Plan Review Details - Permit 22021422
Plan Review Stops For Permit 22021422
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By rmcphers Date 2022-06-27 Time 09:00 Rev Time 0.00
Received By rmcphers Date 2022-06-27 Time 09:00 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By rmcphers Date 2022-04-25 Time 09:03 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 17:17 Sent To  
Notes
2022-04-25 09:05:06PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By rmcphers Date 2022-07-19 Time 08:08 Rev Time 0.00
Received By rmcphers Date 2022-07-19 Time 08:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-27 Cont ID  
Sent By rmcphers Date 2022-06-27 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2022-06-27 Time 08:56 Sent To  
Notes
2022-06-27 08:59:54REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING IN-501 DETAIL D1 SHOWS TOILET SIDE GRAB BAR
 LESS THEN THE REQUIRED 54 INCH FROM THE BACK WALL - FBC
 A 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 08:48 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By rmcphers Date 2022-04-25 Time 09:17 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 17:17 Sent To  
Notes
2022-04-25 09:17:54REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE ADDRESS ON THE PLANS DOES NOT MATCH THE ADDRESS
 ON THE BUILDING PERMIT APPLICATION.
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE (18") BESIDE THE LATCH SIDE TO
 EXIT THE RESTROOM (DOORS D0703 AND D0803) - FBC A
 404.2.4
  
 3) ACCESSIBLE RESTROOM - THE GRAB BAR HEIGHT SHOULD BE
 SHOWN FROM THE TOP OF THE GRIPPING SURFACE NOT THE
 CENTER OF THE BAR PER FBC A 609.4 POSITION OF GRAB
 BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 4) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION
 DIMENSIONS FROM THE FACE OF THE TOILET TO THE CENTER
 THE TOILET PAPER HOLDER - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 5) ACCESSIBLE RESTROOMS - PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" OF THE MIRROR WHEN REFERRING TO
 THE DIMENSIONS FROM THE FLOOR - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-05 Cont ID  
Sent By mpeterso Date 2022-07-05 Time 13:14 Rev Time 0.00
Received By mpeterso Date 2022-07-05 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 09:56 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-07 Cont ID  
Sent By jleahy Date 2022-04-07 Time 12:12 Rev Time 0.00
Received By jleahy Date 2022-04-06 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-22 Cont ID  
Sent By pleduc Date 2022-06-22 Time   Rev Time 0.00
Received By pleduc Date 2022-06-22 Time 11:46 Sent To  
Notes
2022-06-22 11:46:31FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-20 Cont ID  
Sent By pleduc Date 2022-05-20 Time   Rev Time 0.00
Received By pleduc Date 2022-05-20 Time 11:55 Sent To  
Notes
2022-05-20 12:15:13FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By pleduc Date 2022-04-04 Time   Rev Time 0.00
Received By pleduc Date 2022-04-04 Time 15:21 Sent To  
Notes
2022-04-04 16:15:14FIRE PROVISO:
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-19 Cont ID  
Sent By rmcphers Date 2022-07-19 Time 08:10 Rev Time 0.00
Received By rmcphers Date 2022-07-06 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-05 Cont ID  
Sent By mpeterso Date 2022-07-05 Time 13:14 Rev Time 0.00
Received By mpeterso Date 2022-06-18 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 09:56 Rev Time 0.00
Received By mpeterso Date 2022-05-19 Time 08:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-25 Cont ID  
Sent By rmcphers Date 2022-04-25 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2022-04-01 Time 09:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-25 Cont ID  
Sent By rmcphers Date 2022-04-25 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2022-04-25 Time 09:18 Sent To  
Notes
2022-04-25 09:18:52NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-04-20 Cont ID  
Sent By hmoser Date 2022-04-20 Time 13:10 Rev Time 0.00
Received By hmoser Date 2022-04-20 Time 12:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 07:33 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-06-24 Cont ID  
Sent By ccole Date 2022-06-24 Time 10:21 Rev Time 0.00
Received By ccole Date 2022-06-24 Time 08:44 Sent To  
Notes
2022-06-24 10:21:37 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22021422
 6/24/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION.
  
 2H) FAILED- 2ND REQUEST. LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SEC. 604.5 & 609.4, FIGURES 604. PLEASE NOTE THE
 DETAILS SHOW THE HEIGHTS MEASURED TO THE CENTER OF THE
 BARS AND NOT THE TOPS OF THE SURFACES. THE SIDE GRAB
 BAR SHALL EXTEND A MINIMUM OF 54-INCHES FROM THE REAR
 WALL. THE DETAIL INDICATES 48-INCHES. PLEASE PROVIDE A
 CORRECT DETAIL FOR BOTH THE MEN?S AND WOMEN?S
 ACCESSIBLE COMPARTMENTS- FIGURES 604.5.1 & 604.5.2 FBC
 ACC.
  
 3) FAILED- 2ND REQUEST. P-101: PLEASE REMOVE NOTE 3 ON
 THE PLAN INDICATING AN ASSE 1070 APPROVED MIXING VALVE
 AT THE MOP SINK. HOT WATER IS REQUIRED AT THE MOP SINK,
 NOT TEMPERED WATER- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-25 Cont ID  
Sent By ccole Date 2022-05-25 Time 10:20 Rev Time 0.00
Received By ccole Date 2022-05-25 Time 09:40 Sent To  
Notes
2022-05-25 10:20:552ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22021422
 5/25/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION.
  
 1) FAILED. SHEET IN-101.2: PLEASE REFER TO SECS. 202.3,
 213.2 & 213.3.1 FBC ACC- THE NEW MEN?S AND WOMEN?S
 ACCESSIBLE TOILET COMPARTMENTS ARE UNDERSIZED PER SEC.
 604.8.1. THE COMPARTMENTS SHALL BE MINIMUM 60-INCHES
 WIDE. PLEASE NOTE THAT SEC. 405.3.1 FBC P ALLOWS FOR
 THE STANDARD COMPARTMENTS TO BE MINIMUM 30-INCHES WIDE
 WHICH WOULD PROVIDE THE ADDITIONAL SPACE NEEDED TO MEET
 THE CODE FOR THE ACCESSIBLE COMPARTMENTS.
 THE RESUBMITTED PLANS SHOW THE ACCESSIBLE TOILET
 COMPARTMENTS REMAIN UNDERSIZED IN WIDTH. ACCESSIBILTY
 COMPLIANCE TO THE MAXIMUM EXTENT FEASIBLE- PLEASE SEE
 SECTION 202.3 EXCEPTION 2. AS PREVIOUSLY NOTED ABOVE
 THERE IS ADEQUATE SPACE TO PROVIDE THE REQUIRED WIDTH
 FOR THE COMPARTMENTS.
  
 2) FAILED ITEMS BELOW SHEET IN-501: MISSING
 ACCESSIBILITY COMPLIANCE DETAILS PER FBC ACC-
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SEC. 604.3.NOT PROVIDED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- SEC. 606.2. NOT PROVIDED.
 C) FAILED. TURNING SPACE DIAGRAMS AND DIMENSIONS- SEC.
 304.3. NOT PROVIDED.
 D) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALLS- SEC. 604.2. NOT PROVIDED.
 E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SEC. 604.4. NOT PROVIDED.
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4,
 FIGURES 604. PLEASE NOTE THE DETAILS SHOW THE HEIGHTS
 MEASURED TO THE CENTER OF THE BARS AND NOT THE TOPS OF
 THE SURFACES. GRAB BAR MINIMUM LENGTHS AND SPACINGS NOT
 PROVIDED.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND
 FIGURE 604.7. NOT PROVIDED.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2 AND FIGURES 306.2 & 306.3. NOT PROVIDED.
 L) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC.
 602.2. NOT PROVIDED.
 M) FAILED. KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN SEC. 602.2 AND FIGURES
 306.2 & 306.3. NOT PROVIDED.
 N) FAILED. SPOUT HEIGHTS MEASURED FROM THE FINISHED
 FLOOR- SECS. 602.4 & 602.7. NOT PROVIDED.
 O) FAILED. SHOW DRINKING FOUNTAIN COMPLIANCE WITH SEC.
 307.2 PROTRUSION LIMITS. NOT PROVIDED.
  
