Plan Review Details - Permit 22020230
| Plan Review Stops For Permit 22020230 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-05-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-12 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-12 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-03 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-03 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2022-05-03 11:11:26 | ELECTRIC REVIEW FAILED | | | 1) ELECTRICAL DRAWINGS DSUBMITTED HAVE NO REFERENCE TO | | | A KITCHEN HOD. PLEASE SUBMIT THE CORRECT DOCUMENTS. FBC | | | 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-18 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-13 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-05 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-03 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-04-13 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-02 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-14 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-02 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-02 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2022-03-02 08:39:18 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22020230 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A SITE PLAN SHOWING THE HOOD EXHAUST | | | TERMINATION LOCATION IN RELATION TO THE SIDE WALK AND | | | THE AMENITY SEATING AREA. FBC 107.2.1 | | | | | | 2) IT IS UNCLEAR WITH SHEET 005 BUT IT APPEARS THAT THE | | | MUA FOR THE KITCHEN HOOD IS IN THE SAME LOCATION AS THE | | | GENERATOR THAT IS SHOWN ON THE ORIGINAL PROJECT | | | DRAWINGS. PLEASE SUBMIT DRAWINGS SHOWING THE MUA AND | | | THE HOOD EXHAUST TERMINATION LOCATION IN RELATION TO | | | THE ORIGINAL SITE PLAN DRAWING. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-13 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-13 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-03 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-03 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2022-05-03 11:17:01 | SIGNATURE REVIEW FAILED | | | 1) SHEET TITLED MECHANICHAL SCREENING DETAILS AN | | | ARCHITECT RICK GONZALEZ TITLE BLOCK WITHOUT THE | | | REQUIRED SEAL AND SIGNATURE. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | | | | PLEASE FOLLOW THE INSTRUCTIONS BELOW TO CORRECT THIS | | | ISSUE. | | | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-02 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-02 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
|