Plan Review Details - Permit 22021128
Plan Review Stops For Permit 22021128
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-04-11 Cont ID  
Sent By pvalenti Date 2022-04-11 Time 07:36 Rev Time 0.00
Received By pvalenti Date 2022-04-11 Time 07:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By pvalenti Date 2022-05-16 Time 10:05 Rev Time 0.00
Received By pvalenti Date 2022-05-12 Time 17:18 Sent To  
Notes
2022-05-16 10:08:16PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION, PROVIDE DETAILS/SPECIFICATIONS
 FOR EXISTING FIRE/SMOKE RATED CURTAINS AT ELEVATOR
 LOBBIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By pvalenti Date 2022-04-14 Time 12:58 Rev Time 0.00
Received By pvalenti Date 2022-04-11 Time 07:36 Sent To  
Notes
2022-04-14 12:59:27PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 1210.3.2, THE URINAL PARTITIONS (BOTTOM
 MEASUREMENT) ON DETAIL PLAN SHEET G-103 ARE NOT TO
 CODE.
  
 2.) FBC B 906.9, THE FIRE EXTINGUISHER MEASUREMENT
 SHOWN ON PLAN SHEET G-103 IS NOT PER THIS CODE SECTION.
  
 3.) FBC B (DEFINITIONS COMMON PATH OF TRAVEL) & (1017.3
 EXIT ACCESS TRAVEL DISTANCES) THE COMMON PATHS OF
 TRAVEL ARE NOT CLEAR AND APPEAR TO BE MIXING WITH THE
 EXIT TRAVEL DISTANCES. THIS NEEDS TO BE CLARIFIED AS IN
 SEVERAL LOCATIONS THROUGH OUT PLANS THE MAXIMUM COMMON
 PATHS OF TRAVEL DISTANCES APPEAR TO BE EXCEEDING 100'.
  
 4.) FBC B 1004.5(TABLE) & FBC B 1007.1.1, PLAN SHEET
 B-101(SROA OPEN OFFICE), B-102(OFFICE 5), & B-104(OPEN
 OFFICE C), THE OCCUPANCY COUNT SHOWN IN THE SCHEDULE
 FOR OFFICE AREAS OF WORK IS ACCURATE PER FBC B TABLE
 1004.5 (BUSINESS) INDICATING TOTAL NUMBER OF PERSONS,
 BUT THE TABLES AND CHAIRS SHOWN ON THE PLAN INDICATE A
 MUCH HIGHER TOTAL NUMBER OF PERSONS. SOME AREAS SHOW
 EMPTY SPACES WHICH COULD INCLUDE MORE CHAIRS/TABLES
 INCREASING THE NUMBERS OF PEOPLE.
 IN THIS CASE, THESE SPACES HAVE MORE THAN 49 (FBC B
 TABLE 1006.2.1) PEOPLE, THE SECOND EXIT REQUIRED DOES
 NOT MEET THE SEPERATION DISTANCE. THE DOORWAYS MUST
 HAVE A SEPERATION DISTANCE OF NOT LESS THAN 1/3 OF THE
 OVERALL DIAGONAL LENGTH OF THE SPACE. AS IS, THIS DOES
 NOT COMPLY WITH FBC B 1007.1.1(EXCEPTION #2).
  
 5.) FBC B 107.2.1, PLAN SHEET B-102 (2ND LEVEL)
 CORRIDOR #210 APPEARS TO SHOW A 1 FOUR FIRE SEPERATION.
 PLEASE CONFIRM WHAT THE SEPARATION IS (DOOR OR WALL).
  
 6.) FBC B 3006.3, ELEVATOR LOBBY DETAILS FOR
 ENCLOSURES, DOORS, & EGRESS ARE REQUIRED.
  
 7.) FBC B 1004.5.1, IF THE INTENTION IS TO INCREASE THE
 OCCUPANT LOADS FOR 1ST (SROA OPEN OFFICE), 2ND (OFFICE
 5), & 4TH (OPEN OFFICES A & B) LEVEL AREAS OF WORK FROM
 THE REQUIREMENTS OF FBC B TABLE 1004.5, THEN YOU WILL
 HAVE TO CONFORM TO FBC B 1004.5.1 INCLUDING SUBMITTAL
 OF REQUIRED DOCUMENTS.
  
 8.) FBC B 107.2.1, PLEASE PROVIDE THE FOLLOWING
 FLOORING INFORMATION:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By mpeterso Date 2022-05-31 Time 13:13 Rev Time 0.00
Received By mpeterso Date 2022-05-31 Time 13:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-08 Cont ID  
Sent By mpeterso Date 2022-04-08 Time 14:12 Rev Time 0.00
Received By mpeterso Date 2022-04-08 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-13 Cont ID  
Sent By cwalker Date 2022-05-13 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-05-13 10:02:18SEE PREVIOUS PROVISO COMMENTS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-08 Cont ID  
Sent By cwalker Date 2022-03-08 Time   Rev Time 0.00
Received By cwalker Date 2022-03-08 Time   Sent To  
Notes
2022-03-08 13:41:39FIRE PROVISO COMMENTS:
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND/OR
 CEILINGS REQUIRES AN EVALUATION OF THE FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COMPLIANT COVERAGE.
 ANY AND ALL WORK ON THE FIRE ALARM, ACCESS CONTROL,
 AND/OR FIRE SPRINKLER SYSTEMS, INCLUDING DEMOLITION,
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING
 DEMOLITION.
 ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE ALARM
 AND/OR FIRE SPRINKLER) THAT EXCEEDS 4 HOURS IN DURATION
 SHALL HAVE A FIRE WATCH INSTITUTED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-31 Cont ID  
Sent By mpeterso Date 2022-05-31 Time 13:13 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-15 Cont ID  
Sent By pvalenti Date 2022-04-14 Time 12:58 Rev Time 0.00
Received By pvalenti Date 2022-03-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By medwards Date 2022-05-26 Time 13:07 Rev Time 0.00
Received By medwards Date 2022-05-26 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 10:10 Rev Time 0.00
Received By medwards Date 2022-04-05 Time 08:35 Sent To  
Notes
2022-04-05 10:18:19PLEASE PROVIDE A ROOF DRAWING INDICATING THE LOCATIONS
 OF THE CONDENSING UNITS AND HOW THEY WILL BE TIED DOWN.
 FBC 107.2.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 11:42 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-03-31 Cont ID  
Sent By rwbrown Date 2022-03-31 Time 15:54 Rev Time 0.00
Received By rwbrown Date 2022-03-31 Time 15:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By dbattles Date 2022-05-31 Time 10:48 Rev Time 0.00
Received By dbattles Date 2022-05-31 Time 10:48 Sent To  
Notes
2022-05-26 13:11:46DIGITAL SIGNATURES FOR MECHANICAL DRAWINGS APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-07 Cont ID  
Sent By dbattles Date 2022-04-07 Time 16:32 Rev Time 0.00
Received By dbattles Date 2022-04-07 Time 16:32 Sent To  
Notes
2022-04-05 10:13:17MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By jroach Date 2022-04-07 Time 16:26 Rev Time 0.00
Received By dbattles Date 2022-04-07 Time 16:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved