Plan Review Details - Permit 22020230
Plan Review Stops For Permit 22020230
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By mpeterso Date 2022-05-12 Time 10:30 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By mpeterso Date 2022-05-03 Time 11:09 Rev Time 0.00
Received By mpeterso Date 2022-05-03 Time 11:09 Sent To  
Notes
2022-05-03 11:11:26ELECTRIC REVIEW FAILED
 1) ELECTRICAL DRAWINGS DSUBMITTED HAVE NO REFERENCE TO
 A KITCHEN HOD. PLEASE SUBMIT THE CORRECT DOCUMENTS. FBC
 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-02-18 Cont ID  
Sent By pleduc Date 2022-02-18 Time   Rev Time 0.00
Received By pleduc Date 2022-02-18 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-13 Cont ID  
Sent By jleahy Date 2022-05-13 Time 15:50 Rev Time 0.00
Received By jleahy Date 2022-05-05 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-03 Cont ID  
Sent By mpeterso Date 2022-05-03 Time 11:17 Rev Time 0.00
Received By mpeterso Date 2022-04-13 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-02 Cont ID  
Sent By medwards Date 2022-03-02 Time 08:40 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 15:48 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By medwards Date 2022-03-02 Time 08:39 Rev Time 0.00
Received By medwards Date 2022-03-02 Time 07:36 Sent To  
Notes
2022-03-02 08:39:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22020230
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE HOOD EXHAUST
 TERMINATION LOCATION IN RELATION TO THE SIDE WALK AND
 THE AMENITY SEATING AREA. FBC 107.2.1
  
 2) IT IS UNCLEAR WITH SHEET 005 BUT IT APPEARS THAT THE
 MUA FOR THE KITCHEN HOOD IS IN THE SAME LOCATION AS THE
 GENERATOR THAT IS SHOWN ON THE ORIGINAL PROJECT
 DRAWINGS. PLEASE SUBMIT DRAWINGS SHOWING THE MUA AND
 THE HOOD EXHAUST TERMINATION LOCATION IN RELATION TO
 THE ORIGINAL SITE PLAN DRAWING. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-13 Cont ID  
Sent By jleahy Date 2022-05-13 Time 15:50 Rev Time 0.00
Received By jleahy Date 2022-05-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-03 Cont ID  
Sent By mpeterso Date 2022-05-03 Time 11:13 Rev Time 0.00
Received By mpeterso Date 2022-05-03 Time 11:13 Sent To  
Notes
2022-05-03 11:17:01SIGNATURE REVIEW FAILED
 1) SHEET TITLED MECHANICHAL SCREENING DETAILS AN
 ARCHITECT RICK GONZALEZ TITLE BLOCK WITHOUT THE
 REQUIRED SEAL AND SIGNATURE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 PLEASE FOLLOW THE INSTRUCTIONS BELOW TO CORRECT THIS
 ISSUE.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-02 Cont ID  
Sent By medwards Date 2022-03-02 Time 08:40 Rev Time 0.00
Received By medwards Date 2022-03-02 Time 08:40 Sent To  
Notes
***NONE***