Plan Review Details - Permit 22020120
Plan Review Stops For Permit 22020120
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By cpuell Date 2022-04-25 Time 15:57 Rev Time 0.00
Received By cpuell Date 2022-04-25 Time 15:57 Sent To  
Notes
2022-04-25 15:57:48HALF ADDRESS READDRESSED TO 231 29TH ST.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 12:13 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 12:13 Sent To  
Notes
2022-03-31 12:13:54PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By cpuell Date 2022-02-04 Time 14:14 Rev Time 0.00
Received By cpuell Date 2022-02-04 Time 14:14 Sent To  
Notes
2022-02-04 14:15:01THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-25 Cont ID  
Sent By rmcdouga Date 2022-04-25 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2022-04-25 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-25 Cont ID  
Sent By rmcdouga Date 2022-03-25 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2022-03-25 Time 08:35 Sent To  
Notes
2022-03-25 08:38:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS POOL IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 THE POOL EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE
 ELEVATION OF THE FINSIH FLOOR OF THE HABITAL AREA OF
 THE DWELLING. FBC-R 322.1.6
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE POOL GUARD SURFACE
 MOTION POOL ALARM AND SHOW THAT SHOW IT IS CERTIFIED TO
 ASTM STANDARD F2208. FBC-R 4501.17.1.9

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By fgiaquin Date 2022-04-18 Time 20:53 Rev Time 0.00
Received By fgiaquin Date 2022-04-18 Time 19:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-23 Cont ID  
Sent By fgiaquin Date 2022-02-23 Time 22:22 Rev Time 0.00
Received By fgiaquin Date 2022-02-23 Time 20:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-25 Cont ID  
Sent By rmcdouga Date 2022-04-25 Time 08:40 Rev Time 0.00
Received By rmcdouga Date 2022-03-31 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-25 Cont ID  
Sent By rmcdouga Date 2022-03-25 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2022-02-04 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By lcrespo Date 2022-04-04 Time 14:44 Rev Time 0.00
Received By lcrespo Date 2022-04-04 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By lcrespo Date 2022-02-14 Time 07:29 Rev Time 0.00
Received By lcrespo Date 2022-02-14 Time 07:29 Sent To  
Notes
2022-02-14 09:04:2402/14/22 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW
 RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF
 THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, FILTER, HEAT PUMP, AND CHLORINATOR.
 ALL SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HEAT
 PUMP, AND CHLORINATOR, PER THE WPB AMENDMENTS TO FBC
 SEC. 107.2.1.
  
 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE RPZ BACKFLOW
 DEVICE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By rmcdouga Date 2022-04-25 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2022-04-25 Time 09:05 Sent To  
Notes
2022-04-25 09:06:39I UPLOADED THE UN-CORRUPTED DIGITALLY SIGNED PLANS THAT
 WERE EMAILED TO ME.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-04-25 Cont ID  
Sent By rmcdouga Date 2022-04-25 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2022-04-25 Time 08:37 Sent To  
Notes
2022-04-25 08:38:39THE DIGITAL SIGNATURES ON THE PLANS COULD NOT BE
 VERIFIED. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS
 471 & FAC 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-07 Cont ID  
Sent By lcrespo Date 2022-02-07 Time 12:53 Rev Time 0.00
Received By lcrespo Date 2022-02-07 Time 12:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-08 Cont ID  
Sent By vbroglia Date 2022-04-08 Time 10:52 Rev Time 0.00
Received By vbroglia Date 2022-04-08 Time 10:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By vbroglia Date 2022-02-14 Time 14:40 Rev Time 0.00
Received By vbroglia Date 2022-02-14 Time 14:40 Sent To  
Notes
***NONE***