| 2022-02-28 09:56:10 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL5680-R29 HAS BEEN |
| | REVISED TO FL5680-R33. PROVIDE THE FOLLOWING: COVER |
| | PAGE, EVALUATION REPORTS PAGES 1-6 TO INCLUDE |
| | LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. SELECTED SYSTEM NO. W-56 DO NOT MEET |
| | EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE |
| | REQUIREMENTS. PROVIDE SIGNED AND SEALED ENGINEERED |
| | NAILING CALCULATIONS FOR ZONE 3 AS PER LIMITATIONS: |
| | 5.7.2./SELECT SYSTEM THAT MEETS OR EXCEEDS EXPOSURE |
| | CATEGORY C MINIMUM DESIGN PRESSURE ZONE 3 REQUIREMENTS |
| | OF -108.17. |
| | 2. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| | HEIGHT(S). |
| | 3. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF |
| | DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE |
| | 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020 |
| | FBC-PLUMBING |
| | 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| | POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |