| Plan Review Stops For Permit 22021045 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-04-27 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-22 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2022-03-22 12:41:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OFEXHAUST AND INTAKES LOCATED | | | ON A EXTERIOR WALL, NOT THE ROOF. | | | | | | PER NFPA 96 | | | | | | 7.8.3 WALL TERMINATIONS. WALL TERMINATIONS SHALL BE | | | ARRANGED | | | WITH OR PROVIDED WITH THE FOLLOWING PROPERTIES: | | | (1) THE TERMINATION SHALL BE THROUGH A NONCOMBUSTIBLE | | | WALL | | | WITH A MINIMUM OF 3 M (10 FT) OF CLEARANCE FROM THE | | | OUTLET TO ADJACENT BUILDINGS, PROPERTY LINES, GRADE | | | LEVEL, | | | COMBUSTIBLE CONSTRUCTION, ELECTRICAL EQUIPMENT OR | | | LINES, | | | AND WITH THE CLOSEST POINT OF ANY AIR INTAKE OR | | | OPERABLE | | | DOOR OR WINDOW AT OR BELOW THE PLANE OF THE EXHAUST | | | TERMINATION. | | | (2) THE CLOSEST POINT OF ANY AIR INTAKE OR OPERABLE | | | DOOR OR WIN DOW ABOVE THE PLANE OF THE EXHAUST | | | TERMINATION SHALL BE A | | | MINIMUM OF 3 M (10 FT) IN DISTANCE, PLUS 76 MM (3 IN.) | | | FOR | | | EACH 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE | | | BEING | | | MEASURED FROM THE CENTER OF THE EXHAUST TERMINATION TO | | | THE | | | CENTER OF THE AIR INTAKE OR OPERABLE DOOR OR WINDOW, AS | | | INDI CATED IN FIGURE 7.8.3. | | | (3) A WALL TERMINATION IN A SECURED AREA SHALL BE | | | PERMITTED TO | | | BE AT A LOWER HEIGHT ABOVE GRADE IF ACCEPTABLE TO THE | | | AU THORITY HAVING JURISDICTION. | | | (4) THE EXHAUST FLOW SHALL BE DIRECTED PERPENDICULARLY | | | OUT WARD FROM THE WALL FACE OR UPWARD. | | | (5) ALL THE DUCTWORK SHALL BE PITCHED TO DRAIN THE | | | GREASE BACK | | | INTO THE HOOD(S) OR WITH A DRAIN PROVIDED TO BRING THE | | | GREASE BACK INTO A CONTAINER WITHIN THE BUILDING OR | | | INTO A | | | REMOTE GREASE TRAP. | | | (6) A LISTED GREASE DUCT SHALL COMPLY WITH SECTION 7.4; | | | OTHER | | | DUCTS SHALL COMPLY WITH SECTION 7.5. | | | (7) AN APPROVED FAN SHALL MEET THE REQUIREMENTS OF | | | 7.8.3(5) | | | AND OF 8.1.2 OR 8.1.4 | | | | | | PLEASE PROVIDE A DETAILED HORIZONTAL VIEW OF THAT WALL | | | SHOWING DIMENSIONS TO ALL WINDOWS, DOORS, OEPNINGS IN | | | COMPLIANCE WITH NFPA 96. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-03-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-08 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2022-03-08 16:12:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS LACK THE FLOOR PLAN INDICATING | | | THE INSTALLATION LOCATION PER THE MASTER. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOOR PLAN. | | | | | | | | | 2) THE SUBMITTED PLANS LACK THE DETAIL FOR ACTUAL | | | CEILING PENETRATIONS WITH EXISTING CONDITIONS AND | | | CONSTRUCTION DETAILS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE ACTUAL CEIING | | | PENETRATION DETAILS IN COMPLAINCE WITH NFPA 96. | | | | | | | | | 3) THE SUBMITTED PLANS LACK A ROOF PLAN AND VENTING | | | INDICATING THE ACTUAL EXISTING INSTALLATION LOCATION | | | AND AREA EQUIPMENT. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ROOF | | | VENTING PLAN WITH DIMENSIONS TO ALL EQUIPMENT IN | | | COMPLAINCE WITH NFPA 96. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
07:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-28 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-23 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-06 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-04 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-21 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-17 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-07 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-28 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-28 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2022-06-28 13:42:07 | THE CONDENSING UNITS APPEAR TO BE ON THE OTHER | | | PROPERTY. PROVIDE PROOF THAT THESE UNITS ARE LOCATED ON | | | THE SAME PROPERTY AS THE BUILDING THEY SERVE. | | | THE HOOD EXHAUST TERMINATION LOCATION FROM THE PROPERTY | | | LINE HAS NOT BEEN RESOLVED AT THIS TIME. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-06 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-06 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2022-05-06 10:45:54 | 1ST REVIEW FMC | | | PERMIT: 22021045 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-103: THE TERMINATION LOCATION FOR THE GREASE | | | DUCT DOES NOT MEET THE TERMINATION LOCATIONS OF FMC | | | 506.3.13.3 | | | 506.3.13.3 TERMINATION LOCATION. EXHAUST OUTLETS SHALL | | | BE LOCATED NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY | | | FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS, | | | ADJACENT BUILDINGS AND ADJACENT PROPERTY LINES AND | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) ABOVE | | | THE | | | ADJOINING GRADE LEVEL. EXHAUST OUTLETS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM OR | | | NOT LESS THAN 3 FEET (914 MM) ABOVE AIR INTAKE OPENINGS | | | INTO ANY BUILDING. | | | EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE NOT LESS | | | THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS OF THE | | | SAME OR CONTIGUOUS BUILDING, AN ADJACENT BUILDING, | | | ADJACENT PROPERTY LINE AND AIR INTAKE OPENINGS INTO A | | | BUILDING WHERE AIR FROM THE EXHAUST OUTLET DISCHARGES | | | AWAY FROM SUCH LOCATIONS. | | | | | | 2) PLEASE EXPLAIN HOW TERMINATING THE GREASE DUCT INTO | | | A PARKING LOT WOULD MEET 506.3.13.2 CREATING A PUBLIC | | | NUISANCE. | | | | | | 3) IT APPEARS THAT THE CONDENSING UNIT ARE TO BE | | | INSTALLED IN THE PARKING LOT. PLEASE SHOW THE REQUIRED | | | BARRIERS FOR THE EQUIPMENT PROTECTION. FMC 303.4 | | | | | | 4) SHEET M-108: I DO NOT SEE WHERE THE MUA-1 UNIT WILL | | | MEET THE 10 DEGREE DIFFERENCE WHEN HEAT WOULD BE | | | REQUIRED. FMC 508.1.1. IF USING THE EXCEPTION PLEASE | | | SHOW THE CALCULATIONS. | | | | | | 5) THE HOOD DRAWINGS SHOULD NOT BE FOR REFERENCE, | | | PLEASE REMOVE THIS NOTE. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | 2022-05-06 10:33:11 | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-04 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-04 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2022-04-04 11:56:39 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-22021045 | | | | | | CODES IN EFFECT: | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A HOOD GREASE DUCT RISER DIAGRAM | | | SHOWING THE GREASE DUCT DESIGN FOR ALL 3 HOOD SYSTEMS. | | | FMC 506.3 | | | | | | 2) PLEASE SHOW THAT THE EF?S FOR THE HOOD SYSTEMS | | | EXHAUST TERMINATION LOCATION IS A MINIMUM OF 3 FEET | | | FROM THE EXTERIOR DOOR. FMC 506.3.13.2 | | | | | | 3) PLEASE PROVIDE A SITE SURVEY PLAN SHOWING THE GREASE | | | DUCT TERMINATION LOCATION IS 10 FEET FROM ADJACENT | | | BUILDINGS AND THE PROPERTY LINE. FMC 506.3.13.3 | | | | | | 4) PLEASE PROVIDE THE DETAILS FOR THE MUA-01, MAKE-UP | | | AIR TEMPERATURE DOES NOT EXCEED 10 DEGREES AND PLEASE | | | SHOW THE AIR BALANCE REPORT FOR THIS TENANT SPACE. THE | | | MAKE UP AIR SHOULD REFLECT ALL 3 HOOD SYSTEMS. FMC 508 | | | | | | 5) PLEASE INDICATE IF THE WALL BEING PENETRATED BY THE | | | EXHAUST AND MAKE UP AIR IS A RATED WALL. IF IT IS | | | PLEASE SHOW THE PROTECTION REQUIRED. FMC 607 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-17 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-17 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2022-03-17 11:06:48 | PLEASE SEE FIRE PLAN REVIEWER COMMENTS BELOW: | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS LACK THE FLOOR PLAN INDICATING | | | THE INSTALLATION LOCATION PER THE MASTER. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOOR PLAN. | | | | | | | | | 2) THE SUBMITTED PLANS LACK THE DETAIL FOR ACTUAL | | | CEILING PENETRATIONS WITH EXISTING CONDITIONS AND | | | CONSTRUCTION DETAILS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE ACTUAL CEIING | | | PENETRATION DETAILS IN COMPLAINCE WITH NFPA 96. | | | | | | | | | 3) THE SUBMITTED PLANS LACK A ROOF PLAN AND VENTING | | | INDICATING THE ACTUAL EXISTING INSTALLATION LOCATION | | | AND AREA EQUIPMENT. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ROOF | | | VENTING PLAN WITH DIMENSIONS TO ALL EQUIPMENT IN | | | COMPLAINCE WITH NFPA 96. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-30 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-30 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2022-06-30 08:58:19 | SHEET M M-103 IS MISSING THE DIGITAL SIGNATURE OF THE | | | DESIGNER. FBC 107.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-28 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-28 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-06 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-06 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-04 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-04 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2022-04-04 12:00:59 | HOOD DRAWINGS BY CAPTIVE AIRE MUST BE SIGNED BY THE | | | DESIGNER. FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-17 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-17 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2022-03-17 11:10:09 | DESIGNER OF DRAWINGS MUST PRINT AND SIGN THEIR NAME ON | | | EACH DRAWING. FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|