| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL25621-R1 HAS BEEN REVISED TO FL25621-R2. |
| | PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| | INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL25621.01-R1 IS NOT RATED FOR USE IN ZONE 2 & |
| | 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D WITH |
| | FLAT ROOF LESS THAN 7 DEGREES, HIP ROOF WITH MAX SLOPE |
| | OF 12:12 OR GABLE ROOF WITH SLOPE BETWEEN 4.4:12 & |
| | 12:12 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS |
| | WIND SPEED 170 MPH. PROVIDE SIGNED AND SEALED |
| | ENGINEERING FOR USE OR SELECT A SYSTEM THAT MEETS THE |
| | ABOVE CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY |
| | AREA. |
| | 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 4. SUBMITTED MIAMI-DADE COUNTY NOA 21-0602.14 COVERS |
| | MULTIPLE PRODUCTS & INSTALLATION PROCEDURES: SYSTEMS |
| | TYPE E(1) THROUGH E(3). SELECT PRODUCT & SYSTEM TYPE TO |
| | BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW |
| | ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF |
| | SLOPE(S), MEAN ROOF HEIGHT(S). LOW SLOPE ROOFS MUST |
| | SHOW POSITIVE DRAINAGE. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |