Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-08 Cont ID  
Sent By rmcdouga Date 2022-03-08 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2022-03-08 Time 13:25 Sent To  
Notes
2022-03-08 13:47:59PROVISO
 ALL CUTS FOR THE OPENINGS IN THE STRUCTURAL FLOORS AND
 ROOF SHALL BE INSPECTED BY A FLORIDA LICENSED THRESHOLD
 INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By rmcdouga Date 2022-02-22 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2022-02-22 Time 10:42 Sent To  
Notes
2022-02-22 10:45:30PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED. PER THE RESPONSE LETTER, NO FIRE-RESISTIVE
 SHAFTS WILL BE CONSTRUCTED.
  
 2) RESOLVED. THE GREASE DUCT WILL BE WRAPPED IN FIRE
 WRAP AND WILL TERMINATE AT THE KITCHEN EXHAUST HOOD.
 THERE WILL NOT BE ANY FIRE-RESISTIVE SHAFTS
 CONSTRUCTED.
  
 3) NOT RESOLVED. [ SPECIFY THE LISTED ASSEMBLY AND THE
 SPECIFIC MATERIALS AND SPECIFICATIONS FOR IT'S
 INSTALLATION.] THAT WILL BE USEDPROVIDE A DETAIL
 SHOWING HOW THE DRAFTSTOPPING MATERIAL AROUND THE
 GREASE DUCT PENETRATION WILL BE SUPPORTED. SHOW AN
 APPROVED LISTED ASSEMBLY FOR A TWO HOUR FIRE-RESISTIVE
 RATING. FBC 718.3.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 5) NEW COMMENT. NOTE: IF A FIRE-RESISTIVE RATED SHAFT
 WILL BE CONSTRUCTED SUBMIT THE DETAILS FOR THE LISTED
 SHAFT ASSEMBLY THAT WILL BE USED. FBC 713.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-16 Cont ID  
Sent By rmcdouga Date 2022-02-16 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-02-16 Time 17:14 Sent To  
Notes
2022-02-16 17:13:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT DRAWINGS THAT SHOW THE LISTED ASSEMBLY THAT
 WILL BE USED TO CONSTRUCT THE PROPOSED 2 HOUR
 FIRE-RESISTANCE RATED GREASE DUCT SHAFT. FBC 713.4
  
 2) SHOW COMPLIANCE WITH FBC 713.11 FOR HOW THE BOTTOM
 OF THE SHAFT WILL BE ENCLOSED AT THE BOTTOM.
  
 3) PROVIDE A DETAIL SHOWING HOW THE DRAFTSTOPPING
 MATERIAL AROUND THE GREASE DUCT PENETRATION WILL BE
 SUPPORTED. SHOW AN APPROVED LISTED ASSEMBLY FOR A TWO
 HOUR FIRE-RESISTIVE RATING. FBC 718.3.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-08 Cont ID  
Sent By lmarchan Date 2022-03-08 Time 16:05 Rev Time 0.00
Received By lmarchan Date 2022-03-03 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-02 Cont ID  
Sent By lmarchan Date 2022-03-02 Time 13:10 Rev Time 0.00
Received By lmarchan Date 2022-02-17 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-16 Cont ID  
Sent By rmcdouga Date 2022-02-16 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-02-04 Time 05:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-03-08 Cont ID  
Sent By medwards Date 2022-03-08 Time 08:24 Rev Time 0.00
Received By medwards Date 2022-03-08 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-02-22 Cont ID  
Sent By medwards Date 2022-02-22 Time 09:44 Rev Time 0.00
Received By medwards Date 2022-02-17 Time 18:09 Sent To  
Notes
2022-02-22 09:44:012ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22020199
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPDATE THE PERMIT APPLICATION TO SHOW THIS IS
 VERTICAL GREASE DUCT FOR FUTURE TENANT.
  
 2) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF
 THIS VERTICAL GREASE DUCT IN THIS EXISTING BUILDING ON
 EACH FLOOR. THIS SHOULD SHOW EACH FLOOR AND HOW THE
 GREASE DUCT WILL BE ACCESSED AT EACH FLOOR. FBC M
 506.3.8
  
 4) PLEASE SHOW ALL CHANGES OF DIRECTION FOR THIS
 VERTICAL GREASE DUCT AND THE CLEANOUTS REQUIRED FOR THE
 CHANGES IN DIRECTION. FBC M 506.3.8
  
 5) PLEASE SHOW THE UL LISTING FOR THE FIRE SEPARATION
 FOR THE TENANT SPACE SEPARATION AT THE FLOOR CUT OUT
 FOR THE DUCT. FBC 107.2.1
  
 6) THERE IS A NOTE ON THE DRAWING SUBMITTED CALLING FOR
 A DEDICATED SHAFT, PLEASE PROVIDE THE ARCHITECTURAL
 DRAWINGS OF THIS SHAFT AND THE UL LISTING FOR THE FIRE
 RATING. FBC 107.2.1
  
  
 7) HOOD PLAN SHEET:2 MENTIONS NOTES BUT THERE ARE NO
 NOTES ON THIS DRAWING. PLEASE SHOW THESE NOTES. FBC
 107.2.1
  
  
  
 9) SHEET M-03 ROOF PLAN: UNDER DISCHARGE NOTES THE 2ND
 NOTE INDICATES A MINIMUM OF 40 INCHES ABOVE THE ROOF
 STRUCTURE. AS THIS AREA OF THE BUILDING WILL HAVE
 PEDESTRIANS THE HOOD EXHAUST WILL NEED TO MEET FBC M
 SECTION 506.3.13.3 EXHAUST OUTLETS SHALL BE LOCATED NOT
 LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM PARTS OF
 THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS
 AND ADJACENT PROPERTY LINES AND SHALL BE LOCATED NOT
 LESS THAN 10 FEET (3048 MM) ABOVE THE ADJOINING GRADE
 LEVEL.
  
