Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By pvalenti Date 2022-09-16 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2022-09-16 Time 15:47 Sent To  
Notes
2022-09-16 15:48:30PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED BY JIM WHITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 10:09 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-26 10:09:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 22021250
 W. P. B. PERMIT: 21021446
 ADD: 3114 TUXEDO AVE.
 CONT: S. MACDONALD CONTRACTING
 TEL: 561-689-8848
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JULY 26TH/2022
 ACTION: DENIED
  
 1) THE SHEET C-2 THE SITE PLAN & C3 ENLARGED SITE PLAN:
 1A) 2ND REQUEST. PLEASE NOTE THE SAME PLAN CAN BE USED
 BUT A SEPARATE PERMIT IS REQUIRED FOR STRIPING OF THE
 PARKING LOT. ALSO NOTE COMMENT 1B-1D WILL BE REVIEWED
 UNDER THE STRIPING PERMIT. FEES WILL NEED TO BE
 ADJUSTED SO SOME OF THE FUNDS GO TOWARDS THE EXTERIOR
 SITE WORK. PLEASE NOTE IF NO NEW PLANS ARE SUBMITTED
 FOR THE SITE WORK THEN THE CORRECTIONS WILL NEED TO
 SHOWN UNDER THE MASTER PERMIT/ REVISION. IF THE
 EXTERIOR SITE WORK IS TO BE SHOWN UNDER THIS REVISION,
 ON BOTH THE REVISION SHEET AND C1 COVER SHEET THE
 PROJECT DESCRIPTION WILL ALSO NEED TO BE UPDATED.
 CURRENTLY THE SCOPE OF WORK STATES INTERIOR BUILD-OUT
 OF EXISTING OPEN SPACE STRUCTURE, (PREVIOUSLY USE AS
 OFFICES).
  
 1ST ROUND COMMENT. A SEPARATE PERMIT IS REQUIRED FOR
 THE STRIPING OF THE PARKING LOT AND REQUIRED ACCESSIBLE
 PARKING SPACES AND ACCESS AISLES. 2020
 FBC-ACCESSIBILITY CODE SECTION ACCESSIBLE PARKING
 SPACES. 208.3. LOCATION.
 PARKING SPACES COMPLYING WITH 502 THAT SERVE A
 PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE
 SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE
 COMPLYING WITH 206.4.
  
 1B) 2ND REQUEST, SHOW THE ELEVATIONS AT THE CORNERS OF
 THE ACCESSIBLE PARKING SPACE AND ACCESS AISLE ( SHOW
 ELEVATION MARKERS) TO SEE IF THEY COMPLY WITH THE 2020
 ACCESSIBILITY CODE SECTION 502.4 ACCESS AISLE & PARKING
 SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND SURFACES.
 PARKING SPACES AND THE ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 1C) 2ND REQUEST SHOW ELEVATIONS WITH ELEVATION MARKERS.
 THERE IS NO DETAIL OF THE TRANSITION FROM THE SIDEWALK
 TO THE ACCESS AISLE SHOWING A DROPPED CURB.
 2020 FBC-ACCESSIBILITY CODE SECTION 406.5. LOCATION.
 CURB RAMPS AND THE FLARED SIDES OF THE CURB RAMPS SHALL
 NOT BE LOCATED SO THAT THEY DO NOT PROJECT INTO
 VEHICULAR TRAFFIC LANES, PARKING SPACES, OR PARKING
 ACCESS AISLES. CURB RAMPS AT MARKED CROSSINGS SHALL BE
 WHOLLY CONTAINS WITHIN THE MARKINGS, EXCLUDING FLARED
 SIDES. ALSO SEE FIGURE 406.4. LANDINGS AT THE TOP OF
 CURB RAMPS.
  
 1D) 2ND REQUEST. PLEASE SHOW HOW A CRUSHED AND
 COMPACTED SURFACE MEETS THE REQUIREMENTS OF 302 AND THE
 ADVISORY. THE ONLY TIME THIS HAS BEEN ALLOWED IS FOR
 TEMPORARY CONSTRUCTION TRAILERS.
 2020 FBC-ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 MUST MEET THE REQUIREMENTS OF 302.1 GROUND AND FLOOR
 SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT AND
 SHALL COMPLY WITH 302.
 ADVISORY 302.1. A STABLE SURFACE IS ONE THAT REMAINS
 UNCHANGED BY CONTAMINANTS OR APPLIED FORCES SO THAT
 WHEN THE CONTAMINANT OR FORCE IS REMOVED, THE SURFACE
 RETURNS TO ITS ORIGINAL CONDITION.
  
 1E) COMPLIED.
  
 2) THE LIFE SAFETY SHEET LS1:
 2A) SEMI-COMPLIED. SHEET LS1 & A8. THE REVISION NOW
 SHOWS COMPLIANCE FOR WHEELCHAIR ENTRY WITH SEAT BUT THE
 WATERCLOSET DOES NOT SHOW COMPLIANCE WITH THE REQUIRED
 SIDE GRAB BAR ACCESS. CODE 604.5.1.
  
