Plan Review Details - Permit 22021317
Plan Review Stops For Permit 22021317
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 12:59 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 12:59 Sent To  
Notes
2022-03-31 13:00:11WEST BUILDING ADDRESSES CHANGED TO 705 AND 707 FERNWOOD
 DR, THIS PERMIT IS FOR THE EAST BUILDING WITH THE
 ADDRESS OF 5555 GARDEN AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-03-11 Cont ID  
Sent By cpuell Date 2022-03-11 Time 15:57 Rev Time 0.00
Received By cpuell Date 2022-03-11 Time 15:57 Sent To  
Notes
2022-03-11 15:57:41WHICH BUILDING IS THE WORK TO BE DONE, EAST OR WEST?
 THE WEST BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By jbrooks Date 2022-07-08 Time 12:43 Rev Time 0.00
Received By jbrooks Date 2022-07-08 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By jbrooks Date 2022-03-14 Time 10:28 Rev Time 0.00
Received By jbrooks Date 2022-03-14 Time 07:51 Sent To  
Notes
2022-03-14 10:29:04JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
 2. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF
 DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE
 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020
 FBC-PLUMBING.
 3. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL
 HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-08 Cont ID  
Sent By jbrooks Date 2022-07-08 Time 12:44 Rev Time 0.00
Received By jbrooks Date 2022-06-27 Time 06:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By jbrooks Date 2022-03-14 Time 10:29 Rev Time 0.00
Received By jbrooks Date 2022-03-11 Time 10:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-08 Cont ID  
Sent By jbrooks Date 2022-07-08 Time 12:43 Rev Time 0.00
Received By jbrooks Date 2022-07-08 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-14 Cont ID  
Sent By jbrooks Date 2022-03-14 Time 10:29 Rev Time 0.00
Received By jbrooks Date 2022-03-14 Time 10:18 Sent To  
Notes
***NONE***