Plan Review Details - Permit 22020815
Plan Review Stops For Permit 22020815
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 13:02 Sent To  
Notes
2022-07-28 13:53:27BUILDING PROVISO
 THE INDOOR BAR ON SHEET A1.108 SHALL COMPLY WITH FBC
 ACCESSIBILITY SECTION 904.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-18 Cont ID  
Sent By rmcdouga Date 2022-07-18 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2022-07-15 Time 15:10 Sent To  
Notes
2022-07-18 14:30:44PLAN REVIEW COMMENTS FOR THIS REVISION
  
 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC
 FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THESE PLANS WERE NOT REVISED TO SHOW THE MISSING
 DOOR. IN ORDER TO AVOID CONFUSION AND MAINTAIN
 CONSISTENCY, PLEASE CORRECT THESE PLANS. THE FLOOR
 PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND A1.269A SHOW
 THE DOOR FROM THE FIRE LOBBY TO STAIR #2 HAS BEEN
 ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT ACCESS FROM
 THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT STAIRWAY.
  
 2) NEW COMMENT. PROVIDE DETAILS/ELEVATIONS TO SHOW THAT
 THE INDOOR BAR (0833A) ON PAGE A1.108 WILL COMPLY WITH
 FBC ACCESSIBILITY SECTION 904.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-10 Cont ID  
Sent By rmcdouga Date 2022-05-10 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2022-05-04 Time 10:45 Sent To  
Notes
2022-05-09 17:27:16PLAN REVIEW COMMENTS FOR THIS REVISION
  
 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC
 FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A1.108 CHANGES WERE MADE TO THE MEN AND
 WOMEN GROUP BATHROOMS AND THEY ARE NOT CLOUDED. FBC
 107.2.1
  
 2) ALSO ON SHEET A1.108 THE DOORS FROM THE TENNIS
 COURTS (0833) TO THE CIRCULATION AREA (0854) HAVE BEEN
 ELIMINATED BUT ARE NOT CLOUDED. THIS EFFECTS EGRESS
 FROM THE TENNIS COURT AREA. SUBMIT A NEW LIFE SAFETY
 PLAN FOR THIS AREA WITH OCCUPANT LOADS, EXIT
 SEPARATION, ETC. FBC CHAPTER 10 AND 107.3.5.1.1
  
 3) ON SHEET A1.112 THERE ARE NO LAVATORIES SHOWN IN THE
 BATHROOMS FOR UNIT D1 - R1204. FBC 107.2.1
  
 4) ON SHEET A1.265 THERE IS A BATHTUB SHOWN INSIDE ONE
 OF THE BEDROOMS OF UNIT B2 - R1303. FBC 107.2.1
  
 5) THE FLOOR PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND
 A1.269A SHOW THE DOOR FROM THE FIRE LOBBY TO STAIR #2
 HAS BEEN ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT
 ACCESS FROM THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT
 STAIRWAY.
  
 6) THE USABLE BATHROOMS HAVE NOT BEEN IDENTIFIED AS
 SPECIFICATION A OR B AS SPECIFIED BY FAIR HOUSING
 GUIDELINES FOR SOME OF THE ENLARGED UNIT PLANS. FAIR
 HOUSING GUIDELINES REQUIREMENT 7(2)
  
 7) THE REQUIRED CLEAR FLOOR SPACE FOR THE BATHROOMS HAS
 NOT BEEN INDICATED ON SOME OF THE ENLARGED UNIT PLANS.
 FOR EXAMPLE UNIT B 4.3 ON SHEET A1.512 DOES NOT APPEAR
 TO HAVE THE REQUIRED CLEAR FLOOR SPACE OF 30" X 48"
 OUTSIDE OF THE DOOR SWING. FAIR HOUSING GUIDELINES
 REQUIREMENT 7(2) PLEASE CORRECT.
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By jleahy Date 2022-06-27 Time 08:09 Rev Time 0.00
Received By jleahy Date 2022-06-24 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By jleahy Date 2022-05-05 Time 08:41 Rev Time 0.00
Received By jleahy Date 2022-05-03 Time 11:13 Sent To  
Notes
2022-05-05 08:48:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FIRE ALARM REVISIONS SHALL BE SUBMITTED SEPARATELY
 UNDER THE PERMIT FOR THE FIRE ALARM
  
 2) LOW VOLTAGE REVISIONS SHALL BE AS STATED IN #1
  
 3) LOAD CALCULATIONS SHOWN ON PAGE E601-A DEMANDS DO
 NOT MATCH UP WITH THE DEMANDS % IN THE TABLE BASED ON
 NUMBER OF UNITS. 220.84
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By pleduc Date 2022-06-03 Time   Rev Time 0.00
Received By pleduc Date 2022-05-31 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-19 Cont ID  
Sent By pleduc Date 2022-04-19 Time   Rev Time 0.00
Received By pleduc Date 2022-04-15 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-22 Cont ID  
Sent By aoliver Date 2022-07-22 Time 09:49 Rev Time 0.00
Received By aoliver Date 2022-05-27 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-10 Cont ID  
Sent By rmcdouga Date 2022-05-10 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2022-04-06 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-03 Cont ID  
Sent By lmarchan Date 2022-03-03 Time 15:01 Rev Time 0.00
Received By lmarchan Date 2022-02-23 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-13 Cont ID  
Sent By medwards Date 2022-06-13 Time 09:57 Rev Time 0.00
Received By medwards Date 2022-06-13 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By medwards Date 2022-04-28 Time 15:09 Rev Time 0.00
Received By medwards Date 2022-04-28 Time 15:09 Sent To  
Notes
2022-04-28 15:10:181ST REVIEW FMC
 PERMIT: 22020815
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE MECHANICAL SIZING CALCULATIONS FOR
 ALL OF THE UNITS THAT HAVE BEEN CHANGED AS IT APPEARS
 THEY ARE NOW LARGER THAN THE ORIGINAL DESIGN. FEC
 C403.2.1
  
 2) SHEET M202: THE NARRATIVE OF CHANGES INDICATE THIS
 REVISION WAS FOR TOILET AND DRYER EXHAUST RISER
 DIMENSIONS/LOCATIONS. NEITHER ARE ON THIS REVISED
 DRAWING.
  
 3) SHEET M202: THERE SEEMS TO BE A LAYER THAT IS
 MISSING FROM THIS SHEET AS AREAS ARE MISSING FROM THE
 LATEST DRAWING. THE FIRE LOBBY AND MECHANICAL ROOMS AT
 THE ELEVATOR AREA AT THE BOTTOM OF THE DRAWING AND THE
 CLOUD SEEMS TO HAVE COVERED UP SOME DUCTWORK AT THE TOP
 RIGHT OF THE SHEET.
  
 4) PLEASE SHOW THAT THE DUCTWORK SERVING THE CORRIDORS
 AND THE RESIDENTIAL SUITES WILL MEET FMC 607.5.3 THE
 DUCT SHALL NOT HAVE OPENINGS THAT COMMUNICATE THE
 CORRIDOR WITH ADJACENT SPACES OR ROOMS. A FIRE DAMPER
 IS REQUIRED AT THE RATED CORRIDOR WALL AT EACH SUITE.
  
 5) THE NARRATIVE FOR THESE DRAWINGS INDICATE CHANGES
 FOR TOILET AND DRYER EXHAUST RISER
 DIMENSIONS/LOCATIONS. THERE ARE NO DIMENSIONS ON THESE
 SHEETS. PLEASE ADD THEM OR ADD A NOTE TO THE SHEET
 NUMBER WHERE THEY ARE LOCATED.
  
 6) PLEASE ADD THE LIFE SAFETY SHEETS FOR THIS PROJECT
 AS I NEED TO KNOW WHERE THE RATED WALL LOCATIONS ARE
 LOCATED OR ADD THIS LAYER TO THE MECHANICAL DRAWINGS.
  
 7) SHEET M.707: TE/R10 SHOULD HAVE THE FIRE RATED DUCT
 AS WAS ON THE PREVIOUS TE /R3 IN THE SAME LOCATION.
  
 8) SHEET M.707: PLEASE ADD NOTES FOR THE DRYER
 MULTISTORY EXHAUST REQUIREMENTS IN FMC 504.10
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE
 ACCORDANCE WITH SECTION 2702 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By rwbrown Date 2022-06-01 Time 14:50 Rev Time 0.00
Received By rwbrown Date 2022-06-01 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By lcrespo Date 2022-04-18 Time 13:13 Rev Time 0.00
Received By rwbrown Date 2022-04-18 Time 13:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-18 Cont ID  
Sent By rmcdouga Date 2022-07-18 Time 14:43 Rev Time 0.00
Received By rmcdouga Date 2022-07-18 Time 14:43 Sent To  
Notes
2022-06-27 08:09:55ELECTRICAL SIGNATURES OK JLEAHY
2022-06-13 10:02:18MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcdouga Date 2022-05-09 Time 14:42 Rev Time 0.00
Received By rmcdouga Date 2022-05-09 Time 14:42 Sent To  
Notes
2022-05-09 14:50:37THE DIGITAL SIGNATURE OF THE ENGINEER FOR THE PLUMBING
 AND MECHANICAL SHEETS CHAD WISLER IS SELF CERTIFIED.
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS REQUIRES
 DIGITAL SIGNATURES TO BE CERTIFIED BY AN APPROVED THIRD
 PARTY AGENCY.
2022-04-28 15:14:42THE ENGINEER FOR THE DIGITAL SIGNATURES ON
 THEMECHANICAL DRAWINGS WILL NEED TO SUBMIT THIRD PARTY
 VERIFIED DIGITAL SIGNTURES, THE ENGINEER CANNOT SELF
 CERTIFY. ME
2022-04-18 13:14:56PLUMBING PAGES ARE SIGNED AND SEALED - RWB

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-21 Cont ID  
Sent By ckimmerl Date 2022-07-21 Time 09:30 Rev Time 0.00
Received By ckimmerl Date 2022-07-21 Time 09:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-29 Cont ID  
Sent By aaponte Date 2022-04-29 Time 15:22 Rev Time 0.00
Received By aaponte Date 2022-04-29 Time 15:06 Sent To  
Notes
2022-04-29 15:22:301. PLEASE EXPLAIN HOW THE FOUR HOTEL ROOMS LOCATED
 WITHIN THE RESIDENTIAL LINER ARE GOING TO WORK. HOW A
 HOTEL GUEST CHECKING IN AT THE HOTEL LOBBY ACCESS THESE
 UNITS?
 2. WAS THE TOTAL NUMBER OF UNITS MODIFIED OR JUST THE
 INTERIOR LAYOUT OF THE UNITS?
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.