Plan Review Details - Permit 22021073
Plan Review Stops For Permit 22021073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By rmcdouga Date 2022-07-12 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2022-07-12 Time 09:46 Sent To  
Notes
2022-07-12 09:46:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROPOSED WORK INCLUDES BORING HOLES THROUGH
 EXISTING FLOOR SLABS IN A THRESHOLD BUILDING (MORE THAN
 3 STORIES IN HEIGHT) WHICH IS STRUCTURAL WORK. THIS
 PROJECT REQUIRES A STATE OF FLORIDA LICENSED GENERAL
 CONTRACTOR (CGC) TO PULL A BUILDING PERMIT FOR THE
 STRUCTURAL WORK. THE PENETRATION FIRESTOP SYSTEM FOR
 THE FIRE-RESISTANCE RATED FLOOR ASSEMBLIES SHOULD ALSO
 BE INCLUDED IN THE WORK OF THE GC. FS 489 & FS 553.71
  
 2) A THRESHOLD BUILDING SPECIAL INSPECTOR WILL BE
 REQUIRED TO PERFORM THE STRUCTURAL INSPECTIONS FOR THIS
 PROJECT. SUBMIT THE REQUIRED THRESHOLD INSPECTION
 DOCUMENTS. FBC AMENDMENTS 110.8.1
  
 3) PROVIDE A FIRESTOP DETAIL WITH A LISTED SYSTEM FOR
 THE FLOOR ASSEMBLY PENETRATIONS. FBC 714.2
 CREATED STOP FOR BUILDING TO REVIEW RATED ASSEMBLIES
 FOR NEW PENTETRATIONS MADE BY FLOOR DRAINS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By rmcdouga Date 2022-05-10 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2022-05-10 Time 14:22 Sent To  
Notes
2022-05-10 14:22:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROPOSED WORK INCLUDES BORING HOLES THROUGH
 EXISTING FLOOR SLABS IN A THRESHOLD BUILDING (MORE THAN
 3 STORIES IN HEIGHT) WHICH IS STRUCTURAL WORK. THIS
 PROJECT REQUIRES A STATE OF FLORIDA LICENSED GENERAL
 CONTRACTOR (CGC) TO PULL A BUILDING PERMIT FOR THE
 STRUCTURAL WORK. THE PENETRATION FIRESTOP SYSTEM FOR
 THE FIRE-RESISTANCE RATED FLOOR ASSEMBLIES SHOULD ALSO
 BE INCLUDED IN THE WORK OF THE GC. FS 489 & FS 553.71
  
 2) A THRESHOLD BUILDING SPECIAL INSPECTOR WILL BE
 REQUIRED TO PERFORM THE STRUCTURAL INSPECTIONS FOR THIS
 PROJECT. SUBMIT THE REQUIRED THRESHOLD INSPECTION
 DOCUMENTS. FBC AMENDMENTS 110.8.1
  
 3) PROVIDE A FIRESTOP DETAIL WITH A LISTED SYSTEM FOR
 THE FLOOR ASSEMBLY PENETRATIONS. FBC 714.2
2022-03-01 12:40:37CREATED STOP FOR BUILDING TO REVIEW RATED ASSEMBLIES
 FOR NEW PENTETRATIONS MADE BY FLOOR DRAINS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-12 Cont ID  
Sent By rmcdouga Date 2022-07-12 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2022-05-12 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-10 Cont ID  
Sent By rmcdouga Date 2022-05-10 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2022-03-03 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-01 Cont ID  
Sent By rwbrown Date 2022-03-01 Time 11:23 Rev Time 0.00
Received By rwbrown Date 2022-02-28 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-16 Cont ID  
Sent By rwbrown Date 2022-05-16 Time 08:53 Rev Time 0.00
Received By rwbrown Date 2022-05-16 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-07 Cont ID  
Sent By rwbrown Date 2022-03-07 Time 09:47 Rev Time 0.00
Received By rwbrown Date 2022-03-07 Time 09:43 Sent To  
Notes
2022-03-07 09:47:202ND PLUMBING REVIEW
  
 V7 FBC P - 2020 FLORIDA PLUMBING CODE
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 V7 FBC P -- 307.3 -- THE FIRE STOPPING DETAILS YOU HAVE
 PROVIDED STATE IN THE USE FOR 2" AND SMALLER PVC. THESE
 PENETRATIONS ARE FOR 3" PVC. PLEASE SUBMIT FIRE
 STOPPING DETAILS THAT ARE SPECIFIC TO THE PENTRANT AND
 TO THE CONSTRUCTION TYPE.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-01 Cont ID  
Sent By rwbrown Date 2022-03-01 Time 11:21 Rev Time 0.00
Received By rwbrown Date 2022-03-01 Time 11:04 Sent To  
Notes
2022-03-01 11:18:451ST PLUMBING REVIEW
  
 PLAN REVIEW: DENIED
  
 V7 FPC -- 307.3 PENETRATIONS OF FLOOR/CEILING
 ASSEMBLIES AND FIRERESISTANCE-RATED ASSEMBLIES. --
 PLEASE SHOW YOUR UL LISTED FIRE STOPPING DETAILS FOR
 REVIEW. EACH UL LISTING SHOULD BE SPECIFIC TO THE TYPE
 OF CONSTRUCTION AND BE CONSISTENT WITH THE PIPING.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-01 Cont ID  
Sent By rwbrown Date 2022-03-01 Time 11:22 Rev Time 0.00
Received By rwbrown Date 2022-03-01 Time 11:22 Sent To  
Notes
***NONE***