| Plan Review Stops For Permit 22020815 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-28 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-28 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2022-07-28 13:53:27 | BUILDING PROVISO | | | THE INDOOR BAR ON SHEET A1.108 SHALL COMPLY WITH FBC | | | ACCESSIBILITY SECTION 904. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-18 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-15 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2022-07-18 14:30:44 | PLAN REVIEW COMMENTS FOR THIS REVISION | | | | | | 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC | | | FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THESE PLANS WERE NOT REVISED TO SHOW THE MISSING | | | DOOR. IN ORDER TO AVOID CONFUSION AND MAINTAIN | | | CONSISTENCY, PLEASE CORRECT THESE PLANS. THE FLOOR | | | PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND A1.269A SHOW | | | THE DOOR FROM THE FIRE LOBBY TO STAIR #2 HAS BEEN | | | ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT ACCESS FROM | | | THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT STAIRWAY. | | | | | | 2) NEW COMMENT. PROVIDE DETAILS/ELEVATIONS TO SHOW THAT | | | THE INDOOR BAR (0833A) ON PAGE A1.108 WILL COMPLY WITH | | | FBC ACCESSIBILITY SECTION 904. | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-05-10 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-05-04 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2022-05-09 17:27:16 | PLAN REVIEW COMMENTS FOR THIS REVISION | | | | | | 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC | | | FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET A1.108 CHANGES WERE MADE TO THE MEN AND | | | WOMEN GROUP BATHROOMS AND THEY ARE NOT CLOUDED. FBC | | | 107.2.1 | | | | | | 2) ALSO ON SHEET A1.108 THE DOORS FROM THE TENNIS | | | COURTS (0833) TO THE CIRCULATION AREA (0854) HAVE BEEN | | | ELIMINATED BUT ARE NOT CLOUDED. THIS EFFECTS EGRESS | | | FROM THE TENNIS COURT AREA. SUBMIT A NEW LIFE SAFETY | | | PLAN FOR THIS AREA WITH OCCUPANT LOADS, EXIT | | | SEPARATION, ETC. FBC CHAPTER 10 AND 107.3.5.1.1 | | | | | | 3) ON SHEET A1.112 THERE ARE NO LAVATORIES SHOWN IN THE | | | BATHROOMS FOR UNIT D1 - R1204. FBC 107.2.1 | | | | | | 4) ON SHEET A1.265 THERE IS A BATHTUB SHOWN INSIDE ONE | | | OF THE BEDROOMS OF UNIT B2 - R1303. FBC 107.2.1 | | | | | | 5) THE FLOOR PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND | | | A1.269A SHOW THE DOOR FROM THE FIRE LOBBY TO STAIR #2 | | | HAS BEEN ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT | | | ACCESS FROM THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT | | | STAIRWAY. | | | | | | 6) THE USABLE BATHROOMS HAVE NOT BEEN IDENTIFIED AS | | | SPECIFICATION A OR B AS SPECIFIED BY FAIR HOUSING | | | GUIDELINES FOR SOME OF THE ENLARGED UNIT PLANS. FAIR | | | HOUSING GUIDELINES REQUIREMENT 7(2) | | | | | | 7) THE REQUIRED CLEAR FLOOR SPACE FOR THE BATHROOMS HAS | | | NOT BEEN INDICATED ON SOME OF THE ENLARGED UNIT PLANS. | | | FOR EXAMPLE UNIT B 4.3 ON SHEET A1.512 DOES NOT APPEAR | | | TO HAVE THE REQUIRED CLEAR FLOOR SPACE OF 30" X 48" | | | OUTSIDE OF THE DOOR SWING. FAIR HOUSING GUIDELINES | | | REQUIREMENT 7(2) PLEASE CORRECT. | | | | | | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-27 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-24 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-05-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-05 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-03 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2022-05-05 08:48:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FIRE ALARM REVISIONS SHALL BE SUBMITTED SEPARATELY | | | UNDER THE PERMIT FOR THE FIRE ALARM | | | | | | 2) LOW VOLTAGE REVISIONS SHALL BE AS STATED IN #1 | | | | | | 3) LOAD CALCULATIONS SHOWN ON PAGE E601-A DEMANDS DO | | | NOT MATCH UP WITH THE DEMANDS % IN THE TABLE BASED ON | | | NUMBER OF UNITS. 220.84 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-06-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-05-31 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-04-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-04-15 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-28 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-28 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-07-22 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-05-27 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-05-10 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-06 |
Time |
11:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-03-03 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-23 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-13 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-13 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-28 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-28 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2022-04-28 15:10:18 | 1ST REVIEW FMC | | | PERMIT: 22020815 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SUBMIT THE MECHANICAL SIZING CALCULATIONS FOR | | | ALL OF THE UNITS THAT HAVE BEEN CHANGED AS IT APPEARS | | | THEY ARE NOW LARGER THAN THE ORIGINAL DESIGN. FEC | | | C403.2.1 | | | | | | 2) SHEET M202: THE NARRATIVE OF CHANGES INDICATE THIS | | | REVISION WAS FOR TOILET AND DRYER EXHAUST RISER | | | DIMENSIONS/LOCATIONS. NEITHER ARE ON THIS REVISED | | | DRAWING. | | | | | | 3) SHEET M202: THERE SEEMS TO BE A LAYER THAT IS | | | MISSING FROM THIS SHEET AS AREAS ARE MISSING FROM THE | | | LATEST DRAWING. THE FIRE LOBBY AND MECHANICAL ROOMS AT | | | THE ELEVATOR AREA AT THE BOTTOM OF THE DRAWING AND THE | | | CLOUD SEEMS TO HAVE COVERED UP SOME DUCTWORK AT THE TOP | | | RIGHT OF THE SHEET. | | | | | | 4) PLEASE SHOW THAT THE DUCTWORK SERVING THE CORRIDORS | | | AND THE RESIDENTIAL SUITES WILL MEET FMC 607.5.3 THE | | | DUCT SHALL NOT HAVE OPENINGS THAT COMMUNICATE THE | | | CORRIDOR WITH ADJACENT SPACES OR ROOMS. A FIRE DAMPER | | | IS REQUIRED AT THE RATED CORRIDOR WALL AT EACH SUITE. | | | | | | 5) THE NARRATIVE FOR THESE DRAWINGS INDICATE CHANGES | | | FOR TOILET AND DRYER EXHAUST RISER | | | DIMENSIONS/LOCATIONS. THERE ARE NO DIMENSIONS ON THESE | | | SHEETS. PLEASE ADD THEM OR ADD A NOTE TO THE SHEET | | | NUMBER WHERE THEY ARE LOCATED. | | | | | | 6) PLEASE ADD THE LIFE SAFETY SHEETS FOR THIS PROJECT | | | AS I NEED TO KNOW WHERE THE RATED WALL LOCATIONS ARE | | | LOCATED OR ADD THIS LAYER TO THE MECHANICAL DRAWINGS. | | | | | | 7) SHEET M.707: TE/R10 SHOULD HAVE THE FIRE RATED DUCT | | | AS WAS ON THE PREVIOUS TE /R3 IN THE SAME LOCATION. | | | | | | 8) SHEET M.707: PLEASE ADD NOTES FOR THE DRYER | | | MULTISTORY EXHAUST REQUIREMENTS IN FMC 504.10 | | | | | | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF | | | THE AIRSTREAM. | | | 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE | | | CONNECTED TO A STANDBY POWER SOURCE | | | ACCORDANCE WITH SECTION 2702 OF THE FLORIDA BUILDING | | | CODE, BUILDING. | | | 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN | | | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR | | | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. | | | 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-01 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-06-01 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-18 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-18 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-04-18 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-18 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-18 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2022-06-27 08:09:55 | ELECTRICAL SIGNATURES OK JLEAHY | | 2022-06-13 10:02:18 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-05-09 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-05-09 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2022-05-09 14:50:37 | THE DIGITAL SIGNATURE OF THE ENGINEER FOR THE PLUMBING | | | AND MECHANICAL SHEETS CHAD WISLER IS SELF CERTIFIED. | | | THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS REQUIRES | | | DIGITAL SIGNATURES TO BE CERTIFIED BY AN APPROVED THIRD | | | PARTY AGENCY. | | 2022-04-28 15:14:42 | THE ENGINEER FOR THE DIGITAL SIGNATURES ON | | | THEMECHANICAL DRAWINGS WILL NEED TO SUBMIT THIRD PARTY | | | VERIFIED DIGITAL SIGNTURES, THE ENGINEER CANNOT SELF | | | CERTIFY. ME | | 2022-04-18 13:14:56 | PLUMBING PAGES ARE SIGNED AND SEALED - RWB |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-21 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-07-21 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-07-21 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-29 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2022-04-29 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2022-04-29 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2022-04-29 15:22:30 | 1. PLEASE EXPLAIN HOW THE FOUR HOTEL ROOMS LOCATED | | | WITHIN THE RESIDENTIAL LINER ARE GOING TO WORK. HOW A | | | HOTEL GUEST CHECKING IN AT THE HOTEL LOBBY ACCESS THESE | | | UNITS? | | | 2. WAS THE TOTAL NUMBER OF UNITS MODIFIED OR JUST THE | | | INTERIOR LAYOUT OF THE UNITS? | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|