Plan Review Stops For Permit 22021413
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By jwitmer Date 2022-03-21 Time 12:38 Rev Time 0.00
Received By jwitmer Date 2022-03-21 Time 12:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-04 Cont ID  
Sent By jwitmer Date 2022-08-04 Time 08:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-08-04 08:33:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021413
 ADD: 4650 GEORGIA AVE.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. AUGUST 04TH/ 2022
 ACTION: PASSED/ BUILDING PROVISO
  
 BUILDING PROVISO: SHEET S-2 SHOWS JOBSITE WELDING.
 WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2022-06-28 Time 13:33 Sent To  
Notes
2022-06-28 15:24:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021413
 ADD: 4650 GEORGIA AVE.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 28TH/ 2022
 ACTION: DENIED
  
 1) SHEET G1.0 PROJECT DATA & INDEX:
 1A) NOTED: WIND LOAD DESIGN, THE DESIGNER OF RECORD HAS
 PLACED THIS BUILDING IN AN EXPOSURE D.
  
 1B) 2ND REQUEST. THE RISK CATEGORY ASSIGNED TO THIS
 PROJECT IS RISK CATEGORY I. RISK CATEGORY I IS
 BUILDINGS OF AGRICULTURE FACILITIES, MINOR STORAGE
 BUILDINGS, SCREEN ENCLOSURES. PLEASE SEE TABLE 1604.5
 OF THE 2020 FBC-BUILDING CODE THE RISK CATEGORY SHOULD
 READ AS RISK CATEGORY II. RESPONSE SHEET STATES RISK
 CATEGORY HAS BEEN STATED ON THE LIFE SAFETY SHEET,
 ILLEGIBLE HAZY, ALSO ON SHEETG1.0 AS RISK CATEGORY I.
  
 1C) 2ND REQUEST. FUZZY CAN NOT READ WHEN ENLARGED. TYPE
 OF CONSTRUCTION/ OCCUPANCY TYPE IS GIVEN AS B/ FACTORY.
 PLEASE INDICATE WHETHER THE FACTORY OCCUPANCY IS A F1
 OR F2. 2020 FBC-BUILDING CODE SECTIONS 306.2 GROUP F-1
 OR GROUP F-2.
  
 1D) THE QUESTION IS IN THE PROCESS OF AQUAMATION/
 ALKALINE HYDROLYSIS HOW MUCH OF THE CHEMICAL ALKALINE
 WILL BE STORED ON SITE, WILL THE CHEMICAL BE STORED IN
 SOLID FORM POUNDS IN CUBIC FEET, LIQUID GALLONS IN WHAT
 TYPE OF STORAGE, WILL IT BE USED IN A CLOSED SYSTEM OR
 OPEN SYSTEM, PLEASE PROVIDE MSDS SHEETS FOR THIS
 CHEMICAL. ADDITIONAL INFORMATION IS REQUIRED, TABLE
 307.1(1) OF THE 2020 FBC-BUILDING CODE.
  
 1E) 2ND REQUEST. THE RESPONSE NOT SHOWN ON THE PLANS
 FOR COMPLIANCE. TYPE OF CONSTRUCTION/ LEVEL OF
 ALTERATION IS LEFT BLANK, ADDING TO AN EXISTING
 MEZZANINE WOULD BE A ADDITION OF SQUARE FOOTAGE TO THE
 BUILDING AND NEED TO SHOW COMPLIANCE WITH THE 2020
 FBC-EXISTING BUILDING CODE CHAPTER 11 ADDITIONS,
 SECTION 1103.3.1. VERTICAL ADDITIONS.
  
 1F)2ND REQUEST. WITH ADDITIONAL SQUARE FOOTAGE ON THE
 MEZZANINE LEVEL(NEW 2ND FLOOR) THE PROJECT DATA HAS NOT
 DECLARED THE LIVE LOADS FOR STORAGE SEE TABLE 1607.1 OF
 THE 2020 FBC-BUILDING, INDICATE ON THE FLOOR PLANS.
  