 OLD 2ND ROUND COMMENTS. THE LS1 SHEET AND A8 SHOW A
 UNISEX ACCESSIBLE BATHROOM (SHOWER). THE SHOWER IS
 DEPICTED AS A 3X3 FOOT MODULAR PAN SHOWER. ON THE RIGHT
 SIDE OF THE SHOWER ENTRY IS AN EXTERIOR WALL. ON THE
 LEFT SIDE OF THE SHOWER THERE IS A WALL THAT PROJECTS
 OUT PAST THE SHOWER APPROXIMATELY 1 FOOT. THE 3 X3 FOOT
 SHOWER IS CONSIDERED A TRANSFER TYPE SHOWER SEE 608.2.1
 ACCESSIBILITY CODE AND REQUIRES AN ADDITIONAL ONE-FOOT
 CLEARANCE BEYOND THE SHOWER OPENING TO BE ABLE TO
 TRANSFER FROM A WHEELCHAIR WHEN PARALLEL WITH THE FRONT
 OF THE SHOWER. SEE FIGURE 608.2.1.
 2B) 2ND REQUEST. PLEASE REVIEW SHEET A8 DRINKING
 FOUNTAIN ELEVATION VIEWS. YES YOU MEET THE 27 MAX
 HEIGHT FOR THE LOWER DRINKING FOUNTAIN BUT NOT THE
 UPPER DRINKING FOUNTAIN AS DEPICTED SOME SORT OF
 BARRIER NEEDS TO BE PLACED FOR A BLIND PERSON WITH
 WALKING CANE IF WALKING TOWARDS THE UPPER DRINKING
 FOUNTAIN TO SHOW COMPLIANCE, SOME MANUFACTURES MAKE A
 SKIRT THAT CAN BE APPLIED TO THE UPPER FOUNTAIN FOR
 COMPLIANCE A OPTION.
 ORIGINAL COMMENT. THE LS1 SHEET AND A8 SHOW HIGH/ LOW
 DRINKING FOUNTAINS. DETAILS ON SHEET A8 SHOW A SIDE
 VIEW OF THE LOW SIDE DRINKING FOUNTAIN AT A HEIGHT OF 2
 FEET 3 INCHES FROM THE FLOOR LEVEL TO THE BOTTOM OF THE
 DRINKING FOUNTAIN IN COMPLIANCE WITH THE 2020
 ACCESSIBILITY CODE SECTION 307.2 PROTRUSION LIMITS. THE
 LEFT-HAND SIDE DRINKING FOUNTAIN MEETS THE REQUIREMENTS
 FOR STANDING OCCUPANTS BUT DOES NOT AS DEPICTED MEET
 THE PROTRUSION LIMITS, THE BOTTOM OF THE DRINKING
 FOUNTAIN IS HIGHER THAN 27 INCHES FROM THE FLOOR.
  
 2C-D) COMPLIED.
  
 3) 2ND REQUEST. SHEET A6.0:
 3A) 2ND REQUEST, NOT ADDRESSED. IF YOU CLASSIFY THE
 BUILDING AS A IIB THEN ALL FRAMING MEMBERS AND ROOF
 DECKING NEED TO BE IDENTIFIED TO MEET THAT DEFINITION
 FOUND UNDER TABLE 601 AND 603.1 OTHERWISE THE BUILDING
 SHOULD BE LABELED IIIB.
 ORIGINAL COMMENT. PLEASE NOTE THE COVERSHEET LIST THIS
 CONSTRUCTION TYPE AS IIB NON-SPRINKLERED BUILDING. THE
 BUILDING SECTIONS ON SHEET A6.0 DO NOT INDICATE IF THE
 TRUSSED ARCH IS STEEL OR LAMINATED WOOD? THE SECTION
 ALSO FAILED TO DEFINE THE ROOF FRAMING MEMBERS/ PURLINS
 AND THE ROOF SHEATHING MATERIAL? ADDITIONAL INFORMATION
 IS REQUIRED. 2020 FBC-BUILDING CODE 603.1 .1.3 ROOF
 CONSTRUCTION, INCLUDING GIRDERS, TRUSSES FRAMING AND
 DECKING. ALL MUST BE FIRE RETARDANT TREATED WOOD.
  
 3B) 2ND REQUEST, NOT ADDRESSED. PLEASE ADD RESPONSE
 NOTES TO PLAN INDICATING FLOOR LOADING. EVERY PERMIT
 STANDS ALONE FOR INFORMATION.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SECTION 2 & 3 BOTH SHOW A EXISTING CRAWL SPACE THE PLAN
 DOES NOT SHOW HOW THE ADDITIONAL GRAVITY LOADS PLUS
 STORAGE LOADS FROM THE NEW ATTIC SPACE ARE GOING TO BE
 TRANSFERRED TO THE FLOOR WITHOUT NEW COLUMNS OR PIERS
 BENEATH THE FIRST FLOOR LEVEL. 107.2. 1.. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3C) 2ND REQUEST, NOT ADDRESSED. SORRY IT WAS ASSUMED
 THE MEZZANINE LEVEL (ATTIC) TO BE STORAGE. THE LS1
 SHEET NOR PROPOSED FLOOR PLAN SHOW A OCCUPANCY TYPE OR
 OCCUPANT LOAD. WITH THE 42 INCH HIGH RAIL WALL IT MEETS
 THE DEFINITION OF MEZZANINE, ASSUMED STORAGE SINCE
 THERE IS NO PERMANENT STAIR NOR IS THERE VERTICAL
 ACCESSIBILITY FOR OCCUPANT LOAD MORE THAN 5. SEE 2020
 FBC-ACCESSIBILITY 201.1.1 EXCEPTION 3 .
 ORIGINAL COMMENT. THE BUILDING SECTIONS SHOWN ON THIS
 SHEET DO NOT INDICATE WHAT TYPE OF LIVE LOADS ARE GOING
 TO BE PRODUCED BY STORAGE IN THE ATTIC. TABLE 1607.1
 STORAGE LIGHT IS 125 PSF, HEAVY AT 250 PSF
  
