Plan Review Details - Permit 22020962
Plan Review Stops For Permit 22020962
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-23 Cont ID  
Sent By dbattles Date 2022-08-23 Time 10:07 Rev Time 0.00
Received By dbattles Date 2022-08-23 Time 10:07 Sent To  
Notes
2022-08-23 10:08:28BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 22020962
 REVIEWED: AUGUST 23, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. AM103.1 EXITS REQUIRED.
  HOW MANY PEOPLE WOULD BE IN THE STRUCTURE?
 2. AM103.2
  IS THE EXIT DOOR EXISTING? WHAT IS THE WIDTH AND
 HEIGHT OF THE DOOR?
 3. AM103.3 TYPE OF LOCK
  WHAT TYPE OF LOCK IS ON THE EXIT DOOR? A PICTURE WOULD
 SUFFICE.
 4. LABEL EACH SPACE WITH THE SQ. FOOTAGE AND NAME OF
 THE SPACE.
 5. ARE THE BATHROOM WALLS EXISTING? IS SO, LABEL THEM
 AS EXISTING.
 6. IS THE 30X30 WINDOW NEW, OR EXISTING. IF EXISTING
 LABEL IT AS EXISTING. IF NEW, PLEASE PROVIDE A PRODUCT
 APPROVAL.
 7. IF EXIT DOOR IS NEW, PLEASE PROVIDE PRODUCT APPROVAL
 FOR IT,
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-24 Cont ID  
Sent By aoliver Date 2022-08-24 Time 08:21 Rev Time 0.00
Received By aoliver Date 2022-08-23 Time 10:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 12:13 Rev Time 0.00
Received By lcrespo Date 2022-02-17 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-08-23 Cont ID  
Sent By rwbrown Date 2022-08-23 Time 14:16 Rev Time 0.00
Received By rwbrown Date 2022-08-23 Time 14:16 Sent To  
Notes
2022-08-23 14:33:451ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PLEASE SHOW AN EXISTING
 AND PROPOSED FLOOR PLAN.
  
 2. 2020 FPC 405.3.1 - PLEASE SHOW THE MINIMUM DISTANCE
 FOR FIXTURES. YOU ARE SHOWING 24" FOR THE LAVATORIES,
 AND A MINIMUM OF 30" IS REQUIRED (15" FROM CENTER, BOTH
 WAYS).
  
 3. 2021 F.A.C. 202.3 - PLEASE SHOW COMPLIANCE WITH THE
 FLORIDA ACCESSIBLITY CODE.
  
 4. 2020 FPC 607.1 - PLEASE SHOW THE HOT AND/OR TEMPERED
 WATER THAT COMPLIES WITH 607
  
 5.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 11:47 Rev Time 0.00
Received By lcrespo Date 2022-02-22 Time 11:47 Sent To  
Notes
2022-02-22 12:13:3202/22/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF AN
 EXPIRED PERMIT FROM 6 TO 12 KIDS, AND NOW THERE IS A
 PERMIT FOR THE EXISTING STRUCTURE. WOULD YOU PLEASE
 PROVIDE A LETTER STATING THAT THE PROPOSED DAYCARE IS
 ONLY UP TO SIX CHILDREN? OTHERWISE, THIS PERMIT WILL
 REQUIRE ACCESSIBILITY COMPLIANCE REVIEW, ZONING REVIEW,
 FIRE REVIEW, AND BUILDING PER THE 305.2 GROUP E,
 DAYCARE FACILITIES FBC B.
  
 2. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM OF SANITARY AND WATER PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 3. WOULD YOU PLEASE PROVIDE A SOURCE OF HOT WATER AND
 THE LOCATION OF CONNECTION PER THE 2020 FBC SEC. FBC R
 2722.2.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. WOULD YOU PLEASE PROVIDE A DESCRIPTIVE SCOPE OF WORK
 TO BE DONE ON THE PLANS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 101.2 SCOPE. IF THIS REVIEW OF THESE PLANS
 INTEL THE STRUCTURE OF THIS BUILD, IT MAY REQUIRE A
 BUILDING, ELECTRICAL, MECHANICAL PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. IF A PERMIT IS RECORDED AND THE
 STRUCTURE HAS ONE, PLEASE PROVIDE IT.
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 07:32 Rev Time 0.00
Received By lcrespo Date 2022-02-22 Time 07:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 11:54 Rev Time 0.00
Received By lcrespo Date 2022-02-22 Time 11:54 Sent To  
Notes
***NONE***