| 2022-04-26 17:02:12 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 7TH EDITION (2020) & CITY OF W.P.B. |
| | CHAPTER 1 AMENDMENTS |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | 300 BANYAN BLVD. |
| | PERMIT #22020521 |
| | 170 MPH, EXPOSURE "D" |
| | FLOOD ZONE "X" |
| | HIGH-RISE BLDG. PER FBC 403 (12 STORIES, 152'-0" TO TOP |
| | OF OCCUPIED LEVEL) |
| | CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE |
| | RESISTANCE RATING OF BUILDING MATERIALS PER FBC |
| | 403.2.1.1) |
| | PROPOSED OCCUPANCY TYPE: (MIXED USE) B, S-2, A-3 |
| | BLDG. AND GARAGE ARE FULLY SPRINKLERED |
| | GARAGE IS ENCLOSED |
| | |
| | DENIED BY BUILDING |
| | |
| | THIS REVIEW IS FOR THE FOUNDATION AND THE BUILDING |
| | SUPER STRUCTURE. THE FIRST REVIEW WAS FOR THE |
| | FOUNDATION ONLY PER REQUEST. ADDITIONAL ITEMS WILL BE |
| | REQUIRED FOR THIS REVIEW. THE PLANS FOR THE COMPLETE |
| | BUILDING HAVE NOT BEEN SUBMITTED AT THIS TIME. PLEASE |
| | ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SITE PLANS ARE MISSING DIMENSIONS, SUCH AS THE |
| | DISTANCES TO THE PROPERTY LINES. PROVIDE A SITE PLAN |
| | WITH DIMENSIONS. |
| | |
| | 2) THE FLOOR PLANS ARE MISSING DIMENSIONS. PROVIDE |
| | DIMENSIONED FLOOR PLANS. THI IS NEEDED TO CHECK SUCH |
| | THINGS AS FIRE LOBBY SIZE PER FBC 3007.6, SEPARATION OF |
| | EXIT ACCESS STAIRWAYS FBC 403.5.1 & 1007.1, ETC. |
| | |
| | 3) THE DISTANCE TO THE PROPERTY LINE AT THE WEST |
| | ELEVATION APPEARS TO BE RATHER TIGHT. PROVIDE |
| | CALCULATIONS TO SHOWN THAT THE PERCENTAGES OF ALLOWABLE |
| | OPENINGS PER STORY ON THE WEST WALLS COMPLY WITH FBC |
| | 705.8.1 & TABLE 705.8. |
| | |
| | 4) PROVIDE A LIFE SAFETY PLAN. FBC CHAPTER 10 |
| | THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING: |
| | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 |
| | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 |
| | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 |
| | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 |
| | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 |
| | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC |
| | 1008.1.1 |
| | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND |
| | MEANS OF EGRESS FACTOR FBC1005.3.2 |
| | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 |
| | |
| | 5) PLEASE CLARIFY IF THE ATTACHED GARAGE IS DESIGNED TO |
| | BE ENCLOSED OR OPEN. IF IT IS AN OPEN GARAGE PROVIDE |
| | CALCULATIONS TO SHOW THAT IT COMPLIES WITH FBC 406.5.2. |
| | |
| | 6) SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY BUILDING |
| | THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE |
| | VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING |
| | AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO BE |
| | CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR |
| | THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE |
| | DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT |
| | LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, |
| | OPEN POSITION AND SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). |
| | |
| | 7) SHOW THAT THE FIRE SERVICE ELEVATOR LOBBY COMPLIES |
| | WITH FBC 3007.6.4 LOBBY SIZE. REGARDLESS OF THE NUMBER |
| | OF FIRE SERVICE ACCESS ELEVATORS SERVED BY THE SAME |
| | ELEVATOR LOBBY, THE ENCLOSED FIRE SERVICE ACCESS |
| | ELEVATOR LOBBY SHALL BE NOT LESS THAN 150 SQUARE FEET |
| | (14 M2) IN AN AREA WITH A DIMENSION OF NOT LESS THAN 8 |
| | FEET (2440 MM). SEE SHEET A6.1.2 (PG. 157) AND OTHER |
| | SHEETS. |
| | |
| | 8) SHOW COMPLIANCE. 403.6.1 FIRE SERVICE ACCESS |
| | ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN |
| | 120 FEET (36 576 MM), MEASURED FROM THE ELEVATION OF |
| | STREET-LEVEL ACCESS TO THE LEVEL OF THE HIGHEST |
| | OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE SERVICE ACCESS |
| | ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 3007. ALL REMAINING ELEVATORS, IF ANY, SHALL BE |
| | PROVIDED WITH PHASE I AND II EMERGENCY OPERATION. EACH |
| | FIRE SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF |
| | NOT LESS THAN 3,500 POUNDS (1588 KG). |
| | |
| | 9) PROVIDE A SCHEMATIC DIAGRAM OF THE FIRE SPRINKLERS. |
| | FBC 107.3.5.1 |
| | |
| | 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS, EXTERIOR WALL VENTS AND EXTERIOR DOOR TYPES. |
| | THESE ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE |
| | DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE |
| | BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. |
| | |
| | 11) FBC AMENDMENTS 107.3.4.1 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 12) SHOW COMPLIANCE WITH FBC 2304.12 FOR TERMITE |
| | PROTECTION. |
| | |
| | 13) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES |
| | FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR |
| | ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY |
| | SECTION 502.5. THERE HAVE BEEN ISSUES WITH EQUIPMENT OR |
| | SYSTEMS INSTALLED BELOW THE REQUIRED 98" IN THESE AREAS |
| | OF PARKING GARAGES. PLEASE PROVIDE NOTES ON THE |
| | DRAWINGS TO HELP AVOID THIS ISSUE. |
| | |
| | 14 ) THE VALUATION FOR THIS BUILDING HAS BEEN |
| | DETERMINED TO BE $43,968,715.77 BASED ON THE CURRENT |
| | ICC BUILDING VALUATION DATA. THE FOUNDATION AND |
| | SUPERSTRUCTURE PERMIT VALUATION WILL BE 80 PERCENT OF |
| | THAT TOTAL OR $35,174,972.61. THE REMAINDER WILL BE |
| | USED FOR THE VALUATION OF THE INTERIOR BUILD-OUT OF THE |
| | BUILDING. THE FBC 109.3 BUILDING PERMIT VALUATION. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 15) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR |
| | SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR |
| | THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, |
| | LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS |
| | OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING. |
| | WHEN APPLYING FOR THE PERMIT TO COMPLETE THE BUILDING, |
| | PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT THESE |
| | ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT BE |
| | CHARGED TWICE FOR THE SAME ITEM. |
| | |
| | 16) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | ****PROVISOS**** |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| | ENGINEERING (IF APPLICABLE). |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE |
| | FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS |
| | SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR |
| | PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS, |
| | STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS |
| | REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW |
| | AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION. |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH |
| | PRESSURES SHOWN ON SHEET S0.0.5) |
| | |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | |
| | SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | SWIMMING POOLS |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF |
| | VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL. |
| | |
| | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR |
| | TO C.O. |
| | |
| | SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED |
| | TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS |
| | TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE |
| | POUR. |
| | |
| | A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED |
| | TO BE PROVIDED PRIOR TO INSTALLATION. |
| | |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |