Plan Review Details - Permit 22020197
Plan Review Stops For Permit 22020197
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-07 Cont ID  
Sent By rmcdouga Date 2022-09-07 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2022-09-07 Time 10:29 Sent To  
Notes
2022-09-07 10:28:23PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I DID NOT SEE THE ENGINEERING FOR THE PRECAST
 GENERATOR PAD. UNLESS YOU ARE DOING A CAST IN PLACE
 GENERATOR SLAB, YOU WILL NEED TO SUBMIT THE ENGINEERING
 FOR THE PREFABRICATED GENERATOR PAD THAT YOU WILL BE
 USING. FBC-R301
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-23 Cont ID  
Sent By rmcdouga Date 2022-08-23 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2022-08-23 Time 09:01 Sent To  
Notes
2022-08-23 09:15:32PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NEW ENGINEERING DOES NOT INCLUDE THE DESIGN FOR
 THE STAND THAT WILL BE USED TO ELEVATE THE GENERATOR
 FOR FLOOD DESIGN. THE GENERATOR IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA (AE). THE GENERATOR WILL NEED TO BE
 RAISED TO OR ABOVE THE ELEVATION OF THE FINISHED FLOOR
 OF THE DWELLING. SHOW HOW COMPLIANCE WITH THIS WILL BE
 MET. FBC-R322.1.6
  
 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By rmcdouga Date 2022-08-02 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2022-07-26 Time 11:21 Sent To  
Notes
2022-05-12 11:31:10PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [ THE ENGINEERING THAT WAS SUBMITTED
 FOR THE PREFABRICATED GENERATOR PAD AND THE STAND ARE
 NOT ACCEPTABLE. THE PROJECT IS LOCATED IN EXPOSURE
 CATEGORY D AND A 170 MPH VULT WIND SPEED. THE DRAWING
 NEEDS TO SPECIFY THE MAXIMUM DIMENSIONS AND THE MINIMUM
 WEIGHT REQUIREMENTS FOR THE GENERATOR.
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) FBC AMENDMENTS 107.2.1 ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-07-06 Time 14:48 Rev Time 0.00
Received By rmcdouga Date   Time 14:48 Sent To  
Notes
2022-03-23 15:09:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING
 FOR THE PREFABRICATED GENERATOR PAD. FBC AMENDMENTS
 107.2.1 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED
 TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE
 ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED
 AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE
 ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
  
 2) THE GENERATOR PLATFORM DRAWING SPECIFIES A 144 MPH
 WIND SPEED. THIS PROJECT IS LOCATED IN A 150 MPH WIND
 SPEED AND EXPOSURE D. FBC-R 301.2.1
  
 3) SUBMIT A SIGNED AND SEALED ENGINEER'S EVALUATION
 WITH CALCULATIONS FOR THE GENERATOR STAND AND SLAB
 ASSEMBLY TO SHOW THAT IT WILL MEET THE WINDLOADS. FBC
 AMENDMENTS 107.2.1.2
  
 4) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-08-31 Cont ID  
Sent By fgiaquin Date 2022-08-31 Time 23:03 Rev Time 0.00
Received By fgiaquin Date 2022-08-31 Time 23:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By mpeterso Date 2022-07-26 Time 20:06 Rev Time 0.00
Received By fgiaquin Date 2022-07-26 Time 20:03 Sent To  
Notes
2022-04-22 15:21:22 
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-31 Cont ID  
Sent By fgiaquin Date 2022-08-31 Time 23:04 Rev Time 0.00
Received By fgiaquin Date   Time 19:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-08-29 Cont ID  
Sent By ccole Date 2022-08-29 Time 16:18 Rev Time 0.00
Received By ccole Date 2022-08-29 Time 15:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-08-04 Cont ID  
Sent By ccole Date 2022-08-04 Time 15:02 Rev Time 0.00
Received By ccole Date 2022-08-04 Time 10:46 Sent To  
Notes
2022-08-04 15:02:412ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22020197
 8/4/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED
 ON RESUBMITTED GAS PLANS
  
 1) GAS RISER: BASED ON TABLE 402.4(5) FBC FG FOR A
 2-PSI SYSTEM WITH 103 FT. TDL, A MINIMUM 1-1/4-INCH
 DIAMETER STEEL PIPE IS REQUIRED FROM THE METER TO THE
 TEE FOR THE TOTAL 2,022,000 BTU GAS LOAD. PLEASE SHOW
 THE PIPE DIAMETER ON THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By ccole Date 2022-07-28 Time 10:30 Rev Time 0.00
Received By ccole Date 2022-07-28 Time 10:29 Sent To  
Notes
2022-07-28 10:31:14REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22020197
 7/28/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED
 ON RESUBMITTED GAS PLANS
  
 1) A PREVIOUSLY APPROVED GAS PIPING LAYOUT PLAN HAS
 BEEN SUBMITTED FOR REFERENCE WHICH APPEARS TO SHOW THE
 GENERATOR LOCATED BETWEEN THE GARAGE AND THE POOL
 CABANA. THIS LOCATION DOES NOT MATCH THE NEW SURVEY
 SUBMITTED WHICH SHOWS THE GENERATOR AT THE REAR OF THE
 PROPERTY. PLEASE CLARIFY IF THE CURRENT RISER DRAWING
 IS CONSISTENT WITH THE SURVEY OR THE REFERENCE PLAN-
 SEC. 107.2.1 WPB.
  
 2) THE RISER DRAWING SHOWING A 3/4-INCH PE MAIN SUPPLY
 PIPE WITH NO BRANCH TEES DOES NOT APPEAR TO BE
 CONSISTENT WITH THE REFERENCE PLAN WHICH SHOWS A MAIN
 SUPPLY (TYPE AND SIZE NOT SHOWN) WITH 3 BRANCH TEES.
 PLEASE MATCH THE RISER WITH THE REFERENCE PLAN AND SHOW
 THE TYPE AND SIZE OF THE MAIN SUPPLY PIPE FROM THE
 METER AND THE TOTAL DEVELOPED LENGTH OF THE 2-PSI
 SYSTEM- SECS. G2413.3, G2413.4, & G2413.4.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2022-04-12 15:12:23 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-09-07 Cont ID  
Sent By rmcdouga Date 2022-09-07 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2022-08-25 Time 06:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-23 Cont ID  
Sent By rmcdouga Date 2022-08-23 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2022-08-03 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-01 Cont ID  
Sent By aoliver Date 2022-08-02 Time 06:47 Rev Time 0.00
Received By rmcdouga Date 2022-07-06 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-06 Cont ID  
Sent By shill Date 2022-07-06 Time 09:53 Rev Time 0.00
Received By shill Date 2022-06-09 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By shill Date 2022-05-18 Time 19:07 Rev Time 0.00
Received By shill Date 2022-04-08 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 15:21 Rev Time 0.00
Received By rmcdouga Date 2022-02-04 Time 06:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-08-29 Cont ID  
Sent By ccole Date 2022-08-29 Time 15:54 Rev Time 0.00
Received By ccole Date 2022-08-29 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By ccole Date 2022-08-04 Time 10:47 Rev Time 0.00
Received By ccole Date 2022-08-04 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-04-13 Cont ID  
Sent By ccole Date 2022-04-13 Time 07:18 Rev Time 0.00
Received By ccole Date 2022-04-12 Time 14:39 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status N Date 2022-08-02 Cont ID  
Sent By rgathrig Date 2022-08-02 Time 15:24 Rev Time 0.00
Received By rgathrig Date 2022-08-02 Time 15:24 Sent To  
Notes
2022-08-02 15:25:58RECEIVED LETTER FROM OWNER REMOVING PRIVATE PROVIDER
 FROM THE JOB.
 THEY WANT THE CITY TO DO THE INSPECTIONS
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2022-07-12 Cont ID  
Sent By rgathrig Date 2022-07-12 Time 17:42 Rev Time 0.00
Received By rgathrig Date 2022-07-12 Time 17:42 Sent To  
Notes
2022-07-12 17:54:13PRIVATE PROVIDER REVIEW OF DOCUMENTS FAILED
  
 THE NEW NOTICE TO BUILDING OFFICIAL STATES INSPECTIONS
 ONLY
  
 THERE ARE TWO CERTIFICATES OF INSURANCE SUBMITTED WITH
 THIS PRIVATE PROVIDER DOCUMENTS. ONE CERTIFICATE
 EXPIRED 4/12/2022. THE OTHER CERTIFICATE HAS AN
 EXPIRATION DATE OF 4/12/2023 BUT IT DOES NOT CONTAIN
 THE LANGUAGE REQUIRED BY FLORIDA STATUTE 553.791 (4)(B)
 THAT THERE IS PROFESSIONAL LIABILITY INSURANCE FOR THE
 PRIVATE PROVIDER FIRM, THE PRIVATE PROVIDER, AND ANY
 DULY AUTHORIZED REPRESENTATIVE. THERE ARE INDIVIDUALS
 LISTED ON THE FORM IN THE DESCRIPTION OF OPERATIONS
 THAT DOES NOT SATISFY THE STATUTORY LANGUAGE.
  
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561-805-6679
 [email protected]

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-07-06 Cont ID  
Sent By shill Date 2022-07-06 Time 09:51 Rev Time 0.00
Received By shill Date 2022-07-06 Time 09:51 Sent To  
Notes
2022-07-06 09:53:01FS553.791
  
 FS553.791, THE NOTICE TO BUILDING OFFICIAL IS FOR PLAN
 REVIEW AND INSPECTIONS, THE PERMIT APPLICATION HAS
 INSPECTIONS ONLY SELECTED. SINCE THE OWNER HAS ELECTED
 TO USE A PRIVATE PROVIDER FOR PLAN REVIEW, THIS IS NOT
 A LEGAL APPLICATION UNTIL AN ACCURATE PLAN REVIEW
 AFFIDAVIT IS SUBMITTED. PLEASE SUBMIT. THE OTHER
 PRIVATE PROVIDER DOCUMENTS WILL BE REVIEWED AFTER THE
 AFFIDAVIT IS RECEIVED.
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-05-18 Cont ID  
Sent By shill Date 2022-05-18 Time 18:52 Rev Time 0.00
Received By shill Date 2022-05-18 Time 18:52 Sent To  
Notes
2022-05-18 18:59:41FBC 107, SEE PROJECTDOX NAMING CONVENTION. ALL FILES
 ARE TO BE NAMED IN A MANNER THAT DESCRIBES THE
 DOCUMENT. "KUNKEL - N2BO" IS NOT DESCRIPTIVE ENOUGH FOR
 CLERICAL AND PLAN REVIEW STAFF TO KNOW THAT YOU HAVE
 FILED A NOTICE TO BUILDING OFFICIAL OF USE OF PRIVATE
 PROVIDER FOR PLAN REVIEW AND INSPECTIONS.
  
 GOING FORWARD, PLEASE SUBMIT THE NOTICE TO BUILDING
 OFFICIAL WITH YOUR PERMIT APPLICATION SO WE CAN PROCESS
 IN ACCORDANCE WITH FS553.791.
  
 FS553.791, THE NOTICE TO BUILDING OFFICIAL IS FOR PLAN
 REVIEW AND INSPECTIONS, THE PERMIT APPLICATION HAS
 INSPECTIONS ONLY SELECTED. SINCE THE OWNER HAS ELECTED
 TO USE A PRIVATE PROVIDER FOR PLAN REVIEW, THIS IS NOT
 A LEGAL APPLICATION UNTIL AN ACCURATE PLAN REVIEW
 AFFIDAVIT IS SUBMITTED. PLEASE SUBMIT. THE OTHER
 PRIVATE PROVIDER DOCUMENTS WILL BE REVIEWED AFTER THE
 AFFIDAVIT IS RECEIVED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-07 Cont ID  
Sent By rmcdouga Date 2022-09-07 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2022-09-07 Time 10:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-23 Cont ID  
Sent By rmcdouga Date 2022-08-23 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2022-08-23 Time 09:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By rmcdouga Date 2022-05-12 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2022-05-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2022-03-23 Time 14:48 Sent To  
Notes
2022-03-23 14:51:15THE DIGITAL SIGNATURE ON THE GENERATOR STAND DRAWING IS
 OKAY.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By vbroglia Date 2022-04-15 Time 09:31 Rev Time 0.00
Received By vbroglia Date 2022-04-15 Time 09:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By vbroglia Date 2022-02-14 Time 14:16 Rev Time 0.00
Received By vbroglia Date 2022-02-14 Time 14:16 Sent To  
Notes
***NONE***