| Plan Review Stops For Permit 22030020 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-26 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-26 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2022-05-26 07:54:42 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, THE SUBMITTED PLAN NEEDS MORE | | | DETAIL. PLEASE SHOW ALL DIMENSIONS, LOCATION OF BACK | | | SCREEN ENCLOSURE, INTERIOR ROOMS, & GARAGE. | | | 2.) FBC B 107.2.1, PROVIDE A SITE-PLAN TO SHOW LOCATION | | | OF HOUSE, STREET, PROPERTY LINES AND ALL SET-BACK | | | DIMENSIONS. | | | 3.) FBC B 107.2.1, PROVIDE DETAILS FOR MATERIALS TO BE | | | USED, SLAB REPLACEMENT DETAILS FOR AREAS CUT FOR | | | PLUMBING WORK, NEW WALL DETAILS, & EXTERIOR OPENING | | | (WINDOWS/DOORS) DETAILS IF APPLICABLE. | | | 4.) FBC B/WPB AMENDMENTS TO CODE 107.2.1, THE OWNER | | | MUST PRINT & SIGN NAME ON SUBMITTED PLANS/INFORMATION | | | IF HE OR SHE IS THE INDIVIDUAL RESPONSIBLE FOR THE | | | SUBMITTED INFORMATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-22 |
Time |
23:14 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-22 |
Time |
23:12 |
Sent To |
|
|
| Notes |
| 2022-03-22 23:14:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY | | | THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-26 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-03-01 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-26 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-26 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2022-05-26 08:16:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-10 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-10 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2022-03-10 11:16:05 | PLEASE SHOW VENTILATION FOR THE BATHROOM MEETS FBC RES | | | R303.3 | | | | | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING | | | AREA IN WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 | | | M2), ONE-HALF OF WHICH MUST BE OPENABLE. | | | | | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE | | | PROVIDED. | | | THE MINIMUM LOCAL EXHAUST RATES SHALL BE DETERMINED IN | | | ACCORDANCE WITH SECTION M1507. EXHAUST AIR FROM THE | | | SPACE SHALL BE EXHAUSTED DIRECTLY TO THE OUTDOORS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-03-07 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-03-07 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2022-03-07 15:04:54 | 1ST PLUMBING REVIEW | | | | | | V7 FBC P - 2020 FLORIDA PLUMBING CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | | | | 1. 2017 WPB AMEND - 107.3.5.3 (12.) -- PLEASE SUBMIT A | | | PLUMBING RISER. PLEASE INCLUDE THE SIGNATURE OF THE | | | PERSON WHO DESIGNED THE ISOMETRIC AS A REQUIREMENT OF | | | 107.2.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-26 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-26 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2022-05-26 08:28:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW DENIED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE A CLARIFICATION IF A NEW | | | SECTION OF ROOFING FOR THE PURPOSE OF THIS PERMIT IS | | | PROPOSED OR IF THERE IS NO NEW ROOFING PROPOSED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-26 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-26 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
2022-03-04 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
2022-03-04 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2022-03-04 16:28:38 | 3/4/22 ? FAILED | | | | | | | | | 1. PLEASE PROVIDE A CURRENT SURVEY OF THE SUBJECT | | | PROPERTY. | | | 2. PLEASE PROVIDE A REVISED SKETCH/LOT/SITE PLAN | | | IDENTIFYING/INDICATING/DEMONSTRATING THE FOLLOWING: | | | - PROPERTY LINES; | | | - LOCATION/FOOTPRINT OF THE EXISTING PRINCIPLE | | | STRUCTURE (RESIDENCE/HOUSE); | | | - LOCATION/DELINEATION OF THE PROPOSED ADDITIONS | | | (BATHROOM AND STORAGE AREAS); | | | - EXISTING AND PROPOSED SETBACK DIMENSIONS FOR | | | PRINCIPAL STRUCTURE (RESIDENCE/HOUSE) FROM THE PROPERTY | | | LINES; AND | | | - EXISTING AND PROPOSED HEIGHT(S) OF THE PRINCIPAL | | | STRUCTURE (RESIDENCE/HOUSE). | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|