Plan Review Details - Permit 22030020
Plan Review Stops For Permit 22030020
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By pvalenti Date 2022-05-26 Time 06:36 Rev Time 0.00
Received By pvalenti Date 2022-05-26 Time 06:25 Sent To  
Notes
2022-05-26 07:54:42PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, THE SUBMITTED PLAN NEEDS MORE
 DETAIL. PLEASE SHOW ALL DIMENSIONS, LOCATION OF BACK
 SCREEN ENCLOSURE, INTERIOR ROOMS, & GARAGE.
 2.) FBC B 107.2.1, PROVIDE A SITE-PLAN TO SHOW LOCATION
 OF HOUSE, STREET, PROPERTY LINES AND ALL SET-BACK
 DIMENSIONS.
 3.) FBC B 107.2.1, PROVIDE DETAILS FOR MATERIALS TO BE
 USED, SLAB REPLACEMENT DETAILS FOR AREAS CUT FOR
 PLUMBING WORK, NEW WALL DETAILS, & EXTERIOR OPENING
 (WINDOWS/DOORS) DETAILS IF APPLICABLE.
 4.) FBC B/WPB AMENDMENTS TO CODE 107.2.1, THE OWNER
 MUST PRINT & SIGN NAME ON SUBMITTED PLANS/INFORMATION
 IF HE OR SHE IS THE INDIVIDUAL RESPONSIBLE FOR THE
 SUBMITTED INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By fgiaquin Date 2022-03-22 Time 23:14 Rev Time 0.00
Received By fgiaquin Date 2022-03-22 Time 23:12 Sent To  
Notes
2022-03-22 23:14:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-26 Cont ID  
Sent By pvalenti Date 2022-05-26 Time 08:28 Rev Time 0.00
Received By pvalenti Date 2022-03-01 Time 13:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By pvalenti Date 2022-05-26 Time 08:13 Rev Time 0.00
Received By pvalenti Date 2022-05-26 Time 08:13 Sent To  
Notes
2022-05-26 08:16:06PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 11:12 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 11:12 Sent To  
Notes
2022-03-10 11:16:05PLEASE SHOW VENTILATION FOR THE BATHROOM MEETS FBC RES
 R303.3
  
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING
 AREA IN WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3
 M2), ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED.
 THE MINIMUM LOCAL EXHAUST RATES SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION M1507. EXHAUST AIR FROM THE
 SPACE SHALL BE EXHAUSTED DIRECTLY TO THE OUTDOORS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-07 Cont ID  
Sent By rwbrown Date 2022-03-07 Time 15:05 Rev Time 0.00
Received By rwbrown Date 2022-03-07 Time 14:59 Sent To  
Notes
2022-03-07 15:04:541ST PLUMBING REVIEW
  
 V7 FBC P - 2020 FLORIDA PLUMBING CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. 2017 WPB AMEND - 107.3.5.3 (12.) -- PLEASE SUBMIT A
 PLUMBING RISER. PLEASE INCLUDE THE SIGNATURE OF THE
 PERSON WHO DESIGNED THE ISOMETRIC AS A REQUIREMENT OF
 107.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By pvalenti Date 2022-05-26 Time 08:16 Rev Time 0.00
Received By pvalenti Date 2022-05-26 Time 06:25 Sent To  
Notes
2022-05-26 08:28:06PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE A CLARIFICATION IF A NEW
 SECTION OF ROOFING FOR THE PURPOSE OF THIS PERMIT IS
 PROPOSED OR IF THERE IS NO NEW ROOFING PROPOSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-26 Cont ID  
Sent By pvalenti Date 2022-05-26 Time 08:12 Rev Time 0.00
Received By pvalenti Date 2022-05-26 Time 06:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By kdefranc Date 2022-03-04 Time 16:32 Rev Time 0.00
Received By kdefranc Date 2022-03-04 Time 16:25 Sent To  
Notes
2022-03-04 16:28:383/4/22 ? FAILED
  
  
 1. PLEASE PROVIDE A CURRENT SURVEY OF THE SUBJECT
 PROPERTY.
 2. PLEASE PROVIDE A REVISED SKETCH/LOT/SITE PLAN
 IDENTIFYING/INDICATING/DEMONSTRATING THE FOLLOWING:
 - PROPERTY LINES;
 - LOCATION/FOOTPRINT OF THE EXISTING PRINCIPLE
 STRUCTURE (RESIDENCE/HOUSE);
 - LOCATION/DELINEATION OF THE PROPOSED ADDITIONS
 (BATHROOM AND STORAGE AREAS);
 - EXISTING AND PROPOSED SETBACK DIMENSIONS FOR
 PRINCIPAL STRUCTURE (RESIDENCE/HOUSE) FROM THE PROPERTY
 LINES; AND
 - EXISTING AND PROPOSED HEIGHT(S) OF THE PRINCIPAL
 STRUCTURE (RESIDENCE/HOUSE).
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  