 3D) 2ND REQUEST, NOT ADDRESSED. 2020 FBC-BUILDING CODE
 SECTION 1603.1. THE DESIGN LOADS AND OTHER INFORMATION
 PERTINENT TO THE STRUCTURAL DESIGN SHALL BE INDICATED
 ON THE CONSTRUCTION DOCUMENTS.
  
 4) SHEET A8;
 4A-C) COMPLIED.
  
 4D) 2ND REQUEST.PLEASE PROVIDE SPECS FOR THE RAINBOW
 ATTIC STAIRS. 107.2.1 2020 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By jwitmer Date 2022-05-17 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2022-05-17 Time 11:44 Sent To  
Notes
2022-05-17 16:48:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 22021250
 W. P. B. PERMIT: 21021446
 ADD: 3114 TUXEDO AVE.
 CONT: S. MACDONALD CONTRACTING
 TEL: 561-689-8848
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 17TH/2022
 ACTION: DENIED
  
 1) THE SHEET C-2 THE SITE PLAN & C3 ENLARGED SITE PLAN:
 1A) A SEPARATE PERMIT IS REQUIRED FOR THE STRIPING OF
 THE PARKING LOT AND REQUIRED ACCESSIBLE PARKING SPACES
 AND ACCESS AISLES. 2020 FBC-ACCESSIBILITY CODE SECTION
 ACCESSIBLE PARKING SPACES. 208.3. LOCATION.
 PARKING SPACES COMPLYING WITH 502 THAT SERVE A
 PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE
 SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE
 COMPLYING WITH 206.4.
  
 1B) 2020 ACCESSIBILITY CODE SECTION 502.4 ACCESS AISLE
 & PARKING SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND
 SURFACES. PARKING SPACES AND THE ACCESS AISLES SERVING
 THEM SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT
 THE SAME LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 1C) THERE IS NO DETAIL OF THE TRANSITION FROM THE
 SIDEWALK TO THE ACCESS AISLE SHOWING A DROPPED CURB.
 2020 FBC-ACCESSIBILITY CODE SECTION 406.5. LOCATION.
 CURB RAMPS AND THE FLARED SIDES OF THE CURB RAMPS SHALL
 NOT BE LOCATED SO THAT THEY DO NOT PROJECT INTO
 VEHICULAR TRAFFIC LANES, PARKING SPACES, OR PARKING
 ACCESS AISLES. CURB RAMPS AT MARKED CROSSINGS SHALL BE
 WHOLLY CONTAINS WITHIN THE MARKINGS, EXCLUDING FLARED
 SIDES. ALSO SEE FIGURE 406.4. LANDINGS AT THE TOP OF
 CURB RAMPS.
  
 1D) 2020 FBC-ACCESSIBILITY CODE, ACCESSIBLE PARKING
 SPACES MUST MEET THE REQUIREMENTS OF 302.1 GROUND AND
 FLOOR SURFACES SHALL BE STABLE, FIRM, AND SLIP
 RESISTANT AND SHALL COMPLY WITH 302.
 ADVISORY 302.1. A STABLE SURFACE IS ONE THAT REMAINS
 UNCHANGED BY CONTAMINANTS OR APPLIED FORCES SO THAT
 WHEN THE CONTAMINANT OR FORCE IS REMOVED, THE SURFACE
 RETURNS TO ITS ORIGINAL CONDITION.
  
 1E) THE DRAWING INDEX INDICATES THERE SHOULD BE A SHEET
 S3.0 ATTIC FLOOR STRUCTURAL FRAMING PLAN, MISSING FROM
 PLAN SET. 107.2.1. 2020 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) THE LIFE SAFETY SHEET LS1:
 2A) THE LS1 SHEET AND A8 SHOW A UNISEX ACCESSIBLE
 BATHROOM (SHOWER). THE SHOWER IS DEPICTED AS A 3X3 FOOT
 MODULAR PAN SHOWER. ON THE RIGHT SIDE OF THE SHOWER
 ENTRY IS AN EXTERIOR WALL. ON THE LEFT SIDE OF THE
 SHOWER THERE IS A WALL THAT PROJECTS OUT PAST THE
 SHOWER APPROXIMATELY 1 FOOT. THE 3 X3 FOOT SHOWER IS
 CONSIDERED A TRANSFER TYPE SHOWER SEE 608.2.1
 ACCESSIBILITY CODE AND REQUIRES AN ADDITIONAL ONE-FOOT
 CLEARANCE BEYOND THE SHOWER OPENING TO BE ABLE TO
 TRANSFER FROM A WHEELCHAIR WHEN PARALLEL WITH THE FRONT
 OF THE SHOWER. SEE FIGURE 608.2.1.
 2B) THE LS1 SHEET AND A8 SHOW HIGH/ LOW DRINKING
 FOUNTAINS. DETAILS ON SHEET A8 SHOW A SIDE VIEW OF THE
 LOW SIDE DRINKING FOUNTAIN AT A HEIGHT OF 2 FEET 3
 INCHES FROM THE FLOOR LEVEL TO THE BOTTOM OF THE
 DRINKING FOUNTAIN IN COMPLIANCE WITH THE 2020
 ACCESSIBILITY CODE SECTION 307.2 PROTRUSION LIMITS. THE
 LEFT-HAND SIDE DRINKING FOUNTAIN MEETS THE REQUIREMENTS
 FOR STANDING OCCUPANTS BUT DOES NOT AS DEPICTED MEET
 THE PROTRUSION LIMITS, THE BOTTOM OF THE DRINKING
 FOUNTAIN IS HIGHER THAN 27 INCHES FROM THE FLOOR.
  
 2C) NEITHER THE LS1 NOR SHEET A8 SHOW THE REQUIRED 30 X
 48 CLEAR FLOOR SPACE FOR THE TRANSFER SHOWER (FIGURE
 608.2.1) NOT THE DRINKING FOUNTAIN (602.2).
  
 2D) GROUND FLOOR OCCUPANT LOAD FACTOR IS TAKEN AT
 1:100. THIS WAS TRUE UNDER THE 2017 FBC-BUILDING CODE.
 THE 2020 FBC-BUILDING CODE TABLE 1004.5 FOR BUSINESS
 OCCUPANCY THE OCCUPANT LOAD FACTOR CHANGED TO 150 NOT
 100. PLEASE UPDATE THE PLANS.
  
  
 3) SHEET A6.0:
 3A) PLEASE NOTE THE COVERSHEET LIST THIS CONSTRUCTION
 TYPE AS IIB NON-SPRINKLERED BUILDING. THE BUILDING
 SECTIONS ON SHEET A6.0 DO NOT INDICATE IF THE TRUSSED
 ARCH IS STEEL OR LAMINATED WOOD? THE SECTION ALSO
 FAILED TO DEFINE THE ROOF FRAMING MEMBERS/ PURLINS AND
 THE ROOF SHEATHING MATERIAL? ADDITIONAL INFORMATION IS
 REQUIRED. 2020 FBC-BUILDING CODE 603.1 .1.3 ROOF
 CONSTRUCTION, INCLUDING GIRDERS, TRUSSES FRAMING AND
 DECKING. ALL MUST BE FIRE RETARDANT TREATED WOOD.
  
 3B) SECTION 2 & 3 BOTH SHOW A EXISTING CRAWL SPACE THE
 PLAN DOES NOT SHOW HOW THE ADDITIONAL GRAVITY LOADS
 PLUS STORAGE LOADS FROM THE NEW ATTIC SPACE ARE GOING
 TO BE TRANSFERRED TO THE FLOOR WITHOUT NEW COLUMNS OR
 PIERS BENEATH THE FIRST FLOOR LEVEL. 107.2. 1.. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3C) THE BUILDING SECTIONS SHOWN ON THIS SHEET DO NOT
 INDICATE WHAT TYPE OF LIVE LOADS ARE GOING TO BE
 PRODUCED BY STORAGE IN THE ATTIC. TABLE 1607.1 STORAGE
 LIGHT IS 125 PSF, HEAVY AT 250 PSF
  
 3D) 2020 FBC-BUILDING CODE SECTION 1603.1. THE DESIGN
 LOADS AND OTHER INFORMATION PERTINENT TO THE STRUCTURAL
 DESIGN SHALL BE INDICATED ON THE CONSTRUCTION
 DOCUMENTS.
  
 4) SHEET A8;
 4A) THE ELEVATION VIEW OF THE ACCESSIBLE ELEMENTS DO
 NOT COMPLIANCE WITH THE TRANSFER SHOWER GRAB BAR
 LOCATIONS NOR BACKING SEE FIGURE 603.1.
  
 4B) MISSING ELEVATION FOR THE TRANSFER SHOWER FOR
 CONTROL LOCATION IN COMPLIANCE WITH 608.5.1.
  
 4C) MISSING DETAIL FOR TRANSFER SHOWER SEAT IN
 COMPLIANCE WITH 608.4 AND BACKING FOR SEAT ALSO REVIEW
 610.3.
  
 4D) PLEASE PROVIDE SPECS FOR THE RAINBOW ATTIC STAIRS.
 107.2.1 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By jwitmer Date 2022-03-02 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2022-03-02 Time 08:25 Sent To  
Notes
2022-03-02 10:56:50WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 22021250
 W. P. B. PERMIT: 21021446
 ADD: 3114 TUXEDO AVE.
 CONT: S. MACDONALD CONTRACTING
 TEL: 561-689-8848
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 02/2022
 ACTION: DENIED
  
