| 2022-04-14 12:59:27 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 1210.3.2, THE URINAL PARTITIONS (BOTTOM |
| | MEASUREMENT) ON DETAIL PLAN SHEET G-103 ARE NOT TO |
| | CODE. |
| | |
| | 2.) FBC B 906.9, THE FIRE EXTINGUISHER MEASUREMENT |
| | SHOWN ON PLAN SHEET G-103 IS NOT PER THIS CODE SECTION. |
| | |
| | 3.) FBC B (DEFINITIONS COMMON PATH OF TRAVEL) & (1017.3 |
| | EXIT ACCESS TRAVEL DISTANCES) THE COMMON PATHS OF |
| | TRAVEL ARE NOT CLEAR AND APPEAR TO BE MIXING WITH THE |
| | EXIT TRAVEL DISTANCES. THIS NEEDS TO BE CLARIFIED AS IN |
| | SEVERAL LOCATIONS THROUGH OUT PLANS THE MAXIMUM COMMON |
| | PATHS OF TRAVEL DISTANCES APPEAR TO BE EXCEEDING 100'. |
| | |
| | 4.) FBC B 1004.5(TABLE) & FBC B 1007.1.1, PLAN SHEET |
| | B-101(SROA OPEN OFFICE), B-102(OFFICE 5), & B-104(OPEN |
| | OFFICE C), THE OCCUPANCY COUNT SHOWN IN THE SCHEDULE |
| | FOR OFFICE AREAS OF WORK IS ACCURATE PER FBC B TABLE |
| | 1004.5 (BUSINESS) INDICATING TOTAL NUMBER OF PERSONS, |
| | BUT THE TABLES AND CHAIRS SHOWN ON THE PLAN INDICATE A |
| | MUCH HIGHER TOTAL NUMBER OF PERSONS. SOME AREAS SHOW |
| | EMPTY SPACES WHICH COULD INCLUDE MORE CHAIRS/TABLES |
| | INCREASING THE NUMBERS OF PEOPLE. |
| | IN THIS CASE, THESE SPACES HAVE MORE THAN 49 (FBC B |
| | TABLE 1006.2.1) PEOPLE, THE SECOND EXIT REQUIRED DOES |
| | NOT MEET THE SEPERATION DISTANCE. THE DOORWAYS MUST |
| | HAVE A SEPERATION DISTANCE OF NOT LESS THAN 1/3 OF THE |
| | OVERALL DIAGONAL LENGTH OF THE SPACE. AS IS, THIS DOES |
| | NOT COMPLY WITH FBC B 1007.1.1(EXCEPTION #2). |
| | |
| | 5.) FBC B 107.2.1, PLAN SHEET B-102 (2ND LEVEL) |
| | CORRIDOR #210 APPEARS TO SHOW A 1 FOUR FIRE SEPERATION. |
| | PLEASE CONFIRM WHAT THE SEPARATION IS (DOOR OR WALL). |
| | |
| | 6.) FBC B 3006.3, ELEVATOR LOBBY DETAILS FOR |
| | ENCLOSURES, DOORS, & EGRESS ARE REQUIRED. |
| | |
| | 7.) FBC B 1004.5.1, IF THE INTENTION IS TO INCREASE THE |
| | OCCUPANT LOADS FOR 1ST (SROA OPEN OFFICE), 2ND (OFFICE |
| | 5), & 4TH (OPEN OFFICES A & B) LEVEL AREAS OF WORK FROM |
| | THE REQUIREMENTS OF FBC B TABLE 1004.5, THEN YOU WILL |
| | HAVE TO CONFORM TO FBC B 1004.5.1 INCLUDING SUBMITTAL |
| | OF REQUIRED DOCUMENTS. |
| | |
| | 8.) FBC B 107.2.1, PLEASE PROVIDE THE FOLLOWING |
| | FLOORING INFORMATION: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | |
| | |