Plan Review Details - Permit 22021281
Plan Review Stops For Permit 22021281
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-18 Cont ID  
Sent By mpeterso Date 2022-03-18 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-03-18 Time 09:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-02-28 Cont ID  
Sent By cwalker Date 2022-02-28 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-02-28 14:43:01FIRE PROVISO COMMENTS:
 (1) AUDIBLE DEVICES PROVIDED FOR SLEEPING AREAS SHALL
 PRODUCE A LOW FREQUENCY SIGNAL COMPLIANT WITH NFPA 72
 18.4.5.3
 (2) PROVIDE A RECORD OF COMPLETION AFTER INSTALLATION
 AND TESTING TO THE FIRE INSPECTOR, PER NFPA 72 7.2
 (3) A BATTERY TEST SHALL BE CONDUCTED AND WITNESSED BY
 THE FIRE INSPECTOR IN ACCORDANCE WITH NFPA 72, 14.4
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-18 Cont ID  
Sent By mpeterso Date 2022-03-18 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-02-25 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-03-01 Cont ID  
Sent By hmoser Date 2022-03-01 Time 13:31 Rev Time 0.00
Received By hmoser Date 2022-03-01 Time 13:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-28 Cont ID  
Sent By jleahy Date 2022-02-28 Time 12:24 Rev Time 0.00
Received By jleahy Date 2022-02-28 Time 12:24 Sent To  
Notes
***NONE***