 1) THE PLANS COULD NOT BE VERSIONED NOR WAS THERE A
 NARRATIVE SUBMITTED INDICATING WHAT THE REVISIONS ARE
 BEING SUBMITTED FOR REVIEW. THE MOST RECENT REVISIONS
 SHOULD BE EITHER BE CLOUDED OR NUMERAL WITHIN A DELTA
 (TRIANGLE).
 REVISION- 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By fgiaquin Date 2022-05-31 Time 23:22 Rev Time 0.00
Received By fgiaquin Date 2022-05-31 Time 22:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-18 Cont ID  
Sent By fgiaquin Date 2022-03-18 Time 20:45 Rev Time 0.00
Received By fgiaquin Date 2022-03-18 Time 19:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-09-08 Cont ID  
Sent By cwalker Date 2022-09-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-09-08 09:25:08FIRE PROVISO COMMENT:
 ANY WORK PERFORMED ON THE FIRE ALARM SYSTEM MUST BE
 PERFORMED BY A PROPERLY LICENSED AND CERTIFIED
 CONTRACTOR, UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-07-25 Cont ID  
Sent By cwalker Date 2022-07-25 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-07-25 08:51:57FIRE PROVISO COMMENT:
 ANY WORK PERFORMED ON THE FIRE ALARM SYSTEM MUST BE
 PERFORMED BY A PROPERLY LICENSED AND CERTIFIED
 CONTRACTOR, UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By cwalker Date 2022-05-12 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-05-12 10:46:14SEE PREVIOUS PROVISO NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-03 Cont ID  
Sent By pleduc Date 2022-03-03 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-03 12:51:33FIRE PROVISO COMMENTS:
 ANY WORK PERFORMED ON THE FIRE ALARM SYSTEM MUST BE
 PERFORMED BY A PROPERLY LICENSED AND CERTIFIED
 CONTRACTOR, UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-16 Cont ID  
Sent By pvalenti Date 2022-09-16 Time 15:54 Rev Time 0.00
Received By pvalenti Date 2022-09-07 Time 07:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-29 Cont ID  
Sent By aoliver Date 2022-07-29 Time 09:07 Rev Time 0.00
Received By aoliver Date 2022-07-22 Time 14:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-31 Cont ID  
Sent By fgiaquin Date 2022-05-31 Time 23:23 Rev Time 0.00
Received By fgiaquin Date 2022-05-10 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-18 Cont ID  
Sent By fgiaquin Date 2022-03-18 Time 20:45 Rev Time 0.00
Received By fgiaquin Date 2022-03-01 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-27 Cont ID  
Sent By medwards Date 2022-07-27 Time 12:14 Rev Time 0.00
Received By medwards Date 2022-07-27 Time 12:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 10:47 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 16:27 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 16:27 Sent To  
Notes
2022-03-10 16:27:541ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22021250
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 USING THE CORRECT
 OCCUPANCY CLASSIFICATION FOR EACH USE OF SPACE IN THIS
 TENANT SPACE.
  
 4) PLEASE SHOW THE CONDENSING PIPE MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC M 307
  
 5) PLEASE PROVIDE A DETAIL OF THE WALLS TO CEILING FOR
 AHU?S 1 AND 2 AT THE FREE DRAW RETURNS. SHOW THE RETURN
 AIR PATH FROM THE ROOMS BACK TO THE AHU?S. FBC M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-07-27 Cont ID  
Sent By ccole Date 2022-07-27 Time 12:38 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-23 Cont ID  
Sent By ccole Date 2022-05-23 Time 13:19 Rev Time 0.00
Received By ccole Date 2022-05-23 Time 11:04 Sent To  
Notes
2022-05-23 13:23:062ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22021250
 3/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS
 ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE
 REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF
 THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY
 DETAILS- SEC. 107.2.1 WPB. FIXTURE CALCULATIONS NOT
 PROVIDED.
  
 3) FAILED. A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC
 ACC: THE CORRECTED PLANS STILL HAVE SOME MISSING
 DETAILS.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- SEC. 606.2. A 48-INCH DEPTH DIMENSION
 IS REQUIRED. THE PLAN SHOWS 3'0".
 E) FAILED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR
 TO THE REFLECTIVE SURFACE- SEC. 603.3. THE DETAIL SHOWS
 THE MEASUREMENT TO THE FRAME. DIMENSION NOT SHOWN TO
 THE REFLECTIVE SURFACE.
 F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE
 MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE
 TOPS OF THE GRIPPING SURFACES. REAR WATER CLOSET GRAB
 BAR DIMENSIONS NOT SHOWN.
 H) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE SHOWER- SECTION 608.2.1 REQUIRED CLEAR FLOOR SPACE
 SHALL BE 30X48-INCHES IN A PARALLEL POSITIONED MEASURED
 FROM THE CONTROL SIDE OF THE SHOWER. THE DRAWING SHOWS
 THERE IS NOT ADEQUATE SPACE TO PROVIDED TO MEET
 COMPLIANCE.
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1 NOT PROVIDED.
 J) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.1. NOT PROVIDED.
 L) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS
 610.3 & 610.3.2. NOT PROVIDED.
 M) FAILED. DRINKING FOUNTAINS: REFER TO SECS. 306, 307,
 AND 602 AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC.
 602.2. SHOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. THE
 DRAWINGS SHOW THE DRINKING FOUNTAINS WILL BE PROTRUDING
 INTO THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES
 ALLOWED- SEC. 307.2 FBC ACC. WING WALLS ON EACH SIDE OF
 THE FOUNTAIN CAN BE INSTALLED OR BARRIER-FREE TYPE
 FOUNTAINS.
  
