11 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-04-07 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2022-04-11 16:14:27 | 4/11/2022 FAILED | | | | | | PLEASE PROVIDE A SURVEY OF THE PROPERTY TO SHOW CLEARLY | | | WHERE THE SCOPE OF WORK IS BEING PROPOSED | | | | | | PLEASE NOTE THIS PROPERTY IS ZONED SF7, WHICH ONLY | | | PERMITS ONE DWELLING UNIT (SINGLE-FAMILY HOME) | | | | | | VALENTINA BROGLIA, ASSOCIATE PLANNER | | | [email protected] | | | |
|
|