| Plan Review Stops For Permit 22020197 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-09-07 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-07 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2022-09-07 10:28:23 | PLAN | | | REVIEW COMMENTS | | | 4TH REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) I DID NOT SEE THE ENGINEERING FOR THE PRECAST | | | GENERATOR PAD. UNLESS YOU ARE DOING A CAST IN PLACE | | | GENERATOR SLAB, YOU WILL NEED TO SUBMIT THE ENGINEERING | | | FOR THE PREFABRICATED GENERATOR PAD THAT YOU WILL BE | | | USING. FBC-R301 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-23 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-23 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2022-08-23 09:15:32 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NEW ENGINEERING DOES NOT INCLUDE THE DESIGN FOR | | | THE STAND THAT WILL BE USED TO ELEVATE THE GENERATOR | | | FOR FLOOD DESIGN. THE GENERATOR IS LOCATED IN A SPECIAL | | | FLOOD HAZARD AREA (AE). THE GENERATOR WILL NEED TO BE | | | RAISED TO OR ABOVE THE ELEVATION OF THE FINISHED FLOOR | | | OF THE DWELLING. SHOW HOW COMPLIANCE WITH THIS WILL BE | | | MET. FBC-R322.1.6 | | | | | | 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-02 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-26 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2022-05-12 11:31:10 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. [ THE ENGINEERING THAT WAS SUBMITTED | | | FOR THE PREFABRICATED GENERATOR PAD AND THE STAND ARE | | | NOT ACCEPTABLE. THE PROJECT IS LOCATED IN EXPOSURE | | | CATEGORY D AND A 170 MPH VULT WIND SPEED. THE DRAWING | | | NEEDS TO SPECIFY THE MAXIMUM DIMENSIONS AND THE MINIMUM | | | WEIGHT REQUIREMENTS FOR THE GENERATOR. | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS. | | | | | | 3) FBC AMENDMENTS 107.2.1 ELECTRONICALLY SUBMITTED | | | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR | | | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE | | | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF | | | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN | | | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-06 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2022-03-23 15:09:13 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING | | | FOR THE PREFABRICATED GENERATOR PAD. FBC AMENDMENTS | | | 107.2.1 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED | | | TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE | | | ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED | | | AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE | | | ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & | | | FAC 61G15 | | | | | | 2) THE GENERATOR PLATFORM DRAWING SPECIFIES A 144 MPH | | | WIND SPEED. THIS PROJECT IS LOCATED IN A 150 MPH WIND | | | SPEED AND EXPOSURE D. FBC-R 301.2.1 | | | | | | 3) SUBMIT A SIGNED AND SEALED ENGINEER'S EVALUATION | | | WITH CALCULATIONS FOR THE GENERATOR STAND AND SLAB | | | ASSEMBLY TO SHOW THAT IT WILL MEET THE WINDLOADS. FBC | | | AMENDMENTS 107.2.1.2 | | | | | | 4) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-31 |
Time |
23:03 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-31 |
Time |
23:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-07-26 |
Time |
20:06 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-26 |
Time |
20:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-31 |
Time |
23:04 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
|
Time |
19:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-29 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-29 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-04 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-04 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2022-08-04 15:02:41 | 2ND REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 22020197 | | | 8/4/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED | | | ON RESUBMITTED GAS PLANS | | | | | | 1) GAS RISER: BASED ON TABLE 402.4(5) FBC FG FOR A | | | 2-PSI SYSTEM WITH 103 FT. TDL, A MINIMUM 1-1/4-INCH | | | DIAMETER STEEL PIPE IS REQUIRED FROM THE METER TO THE | | | TEE FOR THE TOTAL 2,022,000 BTU GAS LOAD. PLEASE SHOW | | | THE PIPE DIAMETER ON THE DRAWING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-28 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-28 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2022-07-28 10:31:14 | REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 22020197 | | | 7/28/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED | | | ON RESUBMITTED GAS PLANS | | | | | | 1) A PREVIOUSLY APPROVED GAS PIPING LAYOUT PLAN HAS | | | BEEN SUBMITTED FOR REFERENCE WHICH APPEARS TO SHOW THE | | | GENERATOR LOCATED BETWEEN THE GARAGE AND THE POOL | | | CABANA. THIS LOCATION DOES NOT MATCH THE NEW SURVEY | | | SUBMITTED WHICH SHOWS THE GENERATOR AT THE REAR OF THE | | | PROPERTY. PLEASE CLARIFY IF THE CURRENT RISER DRAWING | | | IS CONSISTENT WITH THE SURVEY OR THE REFERENCE PLAN- | | | SEC. 107.2.1 WPB. | | | | | | 2) THE RISER DRAWING SHOWING A 3/4-INCH PE MAIN SUPPLY | | | PIPE WITH NO BRANCH TEES DOES NOT APPEAR TO BE | | | CONSISTENT WITH THE REFERENCE PLAN WHICH SHOWS A MAIN | | | SUPPLY (TYPE AND SIZE NOT SHOWN) WITH 3 BRANCH TEES. | | | PLEASE MATCH THE RISER WITH THE REFERENCE PLAN AND SHOW | | | THE TYPE AND SIZE OF THE MAIN SUPPLY PIPE FROM THE | | | METER AND THE TOTAL DEVELOPED LENGTH OF THE 2-PSI | | | SYSTEM- SECS. G2413.3, G2413.4, & G2413.4.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | 2022-04-12 15:12:23 | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-09-07 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-25 |
Time |
06:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-23 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-03 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-08-02 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-06 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-06 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-09 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-18 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-04-08 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-23 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-04 |
Time |
06:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-29 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-29 |
Time |
15:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-04 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-04 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-13 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-12 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
4 |
Status |
N |
Date |
2022-08-02 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2022-08-02 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2022-08-02 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2022-08-02 15:25:58 | RECEIVED LETTER FROM OWNER REMOVING PRIVATE PROVIDER | | | FROM THE JOB. | | | THEY WANT THE CITY TO DO THE INSPECTIONS | | | | | | RICHARD GATHRIGHT | | | ASSISTANT BUILDING OFFICIAL | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2022-07-12 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2022-07-12 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2022-07-12 17:54:13 | PRIVATE PROVIDER REVIEW OF DOCUMENTS FAILED | | | | | | THE NEW NOTICE TO BUILDING OFFICIAL STATES INSPECTIONS | | | ONLY | | | | | | THERE ARE TWO CERTIFICATES OF INSURANCE SUBMITTED WITH | | | THIS PRIVATE PROVIDER DOCUMENTS. ONE CERTIFICATE | | | EXPIRED 4/12/2022. THE OTHER CERTIFICATE HAS AN | | | EXPIRATION DATE OF 4/12/2023 BUT IT DOES NOT CONTAIN | | | THE LANGUAGE REQUIRED BY FLORIDA STATUTE 553.791 (4)(B) | | | THAT THERE IS PROFESSIONAL LIABILITY INSURANCE FOR THE | | | PRIVATE PROVIDER FIRM, THE PRIVATE PROVIDER, AND ANY | | | DULY AUTHORIZED REPRESENTATIVE. THERE ARE INDIVIDUALS | | | LISTED ON THE FORM IN THE DESCRIPTION OF OPERATIONS | | | THAT DOES NOT SATISFY THE STATUTORY LANGUAGE. | | | | | | | | | RICHARD GATHRIGHT | | | ASSISTANT BUILDING OFFICIAL | | | 561-805-6679 | | | [email protected] |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-06 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-06 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2022-07-06 09:53:01 | FS553.791 | | | | | | FS553.791, THE NOTICE TO BUILDING OFFICIAL IS FOR PLAN | | | REVIEW AND INSPECTIONS, THE PERMIT APPLICATION HAS | | | INSPECTIONS ONLY SELECTED. SINCE THE OWNER HAS ELECTED | | | TO USE A PRIVATE PROVIDER FOR PLAN REVIEW, THIS IS NOT | | | A LEGAL APPLICATION UNTIL AN ACCURATE PLAN REVIEW | | | AFFIDAVIT IS SUBMITTED. PLEASE SUBMIT. THE OTHER | | | PRIVATE PROVIDER DOCUMENTS WILL BE REVIEWED AFTER THE | | | AFFIDAVIT IS RECEIVED. | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-18 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-18 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2022-05-18 18:59:41 | FBC 107, SEE PROJECTDOX NAMING CONVENTION. ALL FILES | | | ARE TO BE NAMED IN A MANNER THAT DESCRIBES THE | | | DOCUMENT. "KUNKEL - N2BO" IS NOT DESCRIPTIVE ENOUGH FOR | | | CLERICAL AND PLAN REVIEW STAFF TO KNOW THAT YOU HAVE | | | FILED A NOTICE TO BUILDING OFFICIAL OF USE OF PRIVATE | | | PROVIDER FOR PLAN REVIEW AND INSPECTIONS. | | | | | | GOING FORWARD, PLEASE SUBMIT THE NOTICE TO BUILDING | | | OFFICIAL WITH YOUR PERMIT APPLICATION SO WE CAN PROCESS | | | IN ACCORDANCE WITH FS553.791. | | | | | | FS553.791, THE NOTICE TO BUILDING OFFICIAL IS FOR PLAN | | | REVIEW AND INSPECTIONS, THE PERMIT APPLICATION HAS | | | INSPECTIONS ONLY SELECTED. SINCE THE OWNER HAS ELECTED | | | TO USE A PRIVATE PROVIDER FOR PLAN REVIEW, THIS IS NOT | | | A LEGAL APPLICATION UNTIL AN ACCURATE PLAN REVIEW | | | AFFIDAVIT IS SUBMITTED. PLEASE SUBMIT. THE OTHER | | | PRIVATE PROVIDER DOCUMENTS WILL BE REVIEWED AFTER THE | | | AFFIDAVIT IS RECEIVED. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-09-07 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-07 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-23 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-23 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-05-12 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-05-12 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-23 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-23 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2022-03-23 14:51:15 | THE DIGITAL SIGNATURE ON THE GENERATOR STAND DRAWING IS | | | OKAY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-04-15 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-04-15 |
Time |
09:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-14 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-14 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|