 NEW COMMENT:
  
 1) SHEET A8: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSETS
 SEC. AND FIGURE 604.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-07 Cont ID  
Sent By ccole Date 2022-03-07 Time 14:08 Rev Time 0.00
Received By ccole Date 2022-03-07 Time 11:46 Sent To  
Notes
2022-03-07 14:17:061ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22021250
 3/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS
 ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE
 REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF
 THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY
 DETAILS- SEC. 107.2.1 WPB.
  
 2) LS1, P1: LABEL THE TOILET ROOMS AS EITHER MALE,
 FEMALE OR UNISEX- SECS. 403.2 & 403.2.1 FBC P. PLEASE
 NOTE THAT SIGNAGE IS REQUIRED- SEC. 403.4.
  
 3) A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4. THE DETAILS SHOW THE MEASUREMENTS
 TO THE RIM AND NOT THE SEAT.
 E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SEC. 603.3. THE DETAILS SHOWS THE
 MEASUREMENT TO THE FRAME.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE
 MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE
 TOPS OF THE GRIPPING SURFACES.
 G) INTERIOR DIMENSIONS OF THE SHOWER- SEC. 608.2.1.
 H) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.1
 I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1
 J) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
 K) SHOWER SPRAY UNIT SPECIFICATIONS INCLUDING ON/OFF
 CONTROL AND NON-POSITIVE SHUTOFF PER SECTION 608.6.
 L) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 &
 610.3.2.
 M) DRINKING FOUNTAINS: REFER TO SECS. 306, 307, AND 602
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SEC. 602.2. SHOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 4) S1 & P1: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1
 WPB.
  
 5) P3: PROVIDE A SHOWER PAN DETAIL- 421.5.2 FBC P.
  
 6) P3: PROVIDE SHOWER VALVE AND SPRAY PLUMBING
 SPECIFICATIONS- 412.2 & 412.3 FBC P.
  
 7) P3: SHOW THE LOCATION OF THE WATER HEATER EXPANSION
 TANK- SEC. 607.3 FBC P.
  
 8) P2 & P3: SHOW THE WATER HEATER PAN DRAIN PIPING RUN
 AND DISCHARGE LOCATION- SEC. 504.7.1 FBC P.
  
 9) P2 & P3: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. PLEASE
 NOTE THAT TEMPERED WATER MIXING VALVES SHALL CONFORM TO
 ASSE 1070.
  
 10) P3: PROVIDE SHOWER FLOOR AND WALL FINISH DETAILS-
 SEC. 421.4.1.
  
 11) A8: REFER TO SECTION 310.3 FBC P AND SEC.1210.2.2
 FBC B WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By pvalenti Date 2022-09-16 Time 15:53 Rev Time 0.00
Received By pvalenti Date 2022-09-16 Time 15:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-27 Cont ID  
Sent By ccole Date 2022-07-27 Time 12:43 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 12:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By fgiaquin Date 2022-05-31 Time 23:23 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-18 Cont ID  
Sent By fgiaquin Date 2022-03-18 Time 20:45 Rev Time 0.00
Received By fgiaquin Date 2022-03-18 Time 20:45 Sent To  
Notes
2022-03-10 16:28:53DIGITAL SIGNATURE FOR THE MECHANICAL DRAWINGS-NOT
 REQUIRED. ME

Review Stop Z ZONING
Rev No 4 Status P Date 2022-09-13 Cont ID  
Sent By kdefranc Date 2022-09-13 Time 11:35 Rev Time 0.00
Received By kdefranc Date 2022-09-13 Time 11:34 Sent To  
Notes
2022-09-13 11:34:589/9/22 ??? PASSED
  
 PREVIOUS REVIEW COMMENTS
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A REVISED ???PLAN REVIEW REQUEST
 FORM??? WITH AN UPDATED DESCRIPTION ACCOUNTING FOR THE
 NEW PROPOSED PARKING SPACES IN ADDITION TO THE PROPOSED
 ???INTERIOR RENOVATION PLANS FOR NEW OFFICE SPACES???.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 2. PLEASE PROVIDE A NARRATIVE PROVIDING CLARIFICATION
 ON THE PROPOSED REVISIONS. [SATISFIED PER RESPONSE
 PROVIDED AND ENTIRE PLAN SET PACKAGE SUBMITTAL]
 3. PLEASE CLEARLY IDENTIFY/INDICATE THE PROPOSED
 REVISIONS ON THE RESUBMITTED PLANS AND MATERIALS.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 4. PLEASE INDICATE THE CURRENT ZONING DISTRICT, THE
 PROPOSED USE OF THE SUBJECT STRUCTURE, THE EXISTING
 NUMBER OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE
 PARKING SPACES, THE REQUIRED NUMBER OF AUTOMOBILE
 (STANDARD AND ADA) AND BICYCLE PARKING SPACES ACCORDING
 TO SECTIONS 94-485 AND 94-486 OF THE CITY???S ZONING
 AND LAND DEVELOPMENT REGULATIONS, AND THE PROPOSED
 NUMBER OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE
 PARKING SPACES IN THE ???PROJECT DATA??? SECTION ON THE
 ???COVER SHEET??? OF THE ???CONSTRUCTION DOCUMENTS???.
 [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED AISLE AND THE LOCATION OF THE PROPOSED
 BICYCLE PARKING FACILITY ON THE ???OVERALL SITE PLAN???
 AND ???ENLARGED WORK AREA SITE PLAN??? SHEETS OF THE
 ???CONSTRUCTION DOCUMENTS???. [SATISFIED]
 6. PLEASE PROVIDE THE ELEVATION DRAWING AND DIMENSIONAL
 DETAILS FOR THE PROPOSED BICYCLE PARKING FACILITY ON
 THE ???ENLARGED WORK AREA SITE PLAN??? SHEET OF THE
 ???CONSTRUCTION DOCUMENTS???. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE SUBMIT A PAVING PERMIT APPLICATION FOR THE
 PROPOSED PARKING SPACES.
  
