Plan Review Details - Permit 22021416
Plan Review Stops For Permit 22021416
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-05-23 Cont ID  
Sent By dbattles Date 2022-05-23 Time 09:53 Rev Time 0.00
Received By dbattles Date 2022-05-23 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-05 Cont ID  
Sent By pvalenti Date 2022-10-05 Time 15:46 Rev Time 0.00
Received By pvalenti Date 2022-10-05 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-08 Cont ID  
Sent By pvalenti Date 2022-08-08 Time 13:57 Rev Time 0.00
Received By pvalenti Date 2022-08-08 Time 12:46 Sent To  
Notes
2022-08-08 13:58:35PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND BUILDING REVIEW DENIED:
  
 PLEASE PROVIDE A RESPONSE SHEET TO THIS BUILDING REVIEW
 AS IT APPEARS THAT THE FOLLOWING COMMENTS, FROM THE
 FIRST REVIEW, BELOW HAVE NOT BEEN ADDRESSED.
  
 1.) FBC B 107.2.1, FBC B 1004, ON PLAN SHEET LS 101
 (PROJECT DATA) COMPLETE THE OCCUPANCY SECTION.
 2.) FBC B 107.2.1, ON PLAN SHEET LS 101, (PROJECT DATA)
 CORRECT THE EXISTING BUILDING CODE EDITION FROM 2020
 6TH EDITION TO 2020 7TH EDITION.
 3.) FBC B 107.2.1, ON PLAN SHEET IN 801, COMPLETE THE
 FIRE RATED COLUMN ON THE DOOR SCHEDULE.
 4.) FBC B 107.2.1, PROVIDE PRODUCT APPROVALS FOR ALL
 PROPOSED DOORS.
 5.) FBC B 107.2.1, PLEASE CORRECT PLAN SHEETS LS 101 &
 G 000 TO SHOW THE SAME CONSTRUCTION TYPE AS PLAN SHEET
 LS 101 INDICATES TYPE IIA & G 000 INDICATES TYPE IIB.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-07 Cont ID  
Sent By pvalenti Date 2022-06-07 Time 08:42 Rev Time 0.00
Received By pvalenti Date 2022-06-06 Time 12:14 Sent To  
Notes
2022-06-07 09:22:15PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, FBC B 1004, ON PLAN SHEET LS 101
 (PROJECT DATA) COMPLETE THE OCCUPANCY SECTION.
 2.) FBC B 107.2.1, ON PLAN SHEET LS 101, (PROJECT DATA)
 CORRECT THE EXISTING BUILDING CODE EDITION FROM 2020
 6TH EDITION TO 2020 7TH EDITION.
 3.) FBC B 107.2.1, ON PLAN SHEET IN 801, COMPLETE THE
 FIRE RATED COLUMN ON THE DOOR SCHEDULE.
 4.) FBC B 107.2.1, PROVIDE PRODUCT APPROVALS FOR ALL
 PROPOSED DOORS.
 5.) FBC B 107.2.1, PLEASE CORRECT PLAN SHEETS LS 101 &
 G 000 TO SHOW THE SAME CONSTRUCTION TYPE AS PLAN SHEET
 LS 101 INDICATES TYPE IIA & G 000 INDICATES TYPE IIB.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By mpeterso Date 2022-05-31 Time 16:24 Rev Time 0.00
Received By mpeterso Date 2022-05-31 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By pleduc Date 2022-04-21 Time   Rev Time 0.00
Received By pleduc Date 2022-04-21 Time 11:33 Sent To  
Notes
2022-04-21 13:00:38FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-05 Cont ID  
Sent By pvalenti Date 2022-10-05 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2022-08-23 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-08 Cont ID  
Sent By pvalenti Date 2022-08-08 Time 14:02 Rev Time 0.00
Received By pvalenti Date 2022-06-27 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-07 Cont ID  
Sent By pvalenti Date 2022-06-07 Time 09:23 Rev Time 0.00
Received By pvalenti Date 2022-04-21 Time 05:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-23 Cont ID  
Sent By dbattles Date 2022-05-23 Time 09:53 Rev Time 0.00
Received By dbattles Date 2022-05-23 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-05-20 Cont ID  
Sent By medwards Date 2022-05-20 Time 10:45 Rev Time 0.00
Received By medwards Date 2022-05-20 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By jesmith Date 2022-08-30 Time 13:44 Rev Time 0.00
Received By jesmith Date 2022-08-30 Time 13:38 Sent To  
Notes
2022-08-30 13:44:2322021416 222 LAKEVIEW AVE FL 10
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO #1: PROVIDE LKAPREZL ELKAY CANE APRON FOR
 HIGHER DRINKING FOUNTAIN TO COMPLY WITH FBC ACC 307.2
  
 PROVISO #2: PER WPB FBC 107.2.1, A REVISED PLAN SHEET
 IN-501 SHALL BE SUBMITTED, APPROVED AND IN PLACE PRIOR
 TO FIRST INSPECTION. THE FOLLOWING DETAILS SHALL BE
 CORRECTED AS NOTED:
 D1; MAXIMUM HEIGHT TO TOP OF VANITY SHALL BE 34 INCHES
 (FBC ACC 606.3)
 D2; SIDE HANDRAIL SHALL BE 12 INCHES FROM REAR WALL AND
 A MINIMUM 54 INCHES OVERALL FROM REAR WALL (FBC ACC
 604.5.1)
 A3; MAXIMUM HEIGHT TO TOP OF VANITY SHALL BE 34 INCHES
 (FBC ACC 606.3)
  
 PROVISO #3: PER WPB FBC 107.2.1, A REVISED PLAN SHEET
 G001 GENERAL ACCESSIBILITY & ABBREVIATIONS PROVIDING A
 NOTE STATING THAT IN CASE OF DISCREPANCY BETWEEN PLAN
 SHEET G001 AND PLAN SHEETS IN501 L10 ENLARGED PLANS &
 ELEVATIONS, IN400 L10 WALL SECTIONS & DETAILS, IN101
 L10 ARCHITECTURAL PLAN, PLAN SHEETS IN501, IN400 AND
 IN101 SHALL PREVAIL. PLAN SHALL BE SUBMITTED, APPROVED
 AND IN PLACE PRIOR TO FIRST INSPECTION.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-07-05 Cont ID  
Sent By jesmith Date 2022-07-05 Time 15:53 Rev Time 0.00
Received By jesmith Date 2022-07-05 Time 15:41 Sent To  
Notes
2022-07-05 15:48:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021416 222 LAKEVIEW AVE FL 10
  
 2ND REVIEW
  
 PROVISO #1: CONTRACTOR SHALL PROVIDE AS DEFERRED
 SUBMITTALS, MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE PLUMBING FIXTURES. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION IN ACCORDANCE WITH WPB FBC 107.2.1 AND
 107.3.4.1. SEE IN101 L10 ARCHITECTURAL PLAN/GENERAL
 CONSTRUCTION NOTE R. PROCEED AT YOUR OWN RISK.
  
 PROVISO #2: A PLUMBING PRE-INSPECTION WILL BE REQUIRED
 ONCE THE WALLS ARE OPEN AND REVISED PLAN, SUBMITTED AND
 APPROVED, SHOWING NOTABLE CHANGES TO DESIGN AND ROUTING
 MAY BE REQUIRED BY THE PLUMBING INSPECTOR IN ACCORDANCE
 WITH WPB FBC 107.4. SEE IN101 L10 ARCHITECTURAL
 PLAN/GENERAL CONSTRUCTION NOTE T.
  
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6, REVISE PLAN SHEET G001 AND PROVIDE
 PLAN AND ELEVATION DETAILS FOR THE UPGRADED TOILET
 ROOMS INDICATING THE FOLLOWING:
 ***A) COMPLIED
 ***B) SECOND REQUEST:THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM
 FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM
 THE REAR WALL PER FBC ACC 604.5.1
 TO BE CLEAR, REVISED IN501 L10 ENLARGED PLANS &
 ELEVATIONS/DETAIL D2 ADA STALL PARTION ELEVATION
 INDICATES 6 INCHES FROM REAR WALL TO SIDE HANDRAIL.
 PLEASE CORRECT, SHOWING 12 INCHES AND MINIMUM 54 INCHES
 MINIMUM OVERALL.
 ***C) COMPLIED
 ***D): COMPLIED
 ***E) COMPLIED
 ***F) COMPLIED
 ***G) COMPLIED
 ***H) COMPLIED
 ***I) COMPLIED
 ***J) PARTIALLY COMPLIED: DRINKING FOUNTAIN: PROVIDE
 ELEVATION AND CLEAR FLOOR SPACE SHOWING COMPLIANCE WITH
 FBC ACC 305, 306, 307 AND 602.
 REQUIREMENTS OF FBC ACC 307 NEED ATTENTION; SEE LINE
 ITEM ***K)
 ***K) SECOND REQUEST: DRINKING FOUNTAIN: FBC ACC 307.2;
 PROTRUDING OBJECTS AND PROTRUSION LIMITS. OBJECTS WITH
 LEADING EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80
 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4
 INCHES HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2.SECOND REQUEST:P-201/FIXTURE SCHEDULE: ELKAY LNTE8K
 DRINKING FOUNTAIN IS DISCONTINUED. PER WPB FBC 107.2.1,
 SPECIFY A DRINKING FOUNTAIN THAT IS CURRENTLY
 MANUFACTURED AND AVAILABLE.
 ENGINEER'S RESPONSE: REVISED SEE P-201. P-201 STILL
 LISTS THE LNTE8K.
 ARCHITECT'S RESPONSE: ADJUSTED SPEC. P-201 STILL LISTS
 THE LNTE8K.
  
 3.COMPLIANT
  
 4. COMPLIANT; SEE PROVISO #1
  
 5. COMPLIANT
  
 6.COMPLIANT
  
 7. COMPLIANT: SEE PROVISO #2
  
 NEW COMMENTS:
  
 1.NEW COMMENT: ENGINEER PROVIDED A RESPONSE STATING
 PLANS HAVE BEEN UPDATED WITH EXISTING PIPING AND THE
 PROPOSED CHANGES TO THE EXISTING PIPING.
 REVIEW OF PLANS REVEALS THE FOLLOWING: REVISED SEE
 P-001. REVIEW OF P-001/PLUMBING SHEET INDEX INDICATES
 REVISED P-101 SANITARY FLOOR PLAN AND ADDED P-102
 DOMESTIC FLOOR PLAN. P-101 IS STILL NOTED P-101
 PLUMBING PLAN, HAS NOT BEEN REVISED AND P-102 IS NOT
 AMONG THE SUBMITTED PLAN SHEETS. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 2.NEW COMMENT: PLAN SHEET G001 GENERAL ACCESSIBILITY &
 ABBREVIATIONS: PER WPB FBC 107.2.1, PROVIDE A NOTE
 STATING THAT IN CASE OF DISCREPANCY BETWEEN PLAN SHEET
 G001 AND PLAN SHEETS IN501 L10 ENLARGED PLANS &
 ELEVATIONS, IN101 L10 ARCHITECTURAL PLAN, PLAN SHEETS
 IN501 AND IN 101 SHALL PREVAIL.
  
 3.NEW COMMENT: SEE REVISED IN501 L10 ENLARGED PLANS &
 ELEVATIONS/DETAIL A2; PER FBC ACC 606.3, LAVATORIES
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SHALL BE 34 INCHES ABOVE THE FINUISH
 FLOOR OR GROUND, NOT 34-1/4 INCHES. PLEASE CORRECT.
  
 4.NEW COMMENT: PER WPB FBC 107.2.1, PLAN SHEET
 G-000/SHEET LIST SHALL REFLECT THE REVISED P-101
 SANITARY FLOOR PLAN AND ADDED P-102 DOMESTIC FLOOR PLAN
 INDICATED ON P-001/PLUMBING SHEET INDEX.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By jesmith Date 2022-05-03 Time 12:54 Rev Time 0.00
Received By jesmith Date 2022-04-28 Time 14:29 Sent To  
Notes
2022-05-03 12:13:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021416 222 LAKEVIEW AVE FL 10
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6, REVISE PLAN SHEET G001 AND PROVIDE
 PLAN AND ELEVATION DETAILS FOR THE UPGRADED TOILET
 ROOMS INDICATING THE FOLLOWING:
 ***A) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***B) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***C) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***D) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***E) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***F) URINAL: SEE PLAN SHEET IN501/MEN?S RR ELEVATIONS
 AND P-201/PLBG FIXTURE SCHEDULE. IN501 SHOWS URINAL LIP
 AT 24-1/2 INCHES AFF; P-201 INDICATES THE URINAL WILL
 BE ACCESSIBLE WALL-HUNG TYPE WITH THE RIM 17 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR. PER WPB FBC 107.2.,
 CLARIFY AND RECONCILE THE TWO PLANS. PER FBC ACC
 213.3.3, AS THERE IS ONLY ONE URINAL, IT IS NOT
 REQUIRED TO BE ACCESSIBLE. IF THE URINAL IS TO BE
 ACCESSIBLE, PROVIDE CORRECT ELEVATION AND CLEAR FLOOR
 SPACE SHOWING COMPLIANCE WITH FBC ACC 305 AND 605.2.
 ***G) LAVATORIES: A CLEAR FLOOR SPACE COMPLYING WITH
 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER
 FBC ACC 606.2
 ***H) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 ***I) SHOW TURNING SPACE FOR COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2.
 ***J) DRINKING FOUNTAIN: PROVIDE ELEVATION AND CLEAR
 FLOOR SPACE SHOWING COMPLIANCE WITH FBC ACC 305, 306,
 307 AND 602.
 ***K) DRINKING FOUNTAIN: FBC ACC 307.2; PROTRUDING
 OBJECTS AND PROTRUSION LIMITS. OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2.P-201/FIXTURE SCHEDULE: ELKAY LNTE8K DRINKING
 FOUNTAIN IS DISCONTINUED. PER WPB FBC 107.2.1, SPECIFY
 A DRINKING FOUNTAIN THAT IS CURRENTLY MANUFACTURED AND
 AVAILABLE.
  