 10) SHEET M-03: PLEASE SHOW THE DIRECTION OF THE
 EXHAUST FLOW AT THE TERMINATION LOCATION. FBC M
 506.3.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE
 NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT
 BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE
 OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST
 OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS.
  
 11) THIS PROJECT WAS STARTED WITHOUT PERMITS AND THE
 FIELD APPLIED GREASE DUCT ENCLOSURE HAS ALREADY BEEN
 INSTALLED. THERE HAVE BEEN NO GREASE DUCT TEST. THE
 FIELD APPLIED GREASE DUCT ENCLOSURE SHALL BE REMOVED
 AND THE GREASE DUCT TEST SHALL BE PERFORMED AND PASSED
 BEFORE THE FIELD APPLIED GREASE DUCT ENCLOSURE CAN BE
 REINSTALLED. FBC M 506.3.2.5
  
  
 13) SHEET M-03: PLEASE SHOW THE FIELD APPLIED GREASE
 DUCT ENCLOSURE ON THE ROOF GREASE DUCT AND HOW THIS
 WILL BE PROTECTED FROM THE WEATHER. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By medwards Date 2022-02-17 Time 18:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 10:26 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 10:26 Sent To  
Notes
2022-02-14 10:26:471ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22020199
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPDATE THE PERMIT APPLICATION TO SHOW THIS IS
 VERTICAL GREASE DUCT FOR FUTURE TENANT.
  
 2) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF
 THIS VERTICAL GREASE DUCT IN THIS EXISTING BUILDING.
 THIS SHOULD SHOW EACH FLOOR AND THE EXHAUST TERMINATION
 ON THE ROOF. THERE IS GREEN SPACE ON THIS ROOF, PLEASE
 SHOW WHERE THE TERMINATION LOCATION WILL BE LOCATED IN
 THIS GREEN SPACE AREA. FBC 107.2.1
  
 3) THE FIELD WRAPPED GREASE DUCT SHALL BE CONTINUOUSLY
 WRAPPED FROM THE ORIGINATION OF THE DUCT TO THE OUTLET
 TERMINAL. FBC M 506.3.11.2
  
 4) PLEASE SHOW ALL CHANGES OF DIRECTION FOR THIS
 VERTICAL GREASE DUCT AND THE CLEANOUTS REQUIRED FOR THE
 CHANGES IN DIRECTION. FBC M 506.3.8
  
 5) PLEASE SHOW THE UL LISTING FOR THE FIRE SEPARATION
 FOR THE TENANT SPACE SEPARATION, FLOOR, FBC 107.2.1
  
 6) THERE IS A NOTE ON THE DRAWING SUBMITTED CALLING FOR
 A DEDICATED SHAFT, PLEASE PROVIDE THE ARCHITECTURAL
 DRAWINGS OF THIS SHAFT AND THE UL LISTING FOR THE FIRE
 RATING. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-03-02 Cont ID  
Sent By dbattles Date 2022-03-02 Time 10:47 Rev Time 0.00
Received By dbattles Date 2022-03-02 Time 10:47 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-02-17 Cont ID  
Sent By shill Date 2022-02-17 Time 06:58 Rev Time 0.00
Received By shill Date 2022-02-17 Time 06:58 Sent To  
Notes
2022-02-17 06:59:05MASTER 21050305
  
 I HAVE BEEN ADVISED THAT A PRIVATE PROVIDER DID AN
 INSPECTION FOR THIS WORK DONE WITHOUT PERMITS, BUT A
 NOTICE TO BUILDING OFFICIAL WAS NOT UPLOADED TO
 PROJECTDOX.
  
 FS553.791, SUBMIT A NOTICE TO BUILDING OFFICIAL.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By medwards Date 2022-03-08 Time 08:24 Rev Time 0.00
Received By medwards Date 2022-03-08 Time 08:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 10:26 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 10:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By aaponte Date 2022-03-08 Time 15:09 Rev Time 0.00
Received By aaponte Date 2022-03-08 Time 15:09 Sent To  
Notes
2022-03-08 15:10:19PROVISO: LANDSCAPE SHALL BE PROVIDED AROUND MECHANICAL
 EQUIPMENT TO SCREEN IT FROM VIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-18 Cont ID  
Sent By aaponte Date 2022-02-18 Time 08:45 Rev Time 0.00
Received By aaponte Date 2022-02-18 Time 08:45 Sent To  
Notes
2022-02-18 08:45:52PROVISO: LANDSCAPE SHALL BE INSTALLED AROUND THE
 MECHANICAL EQUIPMENT TO SCREEN IT FROM VIEW.