Plan Review Details - Permit 22021383
Plan Review Stops For Permit 22021383
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2023-01-26 Cont ID  
Sent By jgomez Date 2023-01-27 Time 15:02 Rev Time 0.00
Received By jgomez Date 2023-01-26 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2022-12-21 Cont ID  
Sent By jgomez Date 2022-12-21 Time 14:42 Rev Time 0.00
Received By jgomez Date 2022-12-21 Time 14:42 Sent To  
Notes
2022-12-21 14:42:3212/21/22 COMMENTS REVISED FOR CLARIFICATION. SHUTTERS
 INSTALLATION SCHEDULE REQUIRED REVISION APPLIES TO THE
 HURRICANE FABRIC SYSTEM. JG.
  
  
 RESIDENTIAL (R3) SEVENTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
 310 DYER RD
  
 ****NOTE:
 COMMENTS BELOW APPLY TO THE HURRICANE FABRIC SYSTEM NOA
 20-1102.08.
  
  
 HURRICANE SHUTTERS:
 7(B)REVISE SHUTTERS INSTALLATION SCHEDULE:
  
 PREVIOUS COMMENT:
 (4)NEED TO COMPLETE THE SHUTTERS GLASS SEPARATION
 COLUMN. SEE PRODUCT APPROVAL FOR REQUIRED SEPARATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 GLASS SEPARATION IS INCORRECT FOR WALL MOUNT
 INSTALLATION. SEE SHEET 2 OF 11 AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 (3)NEED TO COMPLETE THE ANCHOR SPACING COLUMN. SPECIFY
 ANCHOR SPACING AT TOP AND BOTTOM.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ANCHOR SPACING IS INCORRECT FOR WALL MOUNT
 INSTALLATION. SEE SHEET 6 OF 11 AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2022-12-19 Cont ID  
Sent By jgomez Date 2022-12-19 Time 15:51 Rev Time 0.00
Received By jgomez Date 2022-12-19 Time 15:51 Sent To  
Notes
2022-12-19 15:52:01RESIDENTIAL (R3) SIXTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
 310 DYER RD
  
 HURRICANE SHUTTERS:
 7(B)REVISE SHUTTERS INSTALLATION SCHEDULE:
  
 PREVIOUS COMMENT:
 (4)NEED TO COMPLETE THE SHUTTERS GLASS SEPARATION
 COLUMN. SEE PRODUCT APPROVAL FOR REQUIRED SEPARATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 GLASS SEPARATION IS INCORRECT FOR WALL MOUNT
 INSTALLATION. SEE SHEET 2 OF 11 AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 (3)NEED TO COMPLETE THE ANCHOR SPACING COLUMN. SPECIFY
 ANCHOR SPACING AT TOP AND BOTTOM.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ANCHOR SPACING IS INCORRECT FOR WALL MOUNT
 INSTALLATION. SEE SHEET 6 OF 11 AND REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-11-14 Cont ID  
Sent By jgomez Date 2022-11-14 Time 16:07 Rev Time 0.00
Received By jgomez Date 2022-11-14 Time 13:41 Sent To  
Notes
2022-11-14 16:07:24RESIDENTIAL (R3) FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
 310 DYER RD
  
 ORIGINAL COMMENT:
 7- HURRICANE SHUTTERS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 PREVIOUS COMMENT:
 REPEAT COMMENT. NOT ADDRESSED. NEED TO PROVIDE THE
 INSTALLATION SCHEDULE.
 NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS
 SUBMITTED. SUBMIT EITHER THE COMPLETE FLORIDA PRODUCT
 APPROVAL FL15208-R6 INCLUDING THE INSTALLATION
 INSTRUCTIONS OR THE MIAMI DADE NOA 20-1102.08.
  
