| Plan Review Stops For Permit 22020997 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-20 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-20 |
Time |
18:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-14 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-14 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2022-05-14 13:21:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, CLARIFY SCOPE. APPLICATION IS FOR INTERIOR | | | RENOVATION, PLANS SHOW CONVERTING A GARAGE TO A CARPORT | | | AND WINDOW/DOOR REPLACEMENT. EITHER REVISE PLANS OR | | | PROVIDE A NEW APPLICATION. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-07-11 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-07-11 |
Time |
20:24 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-11 |
Time |
18:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-09 |
Time |
23:06 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-09 |
Time |
22:20 |
Sent To |
|
|
| Notes |
| 2022-03-09 23:06:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | 2. PROVIDE RISER DIAGRAM OF SERVICE. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-03-09 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-03-09 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-08-04 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-06-27 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-14 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-02-23 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-28 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-28 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-02 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-02 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2022-03-02 14:51:58 | PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THE MECHANICAL SYSTEMS BEING INSTALLED | | | ON THIS PROJECT. FBC EC R403.7 AND FBC RES M1401.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-02-24 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-02-24 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-20 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-20 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2022-06-28 08:53:35 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-14 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-14 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2022-03-02 14:53:20 | MECHANICAL SIGNATURE REVIEW APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-03 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-08-03 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-08-03 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-03-09 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-03-09 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2022-03-09 14:14:56 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PERMIT VALUE IS OVER 50% OF IMPROVEMENT VALUE OF HOME, | | | A LANDSCAPE PERMIT MUST BE APPLIED FOR PRIOR TO ZONING | | | APPROVAL. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|