| 2022-06-15 10:36:05 | ROOFING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: FLAT ROOF SHALL BE INSULATED PER NOTE ON ROOF |
| | FRAMING PLAN PAGE 8/12 IN MASTER PERMIT 21091179. PLAN |
| | PAGE UPLOADED TO THIS SUBMITTAL FOR YOUR REFERENCE. |
| | |
| | PLEASE REFERENCE NOA 20-0723.29 (MODIFIED BITUMEN) FOR |
| | THE FOLLOWING COMMENTS: |
| | |
| | 1. STARTING ON PG. 10 OF THE NOA, THERE ARE ELEVEN |
| | SYSTEMS FOR INSTALLATION OVER WOOD DECKS WITH |
| | INSULATION TO CHOOSE FROM. DESIGNER SHALL SELECT SYSTEM |
| | TO BE INSTALLED. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. LIMITATION #7, PAGE 48/48 OF NOA APPLIES TO ALL |
| | ELEVEN INSULATED SYSTEMS. |
| | PROVIDE INCREASED FASTENER DENSITIES FOR PERIMETER AND |
| | CORNER AREAS DUE TO THE ENHANCED UPLIFT PRESSURES OF |
| | THESE AREAS. |
| | CALCULATIONS SHALL BE PREPARED, SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED DESIGN PROFESSIONAL. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |