Plan Review Details - Permit 22021209
Plan Review Stops For Permit 22021209
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 12:09 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 12:09 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-04 Cont ID  
Sent By cpuell Date 2022-03-04 Time 16:28 Rev Time 0.00
Received By cpuell Date 2022-03-04 Time 16:28 Sent To  
Notes
2022-03-04 16:28:30BLDG 4 HAS THE ADDRESS OF 1665 BRANDYWINE RD UPDATED
 PERMIT
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-02 Cont ID  
Sent By ppetty Date 2022-06-02 Time 10:34 Rev Time 0.00
Received By ppetty Date 2022-06-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-04-15 Cont ID  
Sent By ppetty Date 2022-04-15 Time 08:28 Rev Time 0.00
Received By ppetty Date 2022-04-15 Time 08:27 Sent To  
Notes
2022-04-15 08:28:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.SEE F.D NOTE
 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By ppetty Date 2022-03-23 Time 08:33 Rev Time 0.00
Received By ppetty Date 2022-03-23 Time 08:31 Sent To  
Notes
2022-03-23 08:34:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.SEE F.D NOTE
 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-05-17 Cont ID  
Sent By cwalker Date 2022-05-17 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By pleduc Date 2022-03-31 Time   Rev Time 0.00
Received By pleduc Date 2022-03-31 Time 12:18 Sent To  
Notes
2022-03-31 12:22:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE HAS NO OBJECTION TO THE PROPOSED; HOWEVER, FOR THE
 OFFICIAL RECORD THE FOLLOWING IS REQUIRED.
  
 1) THERE IS AN INDICATION OF A CELL COMMUNICATOR;
 HOWEVER, THERE IS NO INDICATION OF WHERE IT WILL BE
 LOCATED.
  
 PLEASE PROVIDE A SITE PLAN SHOWING WHICH BUILDING AND A
 FLOOR PLAN SHOWING THE LOCATION OF THE PROPOSED.
  
  
 1A) THE APPLICATION INDICATES 1655 BRANDYWINE # 1;
 HOWEVER, OUR RECORDS INDICATES # 1 AT 1677.
  
 BLDG # 1 HAS ALSO BEEN ON ANOTHER APPLICATION 22021215,
 PLEASE CORRECT
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By pleduc Date 2022-03-04 Time   Rev Time 0.00
Received By pleduc Date 2022-03-04 Time 12:17 Sent To  
Notes
2022-03-04 12:17:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE HAS NO OBJECTION TO THE PROPOSED; HOWEVER, FOR THE
 OFFICIAL RECORD THE FOLLOWING IS REQUIRED.
  
 1) THERE IS AN INDICATION OF A CELL COMMUNICATOR;
 HOWEVER, THERE IS NO INDICATION OF WHERE IT WILL BE
 LOCATED.
  
 PLEASE PROVIDE A SITE PLAN SHOWING WHICH BUILDING AND A
 FLOOR PLAN SHOWING THE LOCATION OF THE PROPOSED.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-02 Cont ID  
Sent By ppetty Date 2022-06-02 Time 10:34 Rev Time 0.00
Received By ppetty Date 2022-05-16 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-15 Cont ID  
Sent By ppetty Date 2022-04-15 Time 08:28 Rev Time 0.00
Received By ppetty Date 2022-03-30 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-03-23 Time   Rev Time 0.00
Received By cdecoeur Date 2022-03-03 Time 06:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By hmoser Date 2022-03-14 Time 10:25 Rev Time 0.00
Received By hmoser Date 2022-03-14 Time 10:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-06-02 Cont ID  
Sent By ppetty Date 2022-06-02 Time 10:34 Rev Time 0.00
Received By ppetty Date 2022-06-02 Time 10:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By ppetty Date 2022-03-23 Time 08:38 Rev Time 0.00
Received By ppetty Date 2022-03-23 Time 08:38 Sent To  
Notes
***NONE***