 2) THE LIFE SAFETY SHEET LSP:
 2A) MEZZANINES NEED TO SHOW COMPLIANCE WITH SECTION
 505.2.1 THAT THE MEZZANINE CAN NOT BE GRATER THAN 1/3RD
 THE ROOM IT IS IN, THE INSIDE BUILDING LINE FLOOR AREA
 THAT COMMUNICATES WITH THE MEZZANINE IS
 38.32 X 29= 1,111.25 AND THE AREA 5X9.25= 46.25 OR A
 TOTAL OF 1,157.50 SQ. FT. ONE THIRD OF THIS AREA IS
 381.975 SQ. FT. THE AREA SHOWN OF THE PROPOSED
 MEZZANINE IS 573 SQ. FT. OR 191.00 FEET OVER THE
 ALLOWABLE SIZE OF THE MEZZANINE.
  
 2B) COMPLIED. 2ND FLOOR LEVEL.
  
 2C) SEMI-COMPLIED. THE PROPOSED 2ND FLOOR DOES NOT HAVE
 A DOOR AT THE TOP OF THE STAIR ENCLOSE NOR DOES THE
 VERTICAL LIFT.
 1ST ROUND COMMENT. PLEASE SHOW ON THE LIFE SAFETY PLAN
 COMPLIANCE WITH 505.2.2 MEANS OF EGRESS FOR MEZZANINE
 AND CHAPTER 10 OF THE 2020 FBC-BUILDING CODE AND
 SECTION 1019.3 EXCEPTION 1 IF THE MEZZANINE
 REQUIREMENTS CAN NOT BE MET. PROVIDE THE COMMON PATH OF
 TRAVEL FROM THE FURTHEST POINT IN ACCORDANCE WITH TABLE
 1006.2.1. 2020FBC-BUILDING CODE.
  
 3) COMPLIED.
 4A) 2ND REQUEST. SHEET A1.5 SHOWS NEW SINGLE AND PAIR
 OF EXTERIOR SWING DOORS. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 4C) PLEASE NOTE ONCE TO THE TECHNICAL SHEETS SOME WOULD
 OPEN AND SOME WOULD NOT, NOT ABLE TO REVIEW.
  
 5) BUILDING PROVISO: SHEET S-2 SHOWS JOBSITE WELDING.
 WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED. THE BEST WAY TO COMMUNICATE IS
 BY E-MAIL.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By jwitmer Date 2022-03-21 Time 17:10 Rev Time 0.00
Received By jwitmer Date 2022-03-21 Time 12:37 Sent To  
Notes
2022-03-21 17:10:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021413
 ADD: 4650 GEORGIA AVE.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MARCH 21ST/ 2022
 ACTION: DENIED
  
 1) SHEET G1.0 PROJECT DATA & INDEX:
 1A) WIND LOAD DESIGN, THE DESIGNER OF RECORD HAS PLACED
 THIS BUILDING IN AN EXPOSURE D WITH HIGHER EXPOSURE
 PRESSURES. THE DESIGNER OF RECORD CAN DESIGN TO A
 HIGHER STANDARD THAN THE MINIMUM CODE. THE CORRECT WIND
 EXPOSURE IS CONSIDERED A C EXPOSURE.
  
 1B) THE RISK CATEGORY ASSIGNED TO THIS PROJECT IS RISK
 CATEGORY I. RISK CATEGORY I IS BUILDINGS OF AGRICULTURE
 FACILITIES, MINOR STORAGE BUILDINGS, SCREEN ENCLOSURES.
 PLEASE SEE TABLE 1604.5 OF THE 2020 FBC-BUILDING CODE
 THE RISK CATEGORY SHOULD READ AS II.
  
 1C) OCCUPANCY TYPE IS GIVEN AS B/ FACTORY. PLEASE
 INDICATE WHETHER THE FACTORY OCCUPANCY IS A F1 OR F2.
 2020 FBC-BUILDING CODE SECTIONS 306.2 GROUP F-1 OR
 GROUP F-2.
  
