Plan Review Details - Permit 22021006
Plan Review Stops For Permit 22021006
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-04-13 Cont ID  
Sent By jwitmer Date 2022-04-13 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2022-04-13 Time 08:03 Sent To  
Notes
2022-04-13 08:02:49SHELL PORTION OF NEW CONSTRUCTION, FIRST BUILD OUT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By jwitmer Date 2022-04-13 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2022-04-13 Time 08:03 Sent To  
Notes
2022-04-13 14:10:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021006
 ADD: 413 S ROSEMARY # 181 (HARRY'S)
 CONT: SHAWMUT WOODWORKING AND SUPPLY
 TEL: 617-352-4380
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 13TH/ 2022
 ACTION: DENIED
  
 1) CITY PLACE MANAGEMENT STAMP OF APPROVAL. THE CITY
 PLACE RETAIL MANAGEMENT APPROVAL STAMP IS REQUIRED ON
 THE PLANS. FOR AN ALTERNATE, YOU MAY PROVIDE A LETTER
 FROM CITY PLACE RETAIL MANAGEMENT WHICH APPROVES THE
 SPECIFIC PLANS SUBMITTED UNDER THIS PERMIT.
  
 2A) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (4) LIST AUTHORITY RELEVANT
 BUILDING CODE AS THE FLORIDA BUILDING CODE (FAMILY OF
 CODES) 6TH EDITION (2017) AS THE CURRENT CODE BEING
 ENFORCED. PLEASE NOTE THE 7TH EDITION OF THE FLORIDA
 BUILDING CODES (FAMILY OF CODES) 2020 EDITION WAS
 ADOPTED STATE-WIDE ON DEC. 31ST/ 2020. PLEASE CORRECT
 THE CODE REFERENCES.
  
 2B) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (7) LIST THE PROJECT OCCUPANCY
 CLASSIFICATION AS, A-2, F-2, & M. FOR THE F-2 OCCUPANCY
 CLASSIFICATION LEASE PROVIDE WHAT TYPE OF ACTIVITY
 REQUIRES THIS OCCUPANCY CLASSIFICATION. COMMERCIAL
 KITCHENS NOT AFFILIATED WITH RESTAURANTS OR SIMILAR
 DINING FACILITIES AND MORE 2,500 SQUARE FEET IN AREA
 ARE CLASSIFIED AS A F-1 OCCUPANCY. SEE 2020
 FBC-BUILDING CODE SECTION 306.2.
  
 2C) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (7) LIST THE PROJECT OCCUPANCY
 CLASSIFICATION AS, A-2, F-2, & M. WHY IS A MERCANTILE
 OCCUPANCY LISTED AS AN OCCUPANCY GROUP? THE LIFE SAFETY
 PLAN DOES NOT SHOW ANY SALES TABLES NOR KIOSK? TO BE
 CONSIDERED ACCESSORY OCCUPANCY. THE AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 % OF THE
 FLOOR AREA (508.2.3) OTHERWISE IT IS CONSIDERED A MIXED
 USE 508.1 OF THE 2020 FBC-BUILDING CODE.
  
 2D) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (6) SHOULD TIE TO THE (8) ZONING
 USE GROUP.
  
 2E) I BELIEVE THIS PORTION OF THE BUIILDING IS 6
 STORIES TALL AND THE REMAINDER OF THE BUILDING IS
 18VERSES 20 STORIES. THIS TENANT SPACE IS THE 1ST
 BUILD-OUT OF SHELL SPACE AND IS CONSIDERED NEW WORK.
 PLEASE REMOVE ALL REFERENCES TO THE 2020 EXISTING
 BUILDING CODE ON ALL PLANS.
  
 3) SHEET GROUND FLOOR LIFE SAFETY PLAN:
 3A) CODE DATA APPLICABLE CODES STATES THE BUILDING CODE
 AS THE FLORIDA BUILDING CODE (FAMILY OF CODES) 6TH
 EDITION (2017) AS THE CURRENT CODE BEING ENFORCED.
 PLEASE NOTE THE 7TH EDITION OF THE FLORIDA BUILDING
 CODES (FAMILY OF CODES) 2020 EDITION WAS ADOPTED
 STATE-WIDE ON DEC. 31ST/ 2020. PLEASE CORRECT THE CODE
 REFERENCES.
  
 3B) THE LIFE SAFETY PLAN SHOWS 2 ACCESSIBLE SEATS AT
 THE BAR. THERE IS NO CUT SECTION THROUGH THE BAR
 SHOWING COMPLIANCE WITH SECTION 902.3 HEIGHT OF THE
 2020 FBC-ACCESSIBILITY CODE. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3C) NOTE ONLY, NO ACTION REQUIRED. DEFERRED SUBMITTALS/
 COMPONENTS AND CLADDING PRODUCT APPROVALS.
  
 4) S-000.10 COMPONENT & CLADDING CHART FOR BUILDING
 HEIGHTS < 60 FT. THE CHART HAS BOTH VULT AND VASD,
 THANK YOU. WHAT IS A BIT CONCERNING NEITHER THE WALL
 ZONES NOR ROOF ZONES ACTUALLY STATE WALL ZONES 4 & 5,
 ROOF ZONES, 1, 2, & 3, IT IS ASSUMED WHERE THE
 TRIBUTARY SQ. FEET START AND STOP FOR EACH ZONE?
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 5) S-101.00 & S3.00 BOTH SHOW DETAILS FOR BOLTED AND
 WELDED STEEL CONNECTIONS. THIS BUILDING CONTAINS EITHER
 BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) SHEET A-514. THE DETAIL SHOWS A 2HR. RATED
 MECHANICAL SPACE FOR KX FAN, THIS ROOM IS MEANT TO
 PROVIDE DUCT WRAPPED RATING FROM THE COOKING HOODS TO
 THE EXTERIOR LOUVER AT THE FACE OF THE BUILDING.
 NOTED THIS SHOULD COME IN AS:
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 104.11 ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT.
  
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY
 DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY
 SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO
 PERFORMANCE- BASED FIRE PROTECTION ANALYSIS AND DESIGN
 OF BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL
 REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED
 TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE
 ALTERNATIVE.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR
 EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO
 THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO
 SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 12) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-12 Cont ID  
Sent By mpeterso Date 2022-04-12 Time 12:51 Rev Time 0.00
Received By mpeterso Date 2022-04-12 Time 09:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By parking Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-04 Cont ID  
Sent By pleduc Date 2022-03-04 Time   Rev Time 0.00
Received By pleduc Date 2022-03-04 Time 13:49 Sent To  
Notes
2022-03-04 14:08:57FIRE PROVISO:
  
 HOOD & SUPPRESSION SYSTEMS SHALL BE INSTALLED
 UNDER SEPARATE PERMIT & SHOP DRAWINGS
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-19 Cont ID  
Sent By jgomez Date 2022-04-19 Time 10:07 Rev Time 0.00
Received By jgomez Date 2022-03-02 Time 07:52 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By medwards Date 2022-04-04 Time 17:07 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 17:07 Sent To  
Notes
2022-04-04 17:08:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22021006
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-050.00: UNDER THE CODE DATA INFORMATION,
 PLEASE PROVIDE THE CURRENT 2020 FBC CODES.
  
 2) PLEASE ADD A NOTE TO THE MECHANICAL DRAWING
 INDICATING THAT THE KITCHEN HOODS AND ASSOCIATED
 DUCTWORK WILL NOT BE REVIEWED UNDER THIS PERMIT AS THIS
 WILL BE REQUIRED TO HAVE A SEPARATE PERMIT AND REVIEW.
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 4) PLEASE PROVIDE A MECHANICAL DEMO DRAWING AND A
 COMPLETE SCOPE OF WORK FOR THE MECHANICAL DEMOLITION.
 FBC 107.2.1
  
 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE ACCORDING TO FMC 403.3.1.1 AND TABLE
 403.3.1.1.
  
 6) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS TENANT
 SPACE. FMC 508
  
 7) PLEASE SHOW THE MAKEUP AIR MEETS THE 10 DEGREE TEMP
 DIFFERENCE OR SHOW THE CALCULATIONS THAT THE MECHANICAL
 SYSTEM IS SIZED TO HANDLE THE LOAD. FMC 508.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-31 Cont ID  
Sent By rwbrown Date 2022-03-31 Time 06:32 Rev Time 0.00
Received By rwbrown Date 2022-03-30 Time 14:27 Sent To  
Notes
2022-03-31 06:33:001ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. PAGE P001, COMMENT #1 AND #10 - 2017 WPB AMEND 107.3
 - REFERENCE TO THE 2014 FPC NEEDS TO BE CURRENT CODE
 CYCLE. PLEASE CHANGE TO 2020 FPC.
  
 2. PAGE P001 - WATER HEATER DETAIL - 2020 FPC - 607.1.1
 TEMPERATURE LIMITING MEANS - THE THERMOSTAT ON THE
 WATER HEATER CANNOT BE THE LIMIT FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A DETAIL FOR SOMETHING OTHER
 THAN THE THERMOSTAT ON THE WATER HEATER EITHER AT THE
 WATER HEATERS OR AT EACH FIXTURE. THIS IS IN ADDITION
 TO THE PROTECTION FOR TEMPERED WATER.
  