 RESPONSE:
 7(A)INFORMATION SUBMITTED UNDER FLORIDA PRODUCT
 APPROVAL FL15208-R6 DOESN'T MATCH INSTALLATION
 INSTRUCTIONS DRAWINGS THAT CORRESPOND TO THIS FLORIDA
 PRODUCT APPROVAL. PLEASE DON'T MISMATCH INSTALLATION
 INSTRUCTIONS. SUBMIT EITHER THE INSTALLATION
 INSTRUCTIONS CORRESPONDING TO THIS FLORIDA PRODUCT
 APPROVAL OR SUBMIT COMPLETE NOA 20-1102.08.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7(B)REVISE SHUTTERS INSTALLATION SCHEDULE:
 (1)OPENINGS LOCATED WITHIN 4 FEET OF THE END OF THE
 STRUCTURE ARE CONSIDERED END ZONE 5. REVISE THE DESIGN
 PRESSURES FOR OPENINGS LOCATED IN THE END ZONE. FOR
 EXAMPLE OPENING #105G IS LOCATED IN THE END ZONE.
 NOTE: DESIGN PRESSURES SHOWN ON THE PROPOSED ELEVATIONS
 ARE TOO LOW. SEE COMPONENTS & CLADDING PRESSURES BELOW
 THE ELEVATION NOTES AND REVISE AS REQUIRED. CHECK ALL
 OPENINGS TO AVOID DELAYS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (2)REVISE DESIGN PRESSURES ON THE SHUTTERS INSTALLATION
 SCHEDULE TO MATCH REVISED DESIGN PRESSURES. SEE ITEM
 ABOVE. CHECK ALL OPENINGS TO AVOID DELAYS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (3)INFORMATION ON SHUTTER MOUNTING IS INCORRECT.
 CORRECT SHUTTER MOUNTING IS EITHER THE "WALL MOUNT
 CONDITION", "INTERIOR MOUNT CONDITION", ETC. SEE
 MOUNTING CONDITIONS ON PAGE 2 OF NOA SUBMITTED AND
 REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (4)NEED TO COMPLETE THE SHUTTERS GLASS SEPARATION
 COLUMN. SEE PRODUCT APPROVAL FOR REQUIRED SEPARATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (3)NEED TO COMPLETE THE ANCHOR SPACING COLUMN. SPECIFY
 ANCHOR SPACING AT TOP AND BOTTOM.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8-ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PREVIOUS COMMENT:
 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH
 SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY
 WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 ALSO. SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT
 OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE.
 DETAIL SPECIFIES 4" SPHERE. DIMENSION HAS TO BE LESS
 THAN 4". REVISE DIMENSION AS REQUIRED.
 NOTE: THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION
 #1, WHERE THE TRIANGULAR AREA FORMED BY THE RISER,
 THREAD AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE
 PASSAGE OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR
 DIMENSION AS WELL.
 REVISE ALL STAIR DETAILS AS REQUIRED.
  
 RESPONSE:
 DETAILS STILL SHOW 4" AND 6" OPENINGS. THIS ITEM WAS
 SPECIFICALLY DISCUSSED IN PERSON WITH CALEB LAUX
 (ARCH.). I TOLD HIM DIMENSIONS NEED TO BE LESS THAN 4"
 AND 6" RESPECTIVELY. REVISE DIMENSIONS AS REQUIRED.
  
 PREVIOUS COMMENT:
 10-ADDITIONAL COLONIAL SHUTTERS FL6414-R6 WAS
 SUBMITTED.
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 RESPONSE:
 INFORMATION ON SHUTTERS INSTALLATION SCHEDULE IS
 INCOMPLETE. NEED TO FILL ALL THE COLUMNS.
 NOTE: COORDINATE WITH COMMENTS ON ITEM #7 ABOVE. UNABLE
 TO IDENTIFY PROPOSED INSTALLATION. CLEARLY IDENTIFY
 CONNECTION TYPES AND DETAILS ON SHEET 4 AND 7 OF
 PRODUCT APPROVAL SUBMITTED. CHECK THE SHUTTER SPAN
 BASED ON THE OPENING SIZE. ALSO, CHECK MAXIMUM SPAN
 BETWEEN STORM BARS.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 12:32 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 09:41 Sent To  
Notes
2022-09-26 12:33:59RESIDENTIAL (R3) PRODUCT APPROVALS FOURTH SUBMITTAL
 BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
 310 DYER RD
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
 5- OK
 6- OK.
  
