Plan Review Details - Permit 22020837
Plan Review Stops For Permit 22020837
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-12 Cont ID  
Sent By rmcdouga Date 2022-04-12 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2022-04-12 Time 16:10 Sent To  
Notes
2022-04-12 16:10:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A ROOF DIAGRAM SHOWING THE LOCATIONS OF THE
 SOLAR PANELS. SPECIFY THE DISTANCE FROM THE ROOF EDGES
 TO THE PANELS AND THE DISTANCES FROM THE PANELS TO THE
 HIPS OR RIDGES. SPECIFY THE ROOF SLOPE, THE ROOF
 HEIGHT, ROOF SHEATHING MATERIAL (INCLUDING THICKNESS)
 AND THE ROOF COVERING MATERIAL. FBC 107.2.1
  
 2) THE WIND LOAD DRAWINGS AND WIND DATA THAT WAS
 SUBMITTED IS FOR EXPOSURE CATEGORY B, SUBMIT THE SIGNED
 AND SEALED ENGINEERING FOR EXPOSURE CATEGORY C, FBC-R
 301
  
 3) SUBMIT A PLUMBING ISOMETRIC DRAWING SPECIFYING THE
 PIPING SIZES AND LOCATION. SHOW THE LOCATIONS OF THE
 TEMPERATURE AND PRESSURE RELIEF VALVE, TEMPERATURE
 CONTROL AND OTHER SYSTEM COMPONENTS. FBC-R M2301.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-03 Cont ID  
Sent By mpeterso Date 2022-03-03 Time 11:02 Rev Time 0.00
Received By mpeterso Date 2022-03-03 Time 11:02 Sent To  
Notes
2022-03-03 11:06:01ELECTRIC REVIEW FAILED
 1) INFORMATION PROVIDED DOES NOT INDICATE IF THIS SOLAR
 COLLECTOR HAS ANY ELECTRICAL COMPONENTS. PLEASE PROVIDE
 INFORMATION REQUIRED TO COMPLETE ELECTRIC REVIEW. FBC
 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-12 Cont ID  
Sent By rmcdouga Date 2022-04-12 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2022-02-17 Time 06:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-22 Cont ID  
Sent By lcrespo Date 2022-02-22 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2022-02-22 Time 07:25 Sent To  
Notes
2022-02-22 12:34:5602/22/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE AN ISOMETRIC FOR THE WATER
 RISER DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 2. WOULD YOU PLEASE TELL US IF DIRECTLY HEATS POTABLE
 WATER FOR A POTABLE WATER DISTRIBUTION SYSTEM, THE
 PIPE, FITTINGS, VALVES, AND OTHER COMPONENTS THAT ARE
 IN CONTACT WITH THE POTABLE WATER IN THE SYSTEM PER THE
 2020 FBC R 2902.5.5.2
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 17:54 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 17:47 Sent To  
Notes
2022-02-17 17:55:57SIGNATURE REVIEW:
  
 1- HARD COPY OF DRAWING ST.1 SUBMITTED HAVE A COPY OF A
 DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE NOT ALLOWED
 TO BE PRINTED. ALL DOCUMENTS PREPARED BY A LICENSED
 ENGINEER NEED TO HAVE THE ORIGINAL SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.004 FAC AND CHAPTER 471 F.S.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-25 Cont ID  
Sent By vbroglia Date 2022-02-25 Time 10:24 Rev Time 0.00
Received By vbroglia Date 2022-02-25 Time 10:24 Sent To  
Notes
***NONE***