 3. PAGE P501 - 2020 FPC 1003.3.1 - GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE
 WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS,
 OILS OR GREASE TO BE DISCHARGED. HAND SINKS INTENDED
 FOR HAND WASHING DO NOT RECEIVE GREASE WASTE AND SHALL
 NOT DISCHARGE TO THE GREASE WASTE.
  
 4. PERMITTING - 2017 WPB AMEND - 107.3 DUE TO A CHANGE
 IN PROCESS, THE BACKFLOW PERMIT AND GREASE INTERCEPTOR
 PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE
 OF THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT
 AN APPLICATION (TBD - TO BE DETERMINED) IF YOU DO NOT
 HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected] . YOU
 WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-19 Cont ID  
Sent By jgomez Date 2022-04-19 Time 10:02 Rev Time 0.00
Received By jgomez Date 2022-04-19 Time 09:20 Sent To  
Notes
2022-04-19 10:07:10SIGNATURE REVIEW:
  
 1- DIGITAL SIGNATURE OF THE ARCHITECT COULD NOT BE
 VERIFIED. ARCHITECT NEEDS TO HAVE ORIGINAL DIGITAL
 SIGNATURE IN ALL DRAWINGS WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 SEC. 61G1-16.003 F.A.C.
 NOTE: RESUBMIT ALL DRAWINGS ELECTRONICALLY WITH
 VERIFIABLE DIGITAL SIGNATURE
  
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
2022-04-04 17:10:25MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-18 Cont ID  
Sent By eschneid Date 2022-04-18 Time 17:03 Rev Time 1.00
Received By eschneid Date 2022-04-18 Time 17:03 Sent To  
Notes
2022-04-18 17:03:58FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 2) SHEETS A-326 AND A-513 ARE REFERENCED ON SHEET A-100
 BUT ARE NOT INCLUDED WITH THE PERMIT SUBMITTAL. PROVIDE
 THESE SHEETS.
  
 3) THE NORTH ELEVATION SHOWS CHANGES TO THE EXISTING
 FENESTRATION, INCLUDING THE ADDITION OF METAL PANELS
 AND WALL SECTIONS WHERE GLAZING CURRENTLY EXISTS. THE
 ROSEMARY SQUARE DEVELOPMENT REGULATIONS REQUIRE THAT
 THAT THERE IS 60% TRANSPARENCY THE FERN STREET FRONTAGE
 BETWEEN GRADE AND 10 FEET. PLEASE PROVIDE VERIFICATION
 THAT THIS CONTINUES TO BE MET AFTER THE FENESTRATION
 REPLACEMENT. PLEASE NOTE THAT THE LATEST SHELL PERMIT
 THAT THE CITY HAS ON FILE SHOWS THE EXISTING CONDITION
 AS HAVING EXACTLY 60% TRANSPARENCY, SO NO REDUCTION IN
 TRANSPARENCY IS PERMITTED.
  
 PLEASE NOTE: TRANSPARENCY MEANS BUILDING FENESTRATION
 ON NONRESIDENTIAL USES WHICH ALLOWS GROUND FLOOR VISUAL
 ACCESS BETWEEN A BUILDING AND ITS ACTIVE USES FROM THE
 PUBLIC SIDEWALK. PLEASE PROVIDE VERIFICATION THAT THE
 KITCHEN AREA WILL BE VISIBLE FROM THE SIDEWALK AND THE
 AREA BEHIND THE WINDOWS IS NOT BLOCKED BY A WALL,
 EQUIPMENT, ETC.
  
 4) THE EAST ELEVATION SHOWS CHANGES TO THE EXISTING
 FENESTRATION. THE ROSEMARY SQUARE DEVELOPMENT
 REGULATIONS REQUIRE THAT THAT THERE IS 60% TRANSPARENCY
 THE ROSEMARY AVENUE FRONTAGE BETWEEN GRADE AND 10 FEET.
 PLEASE PROVIDE VERIFICATION THAT THE FENESTRATION FOR
 THIS BAY DOES NOT REDUCE THE 566 SQUARE FEET OF
 FENESTRATION FROM THE LATEST SHELL APPROVAL.
  
 5) PLEASE EXPLAIN WHAT IS OCCURRING IN THE MEZZANINE.
 IS THIS OCCUPIABLE SPACE (EVEN IF JUST STORAGE)?
  
 6) THE AWNINGS REQUIRE A SEPARATE PERMIT WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  