 3) FAILED. P-101 & P-201: PROVIDE A MEANS OF LIMITING
 THE HOT WATER TEMPERATURE AT THE MOP SINK OTHER THAN
 THE THERMOSTAT CONTROL IN THE WATER HEATER- SEC.
 607.1.1 FBC P. NOTE 3 ON THE PLAN SHOWS AN ASSE 1070
 APPROVED MIXING VALVE AT THE MOP SINK. PLEASE NOTE THE
 ASSE 1070 MIXING VALVES DELIVER TEMPERED WATER BETWEEN
 85 AND 110 DEGREES F. THE SPECIFIED VALVE SHALL BE FOR
 LIMITING HOT WATER TEMPERATURE AT 110 F AND ABOVE.
  
 4) FAILED P-101 & P-102: INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P. PLEASE NOTE THAT MIXING VALVES FOR TEMPERED WATER
 SHALL BE ASSE 1070 APPROVED- SEC. 607.1.2 FBC P. PLACE
 A NOTE TO INDIOCATE COLD WATER ONLY TO THE LAVATORIES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By ccole Date 2022-04-11 Time 12:15 Rev Time 0.00
Received By ccole Date 2022-04-11 Time 10:25 Sent To  
Notes
2022-04-11 12:17:261ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22021422
 4/11/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET IN-101.2: PLEASE REFER TO SECS. 202.3, 213.2 &
 213.3.1 FBC ACC- THE NEW MEN?S AND WOMEN?S ACCESSIBLE
 TOILET COMPARTMENTS ARE UNDERSIZED PER SEC. 604.8.1.
 THE COMPARTMENTS SHALL BE MINIMUM 60-INCHES WIDE.
 PLEASE NOTE THAT SEC. 405.3.1 FBC P ALLOWS FOR THE
 STANDARD COMPARTMENTS TO BE MINIMUM 30-INCHES WIDE
 WHICH WOULD PROVIDE THE ADDITIONAL SPACE NEEDED TO MEET
 THE CODE FOR THE ACCESSIBLE COMPARTMENTS.
  
 2) SHEET IN-501: MISSING ACCESSIBILITY COMPLIANCE
 DETAILS PER FBC ACC-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAGRAMS AND DIMENSIONS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604. PLEASE NOTE THE DETAILS SHOW THE HEIGHTS MEASURED
 TO THE CENTER OF THE BARS AND NOT THE TOPS OF THE
 SURFACES.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 AND FIGURES 306.2 & 306.3.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2.
 M) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN SEC. 602.2 AND FIGURES
 306.2 & 306.3.
 N) SPOUT HEIGHTS MEASURED FROM THE FINISHED FLOOR-
 SECS. 602.4 & 602.7.
 O) SHOW DRINKING FOUNTAIN COMPLIANCE WITH SEC. 307.2
 PROTRUSION LIMITS.
  
 3) P-101 & P-201: PROVIDE A MEANS OF LIMITING THE HOT
 WATER TEMPERATURE AT THE MOP SINK OTHER THAN THE
 THERMOSTAT CONTROL IN THE WATER HEATER- SEC. 607.1.1
 FBC P.
  
 4) P-101 & P-102: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. PLEASE
 NOTE THAT MIXING VALVES FOR TEMPERED WATER SHALL BE
 ASSE 1070 APPROVED- SEC. 607.1.2 FBC P
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 07:33 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 07:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-24 Cont ID  
Sent By ccole Date 2022-06-24 Time 10:25 Rev Time 0.00
Received By ccole Date 2022-06-24 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 08:51 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-25 Cont ID  
Sent By rmcphers Date 2022-04-25 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2022-04-25 Time 09:24 Sent To  
Notes
***NONE***