| Plan Review Stops For Permit 22021209 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-31 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-31 |
Time |
12:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-04 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-04 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2022-03-04 16:28:30 | BLDG 4 HAS THE ADDRESS OF 1665 BRANDYWINE RD UPDATED | | | PERMIT | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-02 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-06-02 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-04-15 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-04-15 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2022-04-15 08:28:49 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.SEE F.D NOTE | | | 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB | | | FBC 107.1; FS 471/481 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-03-23 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-03-23 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2022-03-23 08:34:19 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.SEE F.D NOTE | | | 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | | VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB | | | FBC 107.1; FS 471/481 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-05-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-31 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2022-03-31 12:22:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | FIRE HAS NO OBJECTION TO THE PROPOSED; HOWEVER, FOR THE | | | OFFICIAL RECORD THE FOLLOWING IS REQUIRED. | | | | | | 1) THERE IS AN INDICATION OF A CELL COMMUNICATOR; | | | HOWEVER, THERE IS NO INDICATION OF WHERE IT WILL BE | | | LOCATED. | | | | | | PLEASE PROVIDE A SITE PLAN SHOWING WHICH BUILDING AND A | | | FLOOR PLAN SHOWING THE LOCATION OF THE PROPOSED. | | | | | | | | | 1A) THE APPLICATION INDICATES 1655 BRANDYWINE # 1; | | | HOWEVER, OUR RECORDS INDICATES # 1 AT 1677. | | | | | | BLDG # 1 HAS ALSO BEEN ON ANOTHER APPLICATION 22021215, | | | PLEASE CORRECT | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-04 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2022-03-04 12:17:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | FIRE HAS NO OBJECTION TO THE PROPOSED; HOWEVER, FOR THE | | | OFFICIAL RECORD THE FOLLOWING IS REQUIRED. | | | | | | 1) THERE IS AN INDICATION OF A CELL COMMUNICATOR; | | | HOWEVER, THERE IS NO INDICATION OF WHERE IT WILL BE | | | LOCATED. | | | | | | PLEASE PROVIDE A SITE PLAN SHOWING WHICH BUILDING AND A | | | FLOOR PLAN SHOWING THE LOCATION OF THE PROPOSED. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-02 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-05-16 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-04-15 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-03-30 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-03-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
cdecoeur |
Date |
2022-03-03 |
Time |
06:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2022-03-14 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2022-03-14 |
Time |
10:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-02 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-06-02 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-03-23 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-03-23 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|