  
 NEW REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE INDICATE THE EXISTING NUMBER OF LOADING
 SPACES, THE REQUIRED NUMBER OF LOADING SPACES ACCORDING
 TO SECTION 94-485 OF THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER OF
 LOADING SPACES IN THE ???PROJECT DATA??? SECTION ON THE
 ???COVER SHEET??? OF THE ???CONSTRUCTION DOCUMENTS???.
 [SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONAL DETAILS OF THE PROPOSED LOADING
 SPACE(S) ON THE ???OVERALL SITE PLAN??? AND ???ENLARGED
 WORK AREA SITE PLAN??? SHEETS OF THE ???CONSTRUCTION
 DOCUMENTS???. [SATISFIED]
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-28 Cont ID  
Sent By kdefranc Date 2022-07-28 Time 16:13 Rev Time 0.00
Received By kdefranc Date 2022-07-28 Time 16:10 Sent To  
Notes
2022-07-28 16:13:327/28/22 ? FAILED
  
 PREVIOUS REVIEW COMMENTS
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A REVISED ?PLAN REVIEW REQUEST FORM?
 WITH AN UPDATED DESCRIPTION ACCOUNTING FOR THE NEW
 PROPOSED PARKING SPACES IN ADDITION TO THE PROPOSED
 ?INTERIOR RENOVATION PLANS FOR NEW OFFICE SPACES?.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 2. PLEASE PROVIDE A NARRATIVE PROVIDING CLARIFICATION
 ON THE PROPOSED REVISIONS. [SATISFIED PER RESPONSE
 PROVIDED AND ENTIRE PLAN SET PACKAGE SUBMITTAL]
 3. PLEASE CLEARLY IDENTIFY/INDICATE THE PROPOSED
 REVISIONS ON THE RESUBMITTED PLANS AND MATERIALS.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 4. PLEASE INDICATE THE CURRENT ZONING DISTRICT, THE
 PROPOSED USE OF THE SUBJECT STRUCTURE, THE EXISTING
 NUMBER OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE
 PARKING SPACES, THE REQUIRED NUMBER OF AUTOMOBILE
 (STANDARD AND ADA) AND BICYCLE PARKING SPACES ACCORDING
 TO SECTIONS 94-485 AND 94-486 OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER
 OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE PARKING
 SPACES IN THE ?PROJECT DATA? SECTION ON THE ?COVER
 SHEET? OF THE ?CONSTRUCTION DOCUMENTS?. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED AISLE AND THE LOCATION OF THE PROPOSED
 BICYCLE PARKING FACILITY ON THE ?OVERALL SITE PLAN? AND
 ?ENLARGED WORK AREA SITE PLAN? SHEETS OF THE
 ?CONSTRUCTION DOCUMENTS?. [SATISFIED]
 6. PLEASE PROVIDE THE ELEVATION DRAWING AND DIMENSIONAL
 DETAILS FOR THE PROPOSED BICYCLE PARKING FACILITY ON
 THE ?ENLARGED WORK AREA SITE PLAN? SHEET OF THE
 ?CONSTRUCTION DOCUMENTS?. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE SUBMIT A PAVING PERMIT APPLICATION FOR THE
 PROPOSED PARKING SPACES.
  
  
 NEW REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE INDICATE THE EXISTING NUMBER OF LOADING
 SPACES, THE REQUIRED NUMBER OF LOADING SPACES ACCORDING
 TO SECTION 94-485 OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER OF
 LOADING SPACES IN THE ?PROJECT DATA? SECTION ON THE
 ?COVER SHEET? OF THE ?CONSTRUCTION DOCUMENTS?. [NOT
 SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONAL DETAILS OF THE PROPOSED LOADING
 SPACE(S) ON THE ?OVERALL SITE PLAN? AND ?ENLARGED WORK
 AREA SITE PLAN? SHEETS OF THE ?CONSTRUCTION DOCUMENTS?.
 [NOT SATISFIED]
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By kdefranc Date 2022-05-16 Time 16:30 Rev Time 0.00
Received By kdefranc Date 2022-05-16 Time 16:29 Sent To  
Notes
2022-05-16 16:30:205/16/22 ? FAILED
  
