| 2022-03-13 08:30:41 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | BU1635 BN4338 |
| | ASFPM CFM US-21-11935 |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. APPLICATION IS BY AN OWNER/BUILDER. O/B MAY NOT |
| | APPLY FOR A COMMERCIAL TYPE PERMIT. HAVE YOUR GENERAL |
| | CONTRACTOR SUBMIT APPLICATION FOR THIS PROJECT. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 2. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY |
| | LOCATION OF WORK. |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE AND INCLUDED BOUNDRY LINE SURVEY. |
| | |
| | 3.PROVIDE SITE SPECIFIC WIND DESIGN DATA PER: |
| | FBC BUILDING CHPT. 16 SECTION 1603.1.4 |
| | ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH) |
| | |
| | DESIGN WIND PRESSURES: |
| | WINDOWS AND DOORS ZONE 4 INT. / ZONE 5 CORNER |
| | (POSITVE/NEGATIVE) |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1. 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. 2.RISK CATEGORY. |
| | 3. 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 4. 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF |
| | (KN/M2). |
| | |
| | 4. REMOVE PLAN SHEET A3.0 FROM THIS SUBMITTAL. SHEET |
| | A3.0 IS PART OF THE COM-INT PERMIT 21100650 AND |
| | INCLUDES WORK NOT PART OF THIS WINDOW/DOOR SUBMITTAL. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5.PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE |
| | PROPOSED EXTERIOR STEEL AND ALUMINUM DOORS. |
| | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE |
| | VERSION, AND STATUS, FBC R 301. |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |