Plan Review Details - Permit 22021216
Plan Review Stops For Permit 22021216
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 11:49 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2022-03-17 Time 16:40 Sent To  
Notes
2022-03-21 08:09:03PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2022-03-17 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By mpeterso Date 2022-04-13 Time 13:27 Rev Time 0.00
Received By mpeterso Date 2022-04-13 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-03-18 Cont ID  
Sent By mpeterso Date 2022-03-18 Time 14:17 Rev Time 0.00
Received By mpeterso Date 2022-03-18 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-06 Cont ID  
Sent By   Date 2022-04-06 Time   Rev Time 0.00
Received By bdolan Date 2022-04-06 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-03 Cont ID  
Sent By cwalker Date 2022-03-03 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-18 Cont ID  
Sent By jgomez Date 2022-04-18 Time 12:53 Rev Time 0.00
Received By jgomez Date 2022-04-15 Time 13:09 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-15 Time 07:26 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-02-28 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-15 Time 07:24 Rev Time 0.00
Received By medwards Date 2022-04-15 Time 07:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 07:17 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 07:17 Sent To  
Notes
2022-03-10 07:17:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22021216
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE TENANT SPACE NUMBER AT THIS
 ADDRESS. FBC 107.2.1
  
 2) SHEET A0: IN THE SCOPE OF WORK COLLIER COUNTY IS
 MENTIONED AS HAVING SHELL DOCUMENTS ON FILE. PLEASE
 REMOVE THIS AND MAKE SURE THE CITY OF WEST PALM BEACH
 IS REFERENCED. FBC 107.2.1
  
 3) PLEASE PROVIDE THE CLASSIFICATION OF THIS DRY
 CLEANING FACILITY AS DETERMINED IN FBC M DEFINITIONS.
  
 4) SHEET M1: PLEASE PROVIDE THE REQUIRED OUTDOOR AIR
 CALCULATIONS FOR EACH USE OF SPACE FOR THIS DRY
 CLEANER. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-06 Cont ID  
Sent By lcrespo Date 2022-04-06 Time 12:02 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 12:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-03-10 Cont ID  
Sent By lcrespo Date 2022-03-10 Time 14:17 Rev Time 0.00
Received By lcrespo Date 2022-03-10 Time 13:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-18 Cont ID  
Sent By jgomez Date 2022-04-18 Time 12:53 Rev Time 0.00
Received By jgomez Date 2022-04-18 Time 11:27 Sent To  
Notes
2022-04-15 13:09:35DIGITALLY SIGNED FILES UPLOADED UNDER SIGNATURES FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-04-13 Cont ID  
Sent By rmcphers Date 2022-04-13 Time 11:51 Rev Time 0.00
Received By rmcphers Date 2022-04-13 Time 11:51 Sent To  
Notes
2022-04-13 11:51:57SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 08:19 Rev Time 0.00
Received By rmcphers Date 2022-03-21 Time 08:19 Sent To  
Notes
2022-03-21 08:20:54SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL OF THE DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2022-03-10 07:19:07MECHANICAL SIGNATURE REVIEW FAILS. THE DIGITAL
 SIGNATURES ON THE DRAWINGS ARE A COPY OF THE ORIGINAL.
 ME