 ORIGINAL COMMENT:
 7- HURRICANE SHUTTERS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. NEED TO PROVIDE THE
 INSTALLATION SCHEDULE.
 NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS
 SUBMITTED. SUBMIT EITHER THE COMPLETE FLORIDA PRODUCT
 APPROVAL FL15208-R6 INCLUDING THE INSTALLATION
 INSTRUCTIONS OR THE MIAMI DADE NOA 20-1102.08.
  
 8-ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PREVIOUS COMMENT:
 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH
 SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY
 WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 ALSO. SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT
 OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE.
 DETAIL SPECIFIES 4" SPHERE. DIMENSION HAS TO BE LESS
 THAN 4". REVISE DIMENSION AS REQUIRED.
 NOTE: THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION
 #1, WHERE THE TRIANGULAR AREA FORMED BY THE RISER,
 THREAD AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE
 PASSAGE OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR
 DIMENSION AS WELL.
 REVISE ALL STAIR DETAILS AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT:
 10-ADDITIONAL COLONIAL SHUTTERS FL6414-R6 WAS
 SUBMITTED.
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-13 Cont ID  
Sent By jgomez Date 2022-07-13 Time 16:26 Rev Time 0.00
Received By jgomez Date 2022-07-13 Time 09:51 Sent To  
Notes
2022-07-13 16:26:55RESIDENTIAL (R3) PRODUCT APPROVALS THIRD SUBMITTAL
 BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
  
 1- CEDAR ROOF SHINGLES:
  
 ORIGINAL COMMENT:
 A)PROVIDE CURRENT (2020 CODE VERSION) PRODUCT APPROVAL
 AS REQUIRED BY FAC 61G20.3.001.
  
 RESPONSE:
 REPEAT COMMENT. FLORIDA PRODUCT APPROVAL FL7993-R1
 SUBMITTED IS FOR 2017 CODE VERSION. NEED PRODUCT
 APPROVAL FOR CURRENT 2020 CODE VERSION. CHAPTER 553
 F.S.
 NOTE: WOOD SHINGLES NEED TO COMPLY WITH THE
 REQUIREMENTS OF SEC. R905.7 FBC-RESIDENTIAL. CHECK IF
 THE ALLOWABLE UPLIFT RESISTANCE STATED IN THE PRODUCT
 APPROVAL MEETS THE UPLIFT REQUIREMENTS FOR THIS HOUSE
 TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL7993-R1 SUBMITTED IS FOR
 2017 CODE VERSION. NEED PRODUCT APPROVAL FOR CURRENT
 2020 CODE VERSION.
 ALSO, INFORMATION SUBMITTED DOESN'T CORRESPOND TO
 FLORIDA PRODUCT APPROVAL FL7993-R1 AND IS TOO OLD TO BE
 USED WITH CURRENT CODE.
 NOTE: WOOD SHINGLES NEED TO COMPLY WITH THE
 REQUIREMENTS OF SEC. R905.7 FBC-RESIDENTIAL. CHECK IF
 THE ALLOWABLE UPLIFT RESISTANCE STATED IN THE PRODUCT
 APPROVAL MEETS THE UPLIFT REQUIREMENTS FOR THIS HOUSE
 TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 2- SKYLIGHT. PROVIDE COMPLETE AND CURRENT PRODUCT
 APPROVAL. FAC 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 PARTIALLY DONE. FLORIDA PRODUCT APPROVAL COVER PAGE FOR
 FL13303-R10 WAS SUBMITTED.
 HALLMARK CERTIFICATE OF CONFORMANCE AND LICENSE (CCL)
 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT OF RECORD AND DOESN'T CORRESPOND TO
 FLORIDA PRODUCT APPROVAL FL13303-R10. NEED TO PROVIDE
 PRODUCT APPROVAL THAT MEETS OR EXCEEDS THE CALCULATED
 DESIGN PRESSURES.
 ALSO, NEED TO SUBMIT THE INSTALLATION INSTRUCTIONS
 CORRESPONDING TO THIS PRODUCT APPROVAL.
  
 3- WINDOW MULLIONS:
 A)OK.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION (2020) AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL
 COVER WAS NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 4-CASEMENT WINDOWS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL
 COVER WAS NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 5-DOUBLE HUNG WINDOWS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL
 COVER WAS NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 6-EXTERIOR DOORS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 RESPONSE:
 REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL
 COVER WAS NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 7- HURRICANE SHUTTERS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8-ARCHITECT OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 NOTE: THIS APPLIES WHEN RESUBMITTING A NEW PRODUCT
 APPROVAL.
  