 1D) THE QUESTION IS IN THE PROCESS OF AQUAMATION/
 ALKALINE HYDROLYSIS HOW MUCH OF THE CHEMICAL ALKALINE
 WILL BE STORED ON SITE, WILL THE CHEMICAL BE STORED IN
 SOLID FORM POUNDS IN CUBIC FEET, LIQUID GALLONS IN WHAT
 TYPE OF STORAGE, WILL IT BE USED IN A CLOSED SYSTEM OR
 OPEN SYSTEM, PLEASE PROVIDE MSDS SHEETS FOR THIS
 CHEMICAL. ADDITIONAL INFORMATION IS REQUIRED, TABLE
 307.1(1) OF THE 2020 FBC-BUILDING CODE.
  
 1E) LEVEL OF ALTERATION IS LEFT BLANK, ADDING TO AN
 EXISTING MEZZANINE WOULD BE A ADDITION OF SQUARE
 FOOTAGE TO THE BUILDING AND NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-EXISTING BUILDING CODE CHAPTER 11
 ADDITIONS, SECTION 1103.3.1. VERTICAL ADDITIONS.
  
 1F) WITH ADDITIONAL SQUARE FOOTAGE ON THE MEZZANINE
 LEVEL THE PROJECT DATA HAS NOT DECLARED THE LIVE LOADS
 FOR STORAGE SEE TABLE 1607.1 OF THE 2020 FBC-BUILDING.
  
 2) THE LIFE SAFETY SHEET LSP:
 2A) MEZZANINES NEED TO SHOW COMPLIANCE WITH SECTION
 505.2.1 THAT THE MEZZANINE CAN NOT BE GRATER THAN 1/3RD
 THE ROOM IT IS IN, THE INSIDE BUILDING LINE FLOOR AREA
 THAT COMMUNICATES WITH THE MEZZANINE IS
 38.32 X 29= 1,111.25 AND THE AREA 5X9.25= 46.25 OR A
 TOTAL OF 1,157.50 SQ. FT. ONE THIRD OF THIS AREA IS
 381.975 SQ. FT. THE AREA SHOWN OF THE PROPOSED
 MEZZANINE IS 573 SQ. FT. OR 191.00 FEET OVER THE
 ALLOWABLE SIZE OF THE MEZZANINE.
  
 2B) THE AREA OF THE MEZZANINE ON THE 2ND LEVEL ALSO HAS
 WALLS MAKING IT WHERE IT DOES NOT COMMUNICATE WITH THE
 1ST FLOOR, 505.2.3 OPENNESS EXCEPTION 3 WILL ALLOW IT
 WHERE THE OCCUPANT LOAD OF THE MEZZANINE ENCLOSED SPACE
 OCCUPANT LOAD IS NOT GREATER THAN 10 PLEASE PROVIDE THE
 BREAK OUT OF THE ENCLOSED MEZZANINE BY ITSELF IN THE
 OCCUPANT LOAD TABLE. THANK YOU.
  
 2C) PLEASE SHOW ON THE LIFE SAFETY PLAN COMPLIANCE WITH
 505.2.2 MEANS OF EGRESS FOR MEZZANINE AND CHAPTER 10 OF
 THE 2020 FBC-BUILDING CODE AND SECTION 1019.3 EXCEPTION
 1 IF THE MEZZANINE REQUIREMENTS CAN NOT BE MET. PROVIDE
 THE COMMON PATH OF TRAVEL FROM THE FURTHEST POINT IN
 ACCORDANCE WITH TABLE 1006.2.1. 2020FBC-BUILDING CODE.
  
