Plan Review Details - Permit 22020748
Plan Review Stops For Permit 22020748
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-04-19 Cont ID  
Sent By rmcphers Date 2022-04-19 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2022-04-19 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-21 Cont ID  
Sent By rmcphers Date 2022-06-21 Time 14:17 Rev Time 0.00
Received By rmcphers Date 2022-06-21 Time 14:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-19 Cont ID  
Sent By rmcphers Date 2022-04-19 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2022-04-19 Time 13:46 Sent To  
Notes
2022-04-19 13:48:17GENERATOR ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SURVEY PER ZONING REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By mpeterso Date 2022-06-06 Time 12:02 Rev Time 0.00
Received By mpeterso Date 2022-06-03 Time 14:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 07:55 Rev Time 0.00
Received By mpeterso Date 2022-04-18 Time 10:36 Sent To  
Notes
2022-04-26 07:58:48ELECTRIC REVIEW FAILED
 1) PLEASE SHOW HOW THIS PROJECT COMPLIES WITH NEC
 700.3(F) REQUIREMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-11 Cont ID  
Sent By clfranci Date 2022-03-11 Time   Rev Time 0.00
Received By clfranci Date 2022-03-11 Time   Sent To  
Notes
2022-03-11 07:58:54THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEMS SHALL BE
 DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS BY
 CERTIFIED CONTRACTORS.
  
 2) THE FIRE ALARM SYSTEMS SHALL REMAIN ACTIVE
 THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-21 Cont ID  
Sent By rmcphers Date 2022-06-21 Time 14:17 Rev Time 0.00
Received By rmcphers Date 2022-05-25 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 07:58 Rev Time 0.00
Received By mpeterso Date 2022-03-07 Time 06:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By mpeterso Date 2022-06-06 Time 12:07 Rev Time 0.00
Received By mpeterso Date 2022-06-06 Time 12:07 Sent To  
Notes
2022-06-06 12:08:30ALL PLANS PASSED SIGNATURE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-19 Cont ID  
Sent By rmcphers Date 2022-04-19 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2022-04-19 Time 13:49 Sent To  
Notes
2022-04-19 13:53:15SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS LS1.1, A1.1, S0.1, E0.1, E1.1, E1.2, E1.3,
 E2.1, E2.2, E2.3, E3.3, E3.4 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By llouie Date 2022-06-10 Time   Rev Time 0.00
Received By llouie Date 2022-06-10 Time   Sent To  
Notes
2022-06-10 09:43:03ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) MINOR PLANNED DEVELOPMENT (PD) AMENDMENT REQUIRED
 FOR THE AS-BUILT PRIOR TO THE ISSUANCE OF A CERTIFICATE
 OF OCCUPANCY (C.O.). A HOLD HAS BEEN PLACED.
  
 (REFERENCE: PB CASE NO. 1068KK)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-18 Cont ID  
Sent By llouie Date 2022-03-18 Time   Rev Time  
Received By llouie Date 2022-03-18 Time   Sent To  
Notes
2022-03-18 16:26:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SURVEY OF THE PROPERTY OR A PARTIAL SURVEY OF THE
 SUBJECT AREA (AT MINIMUM) IS REQUIRED AS PART OF THIS
 PERMIT SUBMISSION.
  
 2.) A SEPARATE LANDSCAPE PERMIT, CONSISTENT WITH THE
 LANDSCAPE PLAN APPROVED AS PART OF PB 1068KK, APPROVED
 BY THE DEVELOPMENT SERVICES DEPARTMENT-PLANNING
 DIVISION ON 1/21/2022, SHALL BE REQUIRED PRIOR TO
 ZONING SIGN-OFF OF THIS PERMIT.
  
 3.) PERMIT PLANS DO NOT MATCH THE PLANS APPROVED AS
 PART OF PB 1068KK. A MINOR PD AMENDMENT REFLECTING THE
 AS-BUILT WILL BE REQUIRED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF COMPLETION. A HOLD HAS BEEN PLACED ON
 THE PERMIT.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CSPD (ST. MARY'S MEDICAL CENTER)
  
 * REFERENCE: PB 1068KK - MINOR PD AMENDMENT (GENERATOR
 ENCLOSURE AND SIDEWALKS)
  
 * SPOKE TO JOHN DMORE OF KIMLEY HORN ON 4/6/22. A MINOR
 AMENDMENT FOR THE AS-BUILT REQUIRED PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF COMPLETION (C.C.) A HOLD
 ON THE CC HAS BEEN PLACED IN COMMUNITY PLUS.
  