Plan Review Details - Permit 22011136
Plan Review Stops For Permit 22011136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 15:33 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 15:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By rmcphers Date 2022-05-25 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2022-05-25 Time 13:48 Sent To  
Notes
2022-05-25 13:54:23GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GENERATOR DISTANCE FROM HOUSE
 OPENINGS - FBC R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) PLEASE PROVIDE FOUNDATION DETAILS.
  
 3) GENERATOR IS SUBJECT TO WIND LOADS - PLEASE PROVIDE
 GENERATOR ATTACHMENT DETAILS TO THE FOUNDATION FROM A
 DESIGN PROFESSIONAL FBC 1609
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By mpeterso Date 2022-06-03 Time 11:11 Rev Time 0.00
Received By mpeterso Date 2022-06-03 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-22 Cont ID  
Sent By mpeterso Date 2022-04-22 Time 15:58 Rev Time 0.00
Received By mpeterso Date 2022-04-22 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 15:33 Rev Time 0.00
Received By rmcphers Date 2022-05-27 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-25 Cont ID  
Sent By rmcphers Date 2022-05-25 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2022-04-05 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By mpeterso Date 2022-06-03 Time 11:13 Rev Time 0.00
Received By mpeterso Date 2022-06-03 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-25 Cont ID  
Sent By rmcphers Date 2022-05-25 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2022-05-25 Time 13:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-14 Cont ID  
Sent By asangele Date 2022-06-14 Time 16:27 Rev Time 0.00
Received By asangele Date 2022-06-14 Time 16:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-06-03 Cont ID  
Sent By asangele Date 2022-06-03 Time 09:10 Rev Time 0.00
Received By asangele Date 2022-06-03 Time 09:10 Sent To  
Notes
2022-06-03 09:11:526/3/2022
 FAIL
 PLEASE ADDRESS PREVIOUS COMMENT MADE.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-08 Cont ID  
Sent By asangele Date 2022-04-08 Time 10:12 Rev Time 0.00
Received By asangele Date 2022-04-08 Time 10:12 Sent To  
Notes
2022-04-08 10:14:334/8/2022
 FAILED
 PLEASE PROVIDE A SURVEY WITH THE SETBACKS OF THE
 GENERATOR
 * MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]