Plan Review Details - Permit 22021426
Plan Review Stops For Permit 22021426
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 15:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-21 Cont ID  
Sent By mpeterso Date 2022-04-04 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 11:54 Sent To  
Notes
2022-04-21 13:21:19PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 15:56 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 12:18 Rev Time 0.00
Received By jleahy Date 2022-05-18 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By mpeterso Date 2022-04-04 Time 14:09 Rev Time 0.00
Received By mpeterso Date 2022-04-04 Time 08:57 Sent To  
Notes
2022-04-04 14:10:42ELECTRIC REVIEW FAILED
 1) ROOM LABELED IT/STORAGE ENCLOSES ELECTRIC PANEL
 WHERE NO STORAGE IS ALLOWED AS PER. PLEASE REMOVE
 STORAGE FROM THIS ROOM LABEL. NEC 110.26 (B)
 2) PLEASE INCLUDE A NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR, LOW VOLTAGE, FIRE ALARM, ACCESS CONTROL
 3) PLEASE ENSURE COMPLIANCE WITH NEC 210.71 (B)(1)
 RECEPTACLES REQUIRED ON FIXED WALLS IN MEETING ROOMS
 4) CONDUCTOR SIZE ON PRIMARY SIZE OF TRANSFORMER IS
 SIZED INCORRECTLY AT #8 CU, PLEASE CORRECT CONDUCTOR
 SIZE TO A #6 CU AS PER NEC 110.14(C)(1)(2). TERMINATION
 OF CIRCUITS RATED 100-AMPERES OR LESS MUST BE SIZED
 USING 65 DEGREE C.
 5) CONDUCTOR SIZE ON SECONDARY SIZE OF TRANSFORMER IS
 SIZED INCORRECTLY AT #2 CU, PLEASE CORRECT CONDUCTOR
 SIZE TO A #1 CU AS PER NEC 110.14(C)(1)(2). TERMINATION
 OF CIRCUITS RATED 100-AMPERES OR LESS MUST BE SIZED
 USING 65 DEGREE C.
 6) PLANS DO NOT DETAIL MAIN BREAKER IN LOW VOLTAGE
 PANEL. PLEASE CORRECT AS PER NEC 408.36
 7) PLEASE DETAIL TRANSFORMER GROUNDING. FBC 107.2
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-10-26 Cont ID  
Sent By mpeterso Date 2022-10-26 Time 10:46 Rev Time 0.00
Received By mpeterso Date 2022-10-26 Time 10:46 Sent To  
Notes
2022-10-26 10:47:00PHONE AND DATA ONLY. MP

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-29 Cont ID  
Sent By pleduc Date 2022-04-29 Time   Rev Time 0.00
Received By pleduc Date 2022-04-29 Time 12:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By pleduc Date 2022-04-04 Time   Rev Time 0.00
Received By pleduc Date 2022-04-04 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 16:00 Rev Time 0.00
Received By medwards Date 2022-05-22 Time 14:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 12:18 Rev Time 0.00
Received By jleahy Date 2022-04-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:31 Rev Time 0.00
Received By rmcphers Date 2022-04-01 Time 10:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:31 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 13:31 Sent To  
Notes
2022-04-21 13:31:48NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 15:58 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 09:33 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 09:33 Sent To  
Notes
2022-05-05 09:36:25THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SUBMITTED
 DID NOT CONTAIN THE COMPLETE DOCUMENT, ONLY THE FIRST 3
 SHEETS WERE SUBMITTED. THE ACTUAL CALCULATIONS WERE
 OMITTED. PLEASE PROVIDE A COMPLETE SIZING CALCULATION
 DOCUMENT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By medwards Date 2022-04-06 Time 08:22 Rev Time 0.00
Received By medwards Date 2022-04-06 Time 07:35 Sent To  
Notes
2022-04-06 08:22:481ST REVIEW FMC
 PERMIT: 22021426
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COULD NOT COMPLETE THE MECHANICAL REVIEW:
 2) THE MECHANICAL ZONE MAP AND THE EQUIPMENT SIZING
 CALCULATIONS SHOW 3 HP?S THE MECHANICAL FLOOR PLAN DOES
 NOT MATCH. PLEASE PROVIDE A MECHANICAL FLOOR PLAN
 CONSISTENT WITH THE ZONE MAP PLAN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-29 Cont ID  
Sent By rwbrown Date 2022-04-29 Time 13:13 Rev Time 0.00
Received By rwbrown Date 2022-04-29 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By rwbrown Date 2022-04-04 Time 13:25 Rev Time 0.00
Received By rwbrown Date 2022-04-04 Time 12:49 Sent To  
Notes
2022-04-04 13:25:211ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.2.1 ? PAGE P1.1 ? PLEASE SHOW
 WHAT TYPE OF DRAIN STACK OR WASTE STACK THE FIXTURE
 DRAIN TO THE SINK CONNECTS TO FOR CODE REVIEW.
  
 2. V7 FPC 607.1.1 ? PLEASE DETAIL THE DEVICE THAT WILL
 BE USED TO LIMIT THE TEMPERATURE ?OTHER THAN THE
 THERMOSTAT? ON THE WATER HEATER FOR THE HOT WATER
 DELIVERY TO THE SINK.
  
 3. V7 FPC 403.1/ 403.3.3 ? PLEASE SHOW WHERE THE
 REQUIRED FACILITIES ARE LOCATED TO SHOW COMPLIANCE WITH
 THE MINIMUM FACILITIES REQUIREMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 15:56 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 15:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 13:30 Sent To  
Notes
2022-04-06 08:23:27MECHANICAL DIGITAL SIGNATURE REVIEW APPROVED ME