Plan Review Details - Permit 22020961
Plan Review Stops For Permit 22020961
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-03 Cont ID  
Sent By jwitmer Date 2022-05-03 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2022-05-03 Time 08:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By jwitmer Date 2022-04-06 Time 08:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-04-06 08:25:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22020961
 ADD: 300 S AUSTRALIAN AVE. # 204
 CONT: LYON CONSULTING LLC
 TEL: 305-528-0516
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 06TH / 2022
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. THE PERMIT VALUATION FOR THE PROJECT IS
 DECLARED TO BE $39,500.00 DOLLARS. THE FLOOR PLAN WILL
 BE REQUIRED TO BE DRAWN BY A DESIGN PROFESSIONAL.
 PLEASE REVIEW THE FLORIDA STATUTE481.229 EXCEPTIONS;
 EXEMPTIONS FROM LICENSURE (1) (C) ANY OTHER TYPE OF
 BUILDING COSTING LESS THAN $25,000.00, EXCEPT A SCHOOL,
 AUDITORIUM, OR OTHER BUILDING INTENDED FOR PUBLIC USE,
 PROVIDED THAT THE SERVICES OF A REGISTERED ARCHITECT
 SHALL NOT BE REQUIRED FOR MINOR SCHOOL PROJECTS
 PURSUANT TO 1013.45.
 A DESIGN PROFESSIONAL WILL BE REQUIRED WITH SIGNED &
 SEALED (DIGITAL SIGNATURE) FOR THE FLOOR PLAN. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C).
  
 3) 2ND REQUEST. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP),
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By jwitmer Date 2022-03-21 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2022-03-21 Time 10:38 Sent To  
Notes
2022-03-21 11:32:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22020961
 ADD: 300 S AUSTRALIAN AVE. # 204
 CONT: LYON CONSULTING LLC
 TEL: 305-528-0516
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21ST/ 2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION DOES NOT INDICATE THE SCOPE
 OF WORK TO BE ACCOMPLISHED, OR THE SQUARE FOOTAGE OF
 AREA TO BE AFFECTED. THIS PERMIT WAS BROUGHT IN AS A
 COM-MISC., SOMEHOW THE PERMIT DESCRIPTION WAS ENTERED
 INTO THE COMPUTER AS A FLOOR REPLACEMENT?
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) THE PERMIT VALUATION FOR THE PROJECT IS DECLARED TO
 BE $39,500.00 DOLLARS. PLEASE REVIEW THE FLORIDA
 STATUTE481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE
 (1) (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
 A DESIGN PROFESSIONAL WILL BE REQUIRED WITH SIGNED &
 SEALED (DIGITAL SIGNATURE) FOR THE FLOOR PLAN. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C).
  
 3) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-30 Cont ID  
Sent By cwalker Date 2022-03-30 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By cwalker Date 2022-03-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-02 12:20:13FIRE COMMENTS:
 THE FLOOR PLAN AND/OR THE PERMIT APPLICATION DOES NOT
 INDICATE THE SCOPE OF WORK. SUBMIT THE TYPE OF FLOORING
 AND UNDERLAYMENT WITH THE TESTING AND CLASSIFICATION
 FOR PERFORMANCE UNDER FIRE CONDITIONS FOR ALL PRODUCTS.
 NFPA 101 10.2.7
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-05-03 Time   Rev Time 0.00
Received By aoliver Date 2022-05-02 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-06 Cont ID  
Sent By jwitmer Date 2022-04-06 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2022-03-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-03-21 Time   Rev Time 0.00
Received By cdecoeur Date 2022-03-01 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-03 Cont ID  
Sent By jwitmer Date 2022-05-03 Time 09:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By jwitmer Date 2022-04-06 Time 08:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-04-06 08:28:02THE PERMIT VALUATION FOR THE PROJECT IS DECLARED TO BE
 $39,500.00 DOLLARS. PROJECTS VALUED AT $25,000.00 OR
 GREATER REQUIRE A DESIGN PROFESSIONAL TO DRAW A FLOOR
 PLAN. PLEASE REVIEW THE FLORIDA STATUTE481.229
 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C) ANY OTHER
 TYPE OF BUILDING COSTING LESS THAN $25,000.00, EXCEPT A
 SCHOOL, AUDITORIUM, OR OTHER BUILDING INTENDED FOR
 PUBLIC USE, PROVIDED THAT THE SERVICES OF A REGISTERED
 ARCHITECT SHALL NOT BE REQUIRED FOR MINOR SCHOOL
 PROJECTS PURSUANT TO 1013.45.
 A DESIGN PROFESSIONAL WILL BE REQUIRED WITH SIGNED &
 SEALED (DIGITAL SIGNATURE) FOR THE FLOOR PLAN. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C).
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-21 Cont ID  
Sent By jwitmer Date 2022-03-21 Time 11:32 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-21 11:32:50THE PERMIT VALUATION FOR THE PROJECT IS DECLARED TO BE
 $39,500.00 DOLLARS. PLEASE REVIEW THE FLORIDA
 STATUTE481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE
 (1) (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
 A DESIGN PROFESSIONAL WILL BE REQUIRED WITH SIGNED &
 SEALED (DIGITAL SIGNATURE) FOR THE FLOOR PLAN. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C).
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2022-03-11 Cont ID  
Sent By aaponte Date 2022-03-11 Time 15:19 Rev Time 0.00
Received By aaponte Date 2022-03-11 Time 15:19 Sent To  
Notes
***NONE***