 3.P-201/TYP. LAV/SK INSTALLATION; COLD AND/OR HOT WATER
 AS INDICATED ON PLAN. PLANS SHOW COLD WATER RISER. PER
 WPB FBC 107.2.1, PROVIDE SPECIFIC GUIDANCE ON THE PLAN.
 COLD WATER ONLY IS ACCEPTABLE. TEMPERED WATER IS
 ACCEPTABLE. IF TEMPERED WATER IS TO BE PROVIDED,
 SPECIFY HOT WATER SOURCE (AND PROVIDE SPECIFICATION AND
 DETAIL) AND AN APPROVED WATER-TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125.3.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR THE NEW PLUMBING
 FIXTURES. THEY SHALL BE ON SITE PRIOR TO INSPECTION AND
 MAY BE LISTED ON THE PLANS AS DEFERRED SUBMITTALS IN
 ACCORDANCE WITH WPB FBC 107.3.4.1. DOCUMENT SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
 5. PLEASE SEE COMMENT 1/***G) URINAL: SEE PLAN SHEET
 IN501/MEN'S RR ELEVATIONS AND P-201/PLBG FIXTURE
 SCHEDULE. IN501 SHOWS URINAL LIP AT 24-1/2 INCHES AFF;
 P-201 INDICATES THE URINAL WILL BE ACCESSIBLE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER WPB FBC 107.2., CLARIFY AND RECONCILE THE
 TWO PLANS. PER FBC ACC 213.3.3, AS THERE IS ONLY ONE
 URINAL, IT IS NOT REQUIRED TO BE ACCESSIBLE. IF THE
 URINAL IS TO BE ACCESSIBLE, PROVIDE CORRECT ELEVATION
 AND CLEAR FLOOR SPACE SHOWING COMPLIANCE WITH FBC ACC
 305 AND 605.2.
  
 6.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 7. IT IS RECOGNIZED THAT CONDITIONS IN THE WALLS WILL
 NOT BE CLEAR UNTIL THE AFFECTED WALLS ARE OPEN. PER WPB
 FBC 110.2.1, A PLUMBING PRE-INSPECTION WILL BE REQUIRED
 ONCE THE WALLS ARE OPEN AND A REVISED PLAN, SUBMITTED
 AND APPROVED, SHOWING NOTABLE CHANGES TO DESIGN AND
 ROUTING MAY BE REQUIRED BY THE PLUMBING INSPECTOR IN
 COMPLIANCE WITH WPB FBC 107.4 PRIOR TO FINAL
 INSPECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-05 Cont ID  
Sent By pvalenti Date 2022-10-05 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2022-10-05 Time 14:57 Sent To  
Notes
2022-08-30 13:45:54SIGNATURES FOR PLUMBING ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By rwbrown Date 2022-08-03 Time 06:12 Rev Time 0.00
Received By rwbrown Date 2022-08-03 Time 06:12 Sent To  
Notes
2022-07-05 15:55:37SIGNATURES FOR PLUMBING ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By mpeterso Date 2022-05-31 Time 16:26 Rev Time 0.00
Received By mpeterso Date 2022-05-31 Time 16:26 Sent To  
Notes
2022-05-31 16:27:01ALL PLANS PASSED WITHDIGITAL SIGNATURES. MP
2022-05-20 10:46:59DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME
2022-04-28 14:49:07SIGNATURES FOR PLUMBING ARE VALID. JS