 PREVIOUS REVIEW COMMENTS
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A REVISED ?PLAN REVIEW REQUEST FORM?
 WITH AN UPDATED DESCRIPTION ACCOUNTING FOR THE NEW
 PROPOSED PARKING SPACES IN ADDITION TO THE PROPOSED
 ?INTERIOR RENOVATION PLANS FOR NEW OFFICE SPACES?.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 2. PLEASE PROVIDE A NARRATIVE PROVIDING CLARIFICATION
 ON THE PROPOSED REVISIONS. [SATISFIED PER RESPONSE
 PROVIDED AND ENTIRE PLAN SET PACKAGE SUBMITTAL]
 3. PLEASE CLEARLY IDENTIFY/INDICATE THE PROPOSED
 REVISIONS ON THE RESUBMITTED PLANS AND MATERIALS.
 [SATISFIED PER RESPONSE PROVIDED AND ENTIRE PLAN SET
 PACKAGE SUBMITTAL]
 4. PLEASE INDICATE THE CURRENT ZONING DISTRICT, THE
 PROPOSED USE OF THE SUBJECT STRUCTURE, THE EXISTING
 NUMBER OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE
 PARKING SPACES, THE REQUIRED NUMBER OF AUTOMOBILE
 (STANDARD AND ADA) AND BICYCLE PARKING SPACES ACCORDING
 TO SECTIONS 94-485 AND 94-486 OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER
 OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE PARKING
 SPACES IN THE ?PROJECT DATA? SECTION ON THE ?COVER
 SHEET? OF THE ?CONSTRUCTION DOCUMENTS?. [PARTIALLY
 SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED AISLE AND THE LOCATION OF THE PROPOSED
 BICYCLE PARKING FACILITY ON THE ?OVERALL SITE PLAN? AND
 ?ENLARGED WORK AREA SITE PLAN? SHEETS OF THE
 ?CONSTRUCTION DOCUMENTS?. [SATISFIED]
 6. PLEASE PROVIDE THE ELEVATION DRAWING AND DIMENSIONAL
 DETAILS FOR THE PROPOSED BICYCLE PARKING FACILITY ON
 THE ?ENLARGED WORK AREA SITE PLAN? SHEET OF THE
 ?CONSTRUCTION DOCUMENTS?. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE SUBMIT A PAVING PERMIT APPLICATION FOR THE
 PROPOSED PARKING SPACES.
  
  
 NEW REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE INDICATE THE EXISTING NUMBER OF LOADING
 SPACES, THE REQUIRED NUMBER OF LOADING SPACES ACCORDING
 TO SECTION 94-485 OF THE CITY?S ZONING AND LAND
 DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER OF
 LOADING SPACES IN THE ?PROJECT DATA? SECTION ON THE
 ?COVER SHEET? OF THE ?CONSTRUCTION DOCUMENTS?.
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONAL DETAILS OF THE PROPOSED LOADING
 SPACE(S) ON THE ?OVERALL SITE PLAN? AND ?ENLARGED WORK
 AREA SITE PLAN? SHEETS OF THE ?CONSTRUCTION DOCUMENTS?.
  
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By ajones Date 2022-03-09 Time 16:16 Rev Time 0.00
Received By kdefranc Date 2022-03-09 Time 16:13 Sent To  
Notes
2022-03-09 16:14:203/9/22 ? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE PROVIDE A REVISED ?PLAN REVIEW REQUEST FORM?
 WITH AN UPDATED DESCRIPTION ACCOUNTING FOR THE NEW
 PROPOSED PARKING SPACES IN ADDITION TO THE PROPOSED
 ?INTERIOR RENOVATION PLANS FOR NEW OFFICE SPACES?.
 2. PLEASE PROVIDE A NARRATIVE PROVIDING CLARIFICATION
 ON THE PROPOSED REVISIONS.
 3. PLEASE CLEARLY IDENTIFY/INDICATE THE PROPOSED
 REVISIONS ON THE RESUBMITTED PLANS AND MATERIALS.
 4. PLEASE INDICATE THE CURRENT ZONING DISTRICT, THE
 PROPOSED USE OF THE SUBJECT STRUCTURE, THE EXISTING
 NUMBER OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE
 PARKING SPACES, THE REQUIRED NUMBER OF AUTOMOBILE
 (STANDARD AND ADA) AND BICYCLE PARKING SPACES ACCORDING
 TO SECTIONS 94-485 AND 94-486 OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, AND THE PROPOSED NUMBER
 OF AUTOMOBILE (STANDARD AND ADA) AND BICYCLE PARKING
 SPACES IN THE ?PROJECT DATA? SECTION ON THE ?COVER
 SHEET? OF THE ?CONSTRUCTION DOCUMENTS?.
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE WIDTH OF
 THE PROPOSED AISLE AND THE LOCATION OF THE PROPOSED
 BICYCLE PARKING FACILITY ON THE ?OVERALL SITE PLAN? AND
 ?ENLARGED WORK AREA SITE PLAN? SHEETS OF THE
 ?CONSTRUCTION DOCUMENTS?.
 6. PLEASE PROVIDE THE ELEVATION DRAWING AND DIMENSIONAL
 DETAILS FOR THE PROPOSED BICYCLE PARKING FACILITY ON
 THE ?ENLARGED WORK AREA SITE PLAN? SHEET OF THE
 ?CONSTRUCTION DOCUMENTS?.
  
 ADDITIONAL REVIEW COMMENTS (THAT REQUIRE A SEPARATE
 PERMIT) TO BE ADDRESSED:
 1. PLEASE SUBMIT A PAVING PERMIT APPLICATION FOR THE
 PROPOSED PARKING SPACES.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  