 NEW COMMENT BASED ON NEW STAIRWAY DRAWINGS SUBMITTED:
 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH
 SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY
 WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NOTE: SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT
 OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE.
 TYPICALLY, THE OPENING IS SPECIFIED WITH A DIMENSION
 LESS THAN 4 INCH TO COMPLY WITH THIS REQUIREMENT.
 THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION #1,
 WHERE THE TRIANGULAR AREA FORMED BY THE RISER, THREAD
 AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE PASSAGE
 OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR DIMENSION AS
 WELL.
 REVISE ALL STAIR DETAILS AS REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-03 Cont ID  
Sent By jbaker Date 2022-06-03 Time 12:39 Rev Time 0.00
Received By jbaker Date 2022-06-03 Time 12:38 Sent To  
Notes
2022-06-03 12:44:2122021383 310 DYER ROAD
 1.CEDAR ROOF SHINGLES: YOUR RESPONSE TO PREVIOUS IS
 INCOMPLETE, PLEASE TRY THE FOLLOWING:
 GO TO FLORIDA PRODUCT APPROVAL PAGE, TYPE IN 2017, TYPE
 IN FL# AND SELECT CEDAR VALLEY MANUFACTURING FROM
 PRODUCT LISTING. THIS WILL TAKE YOU TO CORRECT PAGE FOR
 COVER SHEET, INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORTS.
 2. SKYLIGHT: YOUR RESPONSE TO PREVIOUS IS INCOMPLETE,
 PLEASE TRY THE FOLLOWING:
 GO TO FLORIDA PRODUCT APPROVAL PAGE, TYPE IN 2017, TYPE
 IN FL# AND SELECT VELUX AMERICA LLC FROM PRODUCT
 LISTING. THIS WILL TAKE YOU TO CORRECT PAGE FOR COVER
 SHEET, INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORTS.
 3. WINDOW MULLIONS: THE PREVIOUS COMMENT REMAINS AS YOU
 HAVE SHOWN ON P. 9 OF CASEMENT WINDOW SUBMITTAL A ?
 INCH X 3-1/2 INCH OR ? INCH X 5 3/16 INCH MULLIONS AND
 IN THE MULLION SUBMITTAL THE TABLE OF CONTENTS ON PAGE
 1 DOES NOT LIST EITHER OF THESE SIZES.
 4. CASEMENT WINDOWS: YOUR RESPONSE TO PREVIOUS IS
 INCOMPLETE, PLEASE TRY THE FOLLOWING:
 GO TO FLORIDA PRODUCT APPROVAL PAGE, TYPE IN 2017, TYPE
 IN FL# AND SELECT ANDERSEN CORPORATION FROM PRODUCT
 LISTING. THIS WILL TAKE YOU TO CORRECT PAGE FOR COVER
 SHEET, INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORTS.
 5. DOUBLE HUNG WINDOWS: YOUR RESPONSE TO PREVIOUS IS
 INCOMPLETE, PLEASE TRY THE FOLLOWING:
 GO TO FLORIDA PRODUCT APPROVAL PAGE, TYPE IN 2017, TYPE
 IN FL# AND SELECT ANDERSEN CORPORATION FROM PRODUCT
 LISTING. THIS WILL TAKE YOU TO CORRECT PAGE FOR COVER
 SHEET, INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORTS.
 6. EXTERIOR DOORS: YOUR RESPONSE TO PREVIOUS IS
 INCOMPLETE, PLEASE TRY THE FOLLOWING:
 GO TO FLORIDA PRODUCT APPROVAL PAGE, TYPE IN 2017, TYPE
 IN FL# AND SELECT ANDERSEN CORPORATION FROM PRODUCT
 LISTING. THIS WILL TAKE YOU TO CORRECT PAGE FOR COVER
 SHEET, INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORTS.
 7. HURRICANE SHUTTERS: YOUR RESPONSE TO PREVIOUS IS
 INCOMPLETE, PLEASE TRY THE FOLLOWING:
  
  
  
