Plan Review Details - Permit 22030091
Plan Review Stops For Permit 22030091
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By jwitmer Date 2022-05-03 Time 17:14 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-05-03 17:14:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030091
 ADD: 3705 S. FLAGLER DR. # 28
 CONT: ROBERT P RUBINO INC
 TEL: 561-445-2010
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 3RD/ 2022
 ACTION: DENIED
  
 MISSING PLAN REVIEW ITEMS. 2020 W. P. B. ADMINISTRATIVE
 CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
  
 1) SITE PLAN WITH LAYOUT, FOOTPRINT OF BUILDING WITH
 UNIT LOCATION IN THE BUILDING IN RELATION TO THE
 INTERCOASTAL WATERWAY.
  
 2.1) FLOOR PLAN OF UNIT WITH WINDOWS AND OR DOORS TO BE
 REPLACED & OPENING SCHEDULE WITH PRESSURES .
  
 2.2 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS AND OR SCHEDULES WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS AND OR SCHEDULES DRAWN.
  
 3) MISSING WINDOW AND OR DOOR PRODUCT APPROVAL.
  
 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5) 2020 FBC-B 1603.1.4 WIND DESIGN DATA, BY A ENGINEER.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 5.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER
 INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2.
 SILL LIMITING FACTOR.
  
 6) 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES,
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWARD DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C , AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT,
 WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 7 A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-05-03 Time   Rev Time 0.00
Received By cdecoeur Date 2022-04-20 Time 07:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-03 Cont ID  
Sent By jwitmer Date 2022-05-03 Time 17:14 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved