Plan Review Details - Permit 22020621
Plan Review Stops For Permit 22020621
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-05 Cont ID  
Sent By jleahy Date 2022-12-05 Time 13:20 Rev Time 0.00
Received By jleahy Date 2022-12-05 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-11-14 Cont ID  
Sent By pleduc Date 2022-11-14 Time   Rev Time 0.00
Received By pleduc Date 2022-11-14 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-17 Cont ID  
Sent By pleduc Date 2022-05-17 Time   Rev Time 0.00
Received By pleduc Date 2022-05-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By pleduc Date 2022-03-02 Time   Rev Time 0.00
Received By pleduc Date 2022-03-02 Time 16:21 Sent To  
Notes
2022-03-02 16:32:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF WHERE IS PROPOSED COOLER
 IS LOCATED WITHIN THE BUILDING.
  
 FOR THE OFFICAIL RECORD AND CONFIRMATION, PLEASE
 PROVIDE A FLOOR PLAN SHOWING WHERE THIS IS PROPOSED.
  
  
  
 2) THERE IS NO INDICATION OF PROVIDING FIRE SPRINKLER
 PROTECTION WITHIN THE COOLER AS REQUIRED PER NFPA 13 IN
 BUILDING PROTECTED WITH FIRE SPRINKLERS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT TO
 INSTALL FIRE SPRINKLER PROTECTION UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 3) THERE IS NO INDICATION OF EMERGENCY LIGHTING WITHIN
 THE COOLER OR TO PROVIDE EMEGENCY GENERATOR CONNECTION.
  
 PLEASE PROVIDE DETAILS FOR PROVIDING EMERGENCY LIGHTING
 THAT IS REQUIRED FOR THIS OCCUPANCY.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-05 Cont ID  
Sent By jleahy Date 2022-12-05 Time 13:21 Rev Time 0.00
Received By jleahy Date 2022-11-30 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-05 Cont ID  
Sent By dbattles Date 2022-11-30 Time 12:22 Rev Time 0.00
Received By shill Date 2022-11-08 Time 18:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-01 Cont ID  
Sent By shill Date 2022-06-01 Time 10:13 Rev Time 0.00
Received By shill Date 2022-05-16 Time 14:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-26 Cont ID  
Sent By shill Date 2022-03-26 Time 12:26 Rev Time 0.00
Received By shill Date 2022-03-01 Time 06:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By medwards Date 2022-12-01 Time 14:19 Rev Time 0.00
Received By medwards Date 2022-12-01 Time 14:19 Sent To  
Notes
2022-12-01 14:20:06AUDIT ONLY ME

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-11-30 Cont ID  
Sent By dbattles Date 2022-11-30 Time 12:51 Rev Time 0.00
Received By dbattles Date 2022-11-30 Time 12:51 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-11-22 Cont ID  
Sent By dbattles Date 2022-11-22 Time 13:15 Rev Time 0.00
Received By dbattles Date 2022-11-22 Time 12:16 Sent To  
Notes
2022-11-22 13:40:36PRIVATE PROVIDER PLAN REVIEW AND INSPECTIONS
 PLAN REVIEW AFFIDAVIT
 THE PLAN COMLIANCE AFFIDAVIT UPLOADED ON 5/16/22 AND IT
 LISTS SHEET 2007556AD DATED 11/24/21
  
 THE DATE IN THE DRAWING THAT WAS UPLOADED SAYS 11/23/20
 (I LOOKED FOR 11/24/21 TO APPEAR ANYWHERE ON THE
 DRAWING, BUT I DID NOT SEE IT REFERENCED)
 PLEASE UPDATE THE PLAN SHEET 2007556AD, OR ADJUST THE
 AFFIDAVIT TO THE ONE THAT IS CURRENT.
 ALSO, PLAN SHEET 2007556AD DATED 11/24/21 WAS UPLOADED
 WITH AN ORIENTATION ERROR.
 YOU CAN SEE IT IN PROJECTDOX THAT THERE IS WHITE SPACE
 ABOVE AND BELOW.
 IT LOOKS LIKE THE PDF PRINTED LANDSCAPE ON A PDF THAT
 IS SET TP PORTRAIT.
 PLEASE RE-UPLOAD SHEET 2007556AD AS WHAT HAS BEEN
 UPLOADED WON'T PRINT CORRECTLY.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 ASSISTANT BUILDING OFFICIAL
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-03-26 Time   Rev Time 0.00
Received By   Date 2022-03-26 Time   Sent To  
Notes
2022-03-26 12:25:20FS553.791, PRIVATE PROVIDER AFFIDAVIT WILL BE REQUIRED.
 THIS WILL BE REVIEWED PRIOR TO BUILDING DIVISION AUDIT.
 FOR ADDITIONAL INFORMATION CONTACT:
  
 JFD-TICE (PRIVATE PROVIDER)
 [email protected]
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-05 Cont ID  
Sent By jleahy Date 2022-12-05 Time 13:21 Rev Time 0.00
Received By jleahy Date 2022-12-05 Time 13:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-11-21 Cont ID  
Sent By ckimmerl Date 2022-11-21 Time 10:12 Rev Time 0.00
Received By ckimmerl Date 2022-11-21 Time 10:11 Sent To  
Notes
2022-11-21 10:12:50PROVISO: ANY NEW ROOF-MOUNTED MECHANICAL EQUIPMENT
 SHALL BE SCREENED WITH A SCREEN THAT IS EQUAL IN HEIGHT
 TO THE PROPOSED MECHANICAL EQUIPMENT.

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-31 Cont ID  
Sent By ckimmerl Date 2022-05-31 Time 10:28 Rev Time 0.00
Received By ckimmerl Date 2022-05-31 Time 10:24 Sent To  
Notes
2022-05-31 10:27:30REPEAT COMMENT:
  
 1. PLEASE PROVIDE INFORMATION INDICATING THE LOCATION
 OF ANY MECHANICAL EQUIPMENT TO BE LOCATED ON THE ROOF,
 AND PROVIDE INFORMATION TO CONFIRM COMPLIANCE WITH
 SCREENING REQUIREMENT.
  
 SHEET 001 SHOWING THE WALK-IN FREEZER UNIT SPECIFIES
 THAT A COMPRESSOR IS LOCATED ON THE ROOF OF THE
 BUILDING.
  
 CHRIS KIMMERLY
 [email protected] 822-1426

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By aaponte Date 2022-03-24 Time 15:38 Rev Time 0.00
Received By aaponte Date 2022-03-24 Time 15:38 Sent To  
Notes
2022-03-28 08:45:44PLEASE PROVIDE INFORMATION INDICATING THE LOCATION OF
 ANY MECHANICAL EQUIPMENT TO BE LOCATED ON THE ROOF, AND
 PROVIDE INFORMATION TO CONFIRM COMPLIANCE WITH
 SCREENING REQUIREMENT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439 OR [email protected]