 JIM BAKER
 561-805-6710
 [email protected]
  
 EMAILS ARE PREFERRED
 A COMMENT/RESPONSE LETTER WILL CAUSE A MORE EXPEDITIOUS
 REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By jgomez Date 2022-03-04 Time 14:52 Rev Time 0.00
Received By jgomez Date 2022-03-04 Time 14:09 Sent To  
Notes
2022-03-04 14:56:01RESIDENTIAL (R3) PRODUCT APPROVALS SUBMITTAL BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
  
 1- CEDAR ROOF SHINGLES:
 A)PROVIDE CURRENT (2020 CODE VERSION) PRODUCT APPROVAL
 AS REQUIRED BY FAC 61G20.3.001.
  
 B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 2- SKYLIGHT. PROVIDE COMPLETE AND CURRENT PRODUCT
 APPROVAL. FAC 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 3- WINDOW MULLIONS:
 A)FLORIDA PRODUCT APPROVAL FL15922 SUBMITTED DOESN'T
 COVER THE MULLION SIZE SPECIFIED ON THE CASEMENT WINDOW
 PRODUCT APPROVAL SUBMITTED. NEED TO PROVIDE CORRECT
 PRODUCT APPROVAL. FAC 61G20.3.001.
  
 B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 4-CASEMENT WINDOWS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 5-DOUBLE HUNG WINDOWS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 6-EXTERIOR DOORS.
 PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001.
 INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE.
 COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT
 APPROVAL COVER PAGE SHOWING THE CODE VERSION AND
 INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT
 APPROVAL.
  
 7- HURRICANE SHUTTERS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 8-ARCHITECT OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 NOTE: ONLY THE HURRICANE SHUTTERS PRODUCT APPROVAL WAS
 APPROVED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 6 Status P Date 2023-02-03 Cont ID  
Sent By amhamilt Date 2023-02-03 Time 12:23 Rev Time 0.00
Received By amhamilt Date 2023-02-03 Time 12:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 13:53 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 13:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2022-11-23 Cont ID  
Sent By fmittner Date 2022-11-23 Time 16:12 Rev Time 0.00
Received By fmittner Date 2022-11-23 Time 16:12 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-10-14 Cont ID  
Sent By amhamilt Date 2022-10-14 Time 11:50 Rev Time 0.00
Received By amhamilt Date 2022-10-14 Time 11:50 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By amhamilt Date 2022-05-27 Time 09:14 Rev Time 0.00
Received By amhamilt Date 2022-05-27 Time 09:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By amhamilt Date 2022-03-23 Time 11:57 Rev Time 0.00
Received By amhamilt Date 2022-03-23 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-02-06 Cont ID  
Sent By lmarchan Date 2023-02-06 Time 08:10 Rev Time 0.00
Received By lmarchan Date 2023-01-25 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-04 Cont ID  
Sent By aoliver Date 2023-01-04 Time 08:09 Rev Time 0.00
Received By aoliver Date 2022-12-08 Time 06:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-28 Cont ID  
Sent By lmarchan Date 2022-11-28 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2022-11-14 Time 07:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-17 Cont ID  
Sent By aoliver Date 2022-10-17 Time 08:45 Rev Time 0.00
Received By aoliver Date 2022-09-23 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-03 Cont ID  
Sent By jbaker Date 2022-06-03 Time 12:39 Rev Time 0.00
Received By jbaker Date 2022-05-04 Time 19:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-24 Cont ID  
Sent By lmarchan Date 2022-03-24 Time 08:39 Rev Time 0.00
Received By lmarchan Date 2022-03-01 Time 05:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-27 Cont ID  
Sent By jgomez Date 2023-01-27 Time 15:05 Rev Time 0.00
Received By jgomez Date 2023-01-26 Time 15:05 Sent To  
Notes
2023-01-27 16:04:08SIGNATURE VALID IN ACROBAT. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-26 Cont ID  
Sent By jgomez Date 2022-12-19 Time 15:54 Rev Time 0.00
Received By jgomez Date 2022-12-19 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By jgomez Date 2022-11-14 Time 16:14 Rev Time 0.00
Received By jgomez Date 2022-11-14 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 12:35 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 12:35 Sent To  
Notes
***NONE***