Plan Review Details - Permit 22030165
Plan Review Stops For Permit 22030165
Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-02-01 Cont ID  
Sent By lquinone Date 2023-02-01 Time 11:34 Rev Time 0.00
Received By lquinone Date 2023-02-01 Time 11:49 Sent To  
Notes
2023-02-01 11:36:26PASSED WITH PROVISO.
  
 AS PER DETAIL PROVIDED, CONCRETE NEED TO BE 6 IN. THICK
 AROUND METER BOX 18 IN. OUT, AND PLEASE CONTACT
 [email protected] FOR HEAVY DUTY METER BOX AND LID BEFORE
 POUR.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-01-31 Cont ID  
Sent By lquinone Date 2023-01-31 Time 14:42 Rev Time 0.00
Received By lquinone Date 2023-01-31 Time 14:42 Sent To  
Notes
2023-01-31 14:48:38PLEASE PROVIDE UPDATED SURVEY AS PER CONVERSATION;
  
 - IF THERE IS NO RELOCATION OF WM, THEN PROVIDE DETAIL
 WITH 6 IN THICK CONCRETE AROUND METER BOX 18" OUT.
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-11-07 Cont ID  
Sent By rrossano Date 2022-11-07 Time   Rev Time 0.00
Received By rrossano Date 2022-11-07 Time   Sent To  
Notes
2022-11-07 11:47:52IF DRIVEWAY APRON CONTAINING EXISTING WATER METER IS
 BEING RECONSTRUCTED, COORDINATE WITH CITY OF WPB PUBLIC
 UTILITIES CUSTOMER SERVICE TO RELOCATE THE EXISTING
 WATER METER OUTSIDE OF THE DRIVEWAY APRON. CALL
 561-822-1300.
  
 CONSTRUCT DRIVEWAY APRON(S) IN COMPLIANCE WITH WPB
 CONSTRUCTION STANDARD DETAIL GC-5 (WHEN DISTANCE
 BETWEEN CURB OR EDGE OF PAVEMENT IS 10 FT. OR GREATER),
 OR STANDARD DETAIL GC-6 (WHEN DISTANCE BETWEEN CURB OR
 EDGE OF PAVEMENT IS LESS THAN 10 FT.) CITY STANDARD
 DETAIL IS REQUIRED, SEE LINK BELOW: HTTPS://WWW.WPB.ORG
 /GOVERNMENT/ENGINEERING/ENGINEERING-STANDARDS-DETAILS
  
 MAXIMUM DRIVEWAY WIDTHS AT RIGHT OF WAY SHALL NOT
 EXCEED 20 FT. PLUS TWO 3 FT. FLARES. (TWO 10 FT.
 DRIVEWAYS PLUS 3 FT. FLARES ON EACH ARE ACCEPTABLE).
  
 TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN
 REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND
 WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT
 FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING
 BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN
 REVIEW TIME.
  
 ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DONT
 UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST
 PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO
 DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE
 AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN
 REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES
 WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S
 ERVICES/PERMITS AND SEE - WHERE CAN I FIND MY PLAN
 REVIEW COMMENTS ONLINE - FOR INSTRUCTIONS.
  
 FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON
 WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION
 TEAM MEMBER WILL HELP YOU.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By rrossano Date 2022-03-28 Time   Rev Time  
Received By rrossano Date 2022-03-28 Time   Sent To  
Notes
2022-03-28 11:21:56INDICATE AREAS OF PROPOSED DRIVEWAY CONSTRUCTION ON A
 COPY OF THE PROPERTY SURVEY.
  
 DIMENSION DRIVEWAYS, LOCATED HORIZONTALLY AND
 VERTICALLY.
  
 CALL OUT SETBACK. SHOW ANY WATER METERS, SANITARY
 CLEANOUTS, STORM INLETS ETC. IN VICINITY OF PROPOSED
 DRIVEWAY.
  
 CONSTRUCT DRIVEWAY APRON IN COMPLIANCE WITH WPB
 CONSTRUCTION STANDARD DETAIL GC-5 (WHEN DISTANCE
 BETWEEN CURB OR EDGE OF PAVEMENT IS 10 FT. OR GREATER),
 OR STANDARD DETAIL GC-6 (WHEN DISTANCE BETWEEN CURB OR
 EDGE OF PAVEMENT IS LESS THAN 10 FT.) CITY STANDARD
 DETAIL IS REQUIRED, SEE LINK BELOW: HTTPS://WWW.WPB.ORG
 /GOVERNMENT/ENGINEERING/ENGINEERING-STANDARDS-DETAILS
  
 UPDATE SURVEY WITH REQUESTED INFORMATION AND RESUBMIT
 WITH A COPY OF THE APPLICABLE STANDARD DETAIL FOR
 DRIVEWAYS.
  
 TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN
 REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND
 WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT
 FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING
 BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN
 REVIEW TIME.
  
 ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DON?T
 UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST
 PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO
 DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE
 AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN
 REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES
 WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S
 ERVICES/PERMITS AND SEE ?WHERE CAN I FIND MY PLAN
 REVIEW COMMENTS ONLINE?? FOR INSTRUCTIONS.
  
 FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON
 WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION
 TEAM MEMBER WILL HELP YOU.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, CITY OF WPB
 ENGINEERING SERVICES DEPARTMENT
 (561) 494-1098, FAX: (561) 494-1116 EMAIL:
 [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-01 Cont ID  
Sent By aoliver Date 2023-02-01 Time 07:17 Rev Time 0.00
Received By aoliver Date 2023-01-18 Time 17:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-07 Cont ID  
Sent By asangele Date 2022-11-07 Time 14:45 Rev Time 0.00
Received By asangele Date 2022-11-07 Time 14:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-04 Cont ID  
Sent By asangele Date 2022-04-04 Time 16:08 Rev Time 0.00
Received By asangele Date 2022-04-04 Time 16:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-01-20 Cont ID  
Sent By asangele Date 2023-01-20 Time 15:31 Rev Time 0.00
Received By asangele Date 2023-01-20 Time 15:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-11-07 Cont ID  
Sent By asangele Date 2022-11-07 Time 14:45 Rev Time 0.00
Received By asangele Date 2022-11-07 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By asangele Date 2022-04-04 Time 16:05 Rev Time 0.00
Received By asangele Date 2022-04-04 Time 16:05 Sent To  
Notes
2022-04-04 16:08:064/4/2022
 FAILED
 PLEASE PROVIDE A SURVEY WITH SETBACKS
 DRIVEWAY CANNOT EXCEED 20FT IN WIDTH AND HAS TO BE 3FT
 FROM THE SIDE OF THE PROPERTY LINE
 FRONT LANDSCAPE REQUIREMENT LESSER OF 1,000 SQUARE FEET
 OR 75 PERCENT OF THE FRONT YARD AREA SHALL BE
 LANDSCAPED WITH LIVING PLANT MATERIAL (SUCH AS GRASS,
 GROUND COVER, SHRUBS, HEDGES, VINES OR TREES).
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]