Plan Review Details - Permit 22020062
Plan Review Stops For Permit 22020062
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-17 Cont ID  
Sent By pleduc Date 2022-05-17 Time   Rev Time 0.00
Received By pleduc Date 2022-05-17 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-17 Cont ID  
Sent By pleduc Date 2022-02-17 Time   Rev Time 0.00
Received By pleduc Date 2022-02-17 Time 12:47 Sent To  
Notes
2022-02-17 13:07:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FOR VERIFICATION PURPOSES PLEASE PROVIDE A
 FLOOR/SITE PLAN CLEARLY INDICATING THE PROPOSED
 LOCATION.
  
  
 2) SHOULD THE LOCATION BE INSTALLED WITHIN THE EXISTING
 BUILDING, THE FIRE SPRINKLER PROTECTION SHALL BE
 EXTENDED INTO THE COOLER.
  
 PER NFPA 101, CH 12
  
 12.3.5.4 WHERE ANOTHER PROVISION OF THIS CHAPTER
 REQUIRES AN AUTOMATIC
 SPRINKLER SYSTEM, THE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE
 WITH 9.7.1.1(1).
  
 9.7 AUTOMATIC SPRINKLERS
 9.7.1 GENERAL.
 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY
 ANOTHER SECTION
 OF THIS CODE SHALL BE IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
  
 (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS
 (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN
 ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES
 (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN
 LOW-RISE RESIDENTIAL OCCUPANCIES
  
 PER NFPA 13
  
 8.1.1* THE REQUIREMENTS FOR SPACING, LOCATION, AND
 POSITION OF SPRINKLERS SHALL BE BASED ON
 THE FOLLOWING PRINCIPLES:
 (1) SPRINKLERS SHALL BE INSTALLED THROUGHOUT THE
 PREMISES.
  
 A.8.1.1 THIS STANDARD CONTEMPLATES FULL SPRINKLER
 PROTECTION FOR ALL AREAS INCLUDING WALK-IN
 COOLERS, FREEZERS, BANK VAULTS, AND SIMILAR AREAS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT FOR
 FIRE SPRINKLER WORK TO BE SUBMITTED UNDER SEPARATE
 PERMIT & SHOP DRAWINGS.
  
  
 3) AS THIS IS A DOUBLE COMPARTMENT COOLER, IS THE PATH
 OF EGRESS LIGHTING PROVIDED WITH BACK UP POWER IN CASE
 OF LOSS OF POWER?
  
 PER NFPA 101 CH 12
  
 12.2.9 EMERGENCY LIGHTING.
 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 7.9.
  
 PLEASE PROVIDE FOR PATH OF EGRESS EMERGENCY LIGHTING
 WITHIN THE EACH COMPARTMENT OF THE COOLER.
  
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 13:03 Rev Time 0.00
Received By medwards Date 2022-05-16 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-17 Cont ID  
Sent By medwards Date 2022-02-17 Time 14:41 Rev Time 0.00
Received By cpuell Date 2022-02-04 Time 07:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 13:02 Rev Time 0.00
Received By medwards Date 2022-05-23 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 12:37 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 12:37 Sent To  
Notes
2022-02-14 12:38:011ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22020062
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE DRAWINGS SHOWING THE WAKIN COOLER AND
 FREEZER IN THE TENANT SPACE INCLUDING THE LOCATION OF
 THE CONDENSING UNITS. IS THIS PROJECT TIED TO A
 CONSTRUCTION PROJECT? IF SO PLEASE PROVIDE THE MASTER
 PERMIT NUMBER. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 13:03 Rev Time 0.00
Received By medwards Date 2022-05-23 Time 13:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 12:38 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 12:38 Sent To  
Notes
2022-02-14 12:40:25THE ENGINEER ON THE DRAWINGS WILL NEED TO PROVIDE THE
 3RD PARTY VERIFIED DIGITAL SIGNATURE OR THEY CAN
 PROVIDE AN ORIGINAL SIGNED AND SEALED DRAWING TO OUR
 OFFICE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  