 3) SHEET A1.4 THE ENLARGED BREAKROOM THE WASHER DRYER
 DOES NOT SHOW THEIR OPERABLE PARTS IN COMPLIANCE WITH
 THE 2020 FBC-ACCESS. CODE SECTION 611.3 OPERABLE PARTS,
 INCLUDING DOORS, LINT SCREENS, DETERGENT AND BLEACH
 COMPARTMENTS IN COMPLIANCE WITH 309.3 HEIGHT. OPERABLE
 PARTS SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH
 RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 4A) SHEET A1.5 SHOWS NEW SINGLE AND PAIR OF EXTERIOR
 SWING DOORS. . PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) SHEET S-2 SHOWS JOBSITE WELDING. WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-08-05 Cont ID  
Sent By fgiaquin Date 2022-08-05 Time 23:47 Rev Time 0.00
Received By fgiaquin Date 2022-08-05 Time 23:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-05 Cont ID  
Sent By fgiaquin Date 2022-07-05 Time 19:47 Rev Time 0.00
Received By fgiaquin Date 2022-07-05 Time 19:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By fgiaquin Date 2022-03-21 Time 22:45 Rev Time 0.00
Received By fgiaquin Date 2022-03-21 Time 22:07 Sent To  
Notes
2022-03-21 22:45:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM IS NOT CLEAR AND CONCISE. THERE ARE
 MULTIPLE MAINS AFTER THE CT METER. PLEASE PROVIDE CLEAR
 RISER DIAGRAM SHOWING SERVICE DISCONECTING MEANS. THERE
 IS A 800AMP 3-POLE DISCONNECT SHOWN THEN A 700AMP
 3-POLE DISCONNECT DOWNSTREAM. FBC 107.2.1
  
 2. THERE IS AN EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM
 CT METER ENCLOSURE TO SERVICE DISCONNECTING MEANS. THIS
 IS NOT PERMITTED. THE EQUIPMENT GROUNDING CONDUCTOR
 ORIGINATES ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANS. PLEASE REMOVE ALL EQUIPMENT
 GROUNDING CONDUCTORS ON THE LINE SIDE OF THE SERVICE
 DISCONNECTING MEANS. NEC 250.30
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-02 Cont ID  
Sent By   Date 2022-08-02 Time   Rev Time 0.00
Received By bdolan Date 2022-08-02 Time 11:42 Sent To  
Notes
2022-08-02 11:42:51ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-21 Cont ID  
Sent By   Date 2022-06-21 Time   Rev Time 0.00
Received By bdolan Date 2022-06-21 Time 08:58 Sent To  
Notes
2022-06-21 08:58:19ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-07 Cont ID  
Sent By   Date 2022-03-07 Time   Rev Time 0.00
Received By bdolan Date 2022-03-07 Time 13:32 Sent To  
Notes
2022-03-07 13:38:59ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 16:00 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 16:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By jesmith Date 2022-03-10 Time 12:30 Rev Time 0.00
Received By jesmith Date 2022-03-08 Time 16:17 Sent To  
Notes
2022-03-10 12:22:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC MC = FLORIDA MECHANICAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021413 4650 GEORGIA AVE
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH FBC FG 402.2 AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG
 305.1.
  
 2. DETAIL SHOWS ONE MP REGULATOR FOR THE TWO WATER
 HEATERS. RISER DIAGRAM SHOWS TWO SEPARATE RISERS OUT OF
 THE GROUND TO THE WATER HEATERS WHICH WOULD INDICATE A
 DEDICATED REGULATOR FOR EACH ONE. PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE THE DRAWINGS.
  
 3. P0.0/GAS FIXTURE LOAD SUMMARY: PER WPB FBC 107.2.1,
 INDICATE QUANTITY OF 2.
  
 4. P0.0: PER WPB FBC 107.2.1, CLEARLY INDICATE MAXIMUM
 DEVELOPED LENGTH OF THE 2LB. SYSTEM PIPING AND THE
 LOW-PRESSURE SYSTEM(S) PIPING.
  
 5. P0.0/NOTE 1: PER WPB FBC 107.2.1, CLARIFY REFERENCE
 ALL ABOVE GROUND PIPING TO BE THE SUPPLY SIDE OF THE MP
 REGULATOR(S)
  
 6. P0.0/NOTE 7: PER WPB FBC 107.2.1, NOTE THE CODE
 REFERENCE AS FLORIDA FUEL GAS CODE 408.2.
  
 7. P0.0: PER WPB FBC 107.2.1, ADD TO GAS NOTES A TABLE
 (SEE FBC FG TABLES 402.4) AND MATERIAL SPECIFICATION
 FOR THE LOW-PRESSURE GAS PIPING; INDICATE INLET
 PRESSURE, PRESSURE DROP AND SPECIFIC GRAVITY. SIZING ON
 P2.0/DETAIL 6 SHALL REFLECT THE REQUIREMENTS OF THE
 TABLE(S).
  
 8. 2.0/DETAIL 6: PER WPB FBC 107.2.1, CLARIFY FUEL
 SOURCE TO INDICATE FROM UTILITY REGULATOR/METER, NOT
 UTILITY.
  
 9. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. COMPLY WITH FBC FG 410.1.
  
 10. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE
 INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE
 WITH FBC FG 409.4, 410.2(5)(6)(7).
  
 11. PER WPB FBC 107.2.1, MP REGULATOR VALVE(S) AND
 APPLIANCE VALVE(S) SHOWING COMPLIANCE WITH FBC FG 409.4
 AND 409.5.
  
 12. P3.0/GAS RISER DIAGRAM: PER WPB FBC 107.2.1, PLEASE
 NOTE ON THE PLANS THAT THE SUPPLY SIDE OF THE METER IS
 BY THE UTILITIES.
  
 13. P3.0/GAS RISER DIAGRAM: IT APPEARS THAT THE SUPPLY
 SIDE IN YOUR CALCULATIONS FOR DEVELOPED LENGTH IS
 INCLUDED. PER WPB FBC 107.2.1, PLEASE CLARIFY.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22021413 4650 GEORGIA AVE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-05 Cont ID  
Sent By fgiaquin Date 2022-08-05 Time 23:50 Rev Time 0.00
Received By fgiaquin Date 2022-07-28 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-05 Cont ID  
Sent By fgiaquin Date 2022-07-05 Time 19:47 Rev Time 0.00
Received By fgiaquin Date 2022-06-16 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-31 Cont ID  
Sent By asangele Date 2022-03-31 Time 14:35 Rev Time 0.00
Received By asangele Date 2022-03-31 Time 14:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-29 Cont ID  
Sent By medwards Date 2022-07-29 Time 10:04 Rev Time 0.00
Received By medwards Date 2022-07-29 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-23 Cont ID  
Sent By medwards Date 2022-06-23 Time 09:37 Rev Time 0.00
Received By medwards Date 2022-06-23 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 10:26 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 10:26 Sent To  
Notes
2022-03-10 10:28:21PLEASE PROVIDE MORE DETAIL FOR THE COOL ROOM, DEFROST,
 DEHUM A AND DEHUM B. MENTIONED ON THE LIFE SAFETY
 DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By rwbrown Date 2022-08-01 Time 07:51 Rev Time 0.00
Received By rwbrown Date 2022-08-01 Time 07:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 16:00 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-08 Cont ID  
Sent By jesmith Date 2022-03-08 Time 16:15 Rev Time 0.00
Received By jesmith Date 2022-03-03 Time 11:47 Sent To  
Notes
2022-03-08 16:11:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC MC = FLORIDA MECHANICAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021413 4650 GEORGIA AVE
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.A1.4/DETAIL 1: PER FBC ACC 804.3.1, THE CLEAR FLOOR
 OR GROUND SPACE SHALL BE CENTERED ON THE KITCHEN WORK
 SURFACE AND SHALL PROVIDE KNEE AND TOE CLEARANCE
 COMPLYING WITH 306. PER WPB FBC 107.2.1, PROVIDE
 FORWARD APPROACH TO KITCHEN SINK WITH KNEE AND TOE
 CLEARANCE.
  
 2.A1.4/DETAIL 1: PER FBC ACC 804.6.1, PROVIDE A CLEAR
 FLOOR SPACE FOR THE MICROWAVE OVEN.
  
 3. A1.4/DETAIL 1: PER FBC ACC 214.2 AND 214.3, WASHER
 AND DRYER SHALL COMPLY WITH FBC ACC 611; PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING:
 ***A) A FRONTAL VIEW OF EACH ITEM SHOWING COMPLIANCE
 WITH FBC ACC 611.4.
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH FBC
 ACC 305 POSITIONED FOR PARALLEL APPROACH; THE CLEAR
 FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE.
  
 4.A1.3: PER WPB FBC 107.2.1, FOR CLARIFICATION PLEASE
 PROVIDE THE ADDITIONAL FOLLOWING INFORMATION
 ***A) THE SIDE WALL GRAB BAR FOR THE WATER CLOSET SHALL
 BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL PER FBC ACC 604.5.1
 ***B) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***D) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ***E) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ***F) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
  
 5.PDFS FOR PLUMBING PLANS HAVE STICKY NOTES ALL OVER,
 MAKING PLANS HARD TO READ. PER WPB FBC 107.2.1, PLEASE
 HIDE OR REMOVE STICKY NOTES ON FUTURE SUBMITTALS.
  
 6.P2.0/DETAIL 8: PER WPB FBC 107.2.1, SHOW TRAP SEAL
 PROTECTION FOR THE FLOOR DRAIN AS REQUIRED BY FBC PL
 1002.4.1.
  
 7. P2.0/DETAIL 7: BOTTLE TRAPS ARE PROHIBITED PER FBC
 PL 1002.2 AND 1002.2(4). PER WPB FBC 107.2.1, REPLACE
 THE TEXT ?BOTTLE TRAP? WITH ?P-TRAP?.
  
 8.P0.0/PLUMBING MATERIAL AND EQUIPMENT NOTE 6: PER WPB
 FBC 107.2.1, PROVIDE A DETAIL FOR INSTALLATION OF THE
 SIOUX CHIEF 695 TRAP PRIMER VALVE FROM WATER
 DISTRIBUTION TO FLOOR DRAIN CONNECTION.
  
 9. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 9. P2.0/DETAIL 4: PER WPB FBC 107.2.1, PROVIDE NOTE AT
 THE PIPE HANGER DETAIL STATING, "HORIZONTAL PIPE SHALL
 BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 10.PER WPB FBC 107.2.1, PROVIDE A SCHEMATIC DETAIL FOR
 THE RECIRCULATING PUMP AND PIPING WITH VALVES AND
 CONTROLS; BE SURE TO SHOW CHECK VALVE WITH FULL OPEN
 VALVE IN COLD WATER LINE TO THE WATER HEATERS AHEAD OF
 THE HOT WATER RETURN LINE CONNECTION TO THE COLD WATER
 (SEE FBC PL 604.2).
  
 11.A1.3 AND P3.0: PLUMBING FIXTURE SCHEDULES HAVE
 CONFLICTING, INACCURATE AND MISSING INFORMATION; PER
 WPB FBC 107.2.1, RECONCILE AND CLARIFY THE FOLLOWING:
 ***A) ALL FIXTURES TO HAVE THE SAME MANUFACTURER/MODEL
 NUMBER/DESCRIPTION.
 ***B) WATER HEATER ON A1.3 SCHEDULE IS ELECTRIC AND A
 STORAGE TANK TYPE. P3.0 PROVIDES A SCHEDULE FOR GAS
 FIRED TANKLESS WATER HEATERS. PIPING AND GAS PLANS ALL
 INDICATE THE GAS FIRED TANKLESS WATER HEATERS.
 ***C) RECIRC PUMP MODEL NUMBERS DON'T MATCH
 ***D) DRINKING FOUNTAIN MODEL NUMBERS DON'T MATCH
 ***E) SINKS DON'T MATCH
 ***F) LAVATORIES DON'T MATCH. BE SURE TO INCLUDE THE
 POINT OF USE MIXING VALVE IN BOTH SCHEDULES
 ***G) PROVIDE SPECIFICATION FOR FD-1
 ***H) RECONCILE FIXTURE ID/TAG NUMBERS
 ***I) P3.0 SCHEDULE MISSING THE MOP SINK
 ***J) A1.3 MISSING EMERGENCY SHOWERS EEWS-1 AND ES-1.
  
 12.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER
 HEATER(S)
  
 13. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS AND DETAIL(S) FOR
 EEWS-1 AND ES-1.
  
 14.P1.0/ELEVATOR DRAIN:
 ***A) PLEASE NOTE, PER FBC 3002.9, FLOOR DRAINS, SUMPS
 AND SUMP PUMPS SHALL BE PERMITTED AT THE BASE OF THE
 HOISTWAY ENCLOSURE PROVIDED THEY ARE INDIRECTLY
 CONNECTED TO THE PLUMBING SYSTEM. PER WPB FBC 107.2.1,
 PROVIDE COMPLIANT DRAINAGE WITH DETAILS SHOWING
 INDIRECT CONNECTION.
 ***B) PLEASE NOTE PER FBC PL 1003.4.2.1, OIL SEPARATORS
 SHALL HAVE A DEPTH OF NOT LESS THAN 2 FEET BELOW THE
 INVERT OF THE DISCHARGE DRAIN. THE OUTLET OPENING OF
 THE SEPARATOR SHALL HAVE NOT LESS THAN AN 18-INCH WATER
 SEAL. PER WPB FBC 107.2.1, SELECT THE SIZE THAT
 COMPLIES. SIZE EFFLUENT DRAIN IN ACCORDANCE WITH
 MANUFACTURER'S RECOMMENDATIONS PER FBC PL 301.7.
  
 15.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 16. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CLOTHES
 WASHER PLUMBING CONNECTIONS.
  
 17. P3.0/SANITARY RISER: PER WPB FBC 107.2.1, IDENTIFY
 KS-1 AND W/D.
  
 18. REGARDING THE HORIZONTAL COMBINATION WASTE AND VENT
 SYSTEM:
 ***A) THE DRY 3 INCH VENT FOR THE SYSTEM SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND
 RISE VERTICALLY TO A POINT NOT LESS THAN 6 INCHES ABOVE
 THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED
 FIXTURE BEING VENTED PER FBC PL 905.3 AND 905.4.
 ***B) PER WPB FBC 107.2.1, SIZE HORIZONTAL BRANCHES
 CONNECTING THE TD FIXTURE DRAINS.
 ***C) PER WPB FBC 107.2.1, REFER TO FBC PL TABLE 709.1,
 FOOTNOTE (H), TABLE 709.2 AND SECTION 709.4. PROVIDE
 FIXTURE UNIT VALUES FOR FLOOR DRAINS AND TRENCH DRAINS
 AND NOTE TOTAL FIXTURE UNIT COUNT FOR THE SYSTEM.
 CONFIRM THAT THE SIZING OF THE SYSTEM IS IN ACCORDANCE
 WITH FBC PL TABLE 915.2.2. IF NECESSARY, SPLIT THE
 SYSTEM AND ADD A VENT ON THE TRENCH DRAIN SIDE. VENT
 SHALL COMPLY WITH FBC PL 905.3 AND 905.4.
 ***D) PER FBC PL 1002.1, PROVIDE A TRAP FOR EACH TRENCH
 DRAIN
 ***E) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE TRENCH
 DRAIN.; CONFIRM THAT 3 INCH CONNECTION IS IN ACCORDANCE
 WITH THE MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL. SEE FBC PL 301.7 WHICH STATES IN INSTANCES
 WHERE CONFLICTS OCCUR BETWEEN THIS CODE AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, THE MORE
 RESTRICTIVE PROVISIONS SHALL APPLY.
  
 19. PER FBC PL 604.1, THE DESIGN OF THE WATER
 DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED
 ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE
 PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER
 DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING
 SYSTEM IS AN APPROVED METHOD.
  
 20. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTORS AT
 THE CLOTHES WASHER. PROVIDE NOTE "WATER-HAMMER
 ARRESTORS SHALL CONFORM TO ASSE 1010"
  
 21. P1.0 SANITARY INDICATES FS-1( FLOOR SINK?) WITH
 WHAT APPEARS TO BE AN INDIRECT WASTE CONNECTION; P3.0
 INDICATES FD-1( FLOOR DRAIN?). PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE.
 21. PLANS INDICATE EQUIPMENT WITH WATER AND WASTE
 CONNECTIONS. PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 ***A) MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE EQUIPMENT
 ***B) DETAIL(S) SHOWING PLUMBING CONNECTIONS INCLUSIVE
 OF WATER, WASTE AND VENTS.
 ***C) IF PROVISION FOR BACKFLOW PREVENTION IS REQUIRED
 FOR THE WATER CONNECTIONS, IT IS ADVISABLE THAT SUCH
 PROTECTION IS SPECIFIED IN ACCORDANCE WITH FBC PL
 SECTION 608.
  
 22.P2.0/DETAIL 5 IS NOT APPLICABLE. PER WPB FBC
 107.2.1, PROVIDE INDIRECT WASTE CONNECTION FOR
 APPLICABLE CIRCUMSTANCES SHOWING COMPLIANCE WITH FBC PL
 SECTION 802.
  
 23.P1.0/NOTE 3: PER WPB FBC 107.2.1, PROVIDE A DETAIL
 FOR 2 INCH VENT PENETRATION AND RISER AT EXTERIOR.
 PROVIDE DISTANCES FROM ANY INTAKE VENTILATION SHOWING
 COMPLIANCE WITH FBC PL 903.5 AND FBC MC 401.4.
  
 24.P3.0/WATER RISER: AT THE POINT OF ENTRANCE FOR THE
 WATER DISTRIBUTION PROVIDE THE FOLLOWING:
 ***A) PER FBC PL 606.1(2), PROVIDE A FULL OPEN VALVE ON
 THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE INTO
 THE STRUCTURE.
 ***B) PER FBC PL 606.2(2), PROVIDE A SHUT-OFF VALVE FOR
 THE HOSE BIBB.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22021413 4650 GEORGIA AVE
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-29 Cont ID  
Sent By medwards Date 2022-07-29 Time 10:06 Rev Time 0.00
Received By medwards Date 2022-07-29 Time 10:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 15:14 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 15:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By fgiaquin Date 2022-03-21 Time 22:47 Rev Time 0.00
Received By fgiaquin Date 2022-03-21 Time 22:47 Sent To  
Notes
2022-03-10 10:30:48MECHANICAL SIGNATURE REVIEW IS APPROVED.ME
2022-03-08 16:19:37SIGNATURES FOR PLUMBING & GAS PLANS ARE COMPLIANT.JS

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By asangele Date 2022-06-29 Time 11:26 Rev Time 0.00
Received By asangele Date 2022-06-29 Time 11:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-31 Cont ID  
Sent By asangele Date 2022-03-31 Time 14:18 Rev Time 0.00
Received By asangele Date 2022-03-31 Time 14:18 Sent To  
Notes
2022-03-31 14:34:593/31/2022
 FAILED
 PLEASE PROVIDE A SURVEY WITH THE SETBACKS,ELEVATION OF
 THE BUILDING SINCE YOU ARE EXPANDING THE EXIST
 FOOTPRINT LARGER. A LANDSCAPE PERMIT IS ALSO REQUIRED
 SINCE YOU ARE EXCEED 50% OF THE VALUE OF THE STRUCTURE.
 A SEPARATE PERMIT IS REQUIRED FOR
 *SIGNAGE
 *PARKING ----- CHANGES/ MODIFICATIONS REGARDING PARKING
 FOR ACCESIBLITY YOU MUST PROVIDE THE SETBACKS OF THE
 PARKING SPOTS.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  
  