| Plan Review Stops For Permit 22011100 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
5 |
Status |
P |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-06-06 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-06-06 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2022-06-06 12:34:17 | WEST BUILDING GIVEN THE ADDRESSES OF 3416 BROADWAY | | | (DOWNSTAIRS UNIT) 596 34TH ST (UPSTAIRS UNIT) AND EAST | | | BUILDING GIVEN THE ADDRESSES OF 582 34TH ST (EAST UNIT) | | | AND 586 34TH ST (WEST UNIT) |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
F |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-18 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-18 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2022-05-18 09:48:35 | PLEASE CONTACT ONCE ZONING APPROVES THE UNITS | | | [email protected] FOR FURTHER QUESTIONS YOU CAN | | | ALSO CALL 561-805-6659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-03 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-03 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2022-05-03 10:27:47 | OWNER CONTACTED ME TO BE ISSUED ADDRESSES, HOWEVER I | | | SPOKE WITH LL AND SHE HAS STATED THAT THE PROPERTY MAY | | | NOT BE ABLE TO HAVE 4 UNITS, CONTACTED OWNER TO REACH | | | OUT TO ME ONCE ZONING APPROVES HOWEVER MANY NUMBER OF | | | UNITS. [email protected] OR 561-805-6659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-17 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-17 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2022-03-17 13:34:04 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-01-27 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-01-27 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2022-01-27 15:39:17 | PLANS INDICATE THAT 4 UNITS ARE TO BE BUILT ALL UNITS | | | NEED THEIR OWN ADDRESS, PLEASE PROVIDE A SITEPLAN | | | SHOWING THE ENTRANCES TO EACH UNIT ON THE BUILDINGS. | | | PLEASE EMAIL TO [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-03 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-03 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-03-16 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-03-16 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2022-03-16 13:42:41 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC R 302.3, PROVIDE THE FIRE RATING FOR TENENT | | | SEPARATION WALLS AND FLOORS. | | | SHEET A-4 HAS THE DETAIL FOR THE INFILLS BUT WE STILL | | | NEED THE UL LISTING INDICATING THE FIRE RESISTANT | | | RATING FOR BOTH THE WALLS AND FLOOR DETAILS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-02-08 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-02-07 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2022-02-08 08:14:49 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE INFILL DETAILS FOR | | | WINDOWS/DOORS AND FLOORS INCLUDING THE OPENING LEFT | | | FROM STAIR REMOVAL BETWEEN 1ST AND 2ND FLOOR. | | | 2.) FBC R 302.3, PROVIDE FIRE RATING DETAILS FOR TENANT | | | SEPARATION AT WALLS AND FLOORS. | | | 3.) FBC B 107.2.1, PROVIDE CORRECTION OF ELEVATION | | | VIEWS AT SHEET A-2, AS NORTH AND SOUTH ELEVATIONS | | | APPEAR TO BE REVERSED. | | | 4.) FBC B 107.2.1, PROVIDE CORRECTION TO PLAN SHEETS | | | A-1 & A-2 FOR LOCATION OF STAIRS AS PLAN SHEET A-1 | | | INDICATES AN INTERIOR STAIR AND SHEET A-2 INDICATES AN | | | EXTERIOR STAIR. | | | 5.) FBC EB 1001.2.2, ACCORDING TO CITY RECORDS AND | | | SUBMITTED PLANS, THIS APPLICATION INVOLVES A STRUCTURE | | | THAT WAS ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE. | | | IT'S PROPOSED TO BE CONVERTED TO AN APARTMENT WITH A | | | KITCHEN, BEDROOM AND BATHROOM. PLEASE INDICATE AND THAT | | | THIS APPLICATION WILL COMPLY WITH THE 2020 FBC EXISTING | | | BUILDING CODE, AS THIS IS CONSIDERED A CHANGE OF | | | OCCUPANCY. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-03-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-28 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-02-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-02 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-02 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2022-02-02 11:40:12 | ELECTRIC REVIEW FAILED | | | 1) ELECTRICAL SERVICES AS DETAILED DO NOT COMPLY WITH | | | NEC 230.2. PLEASE CORRECT TO BRING INTO COMPLIANCE. | | | 2) PROVIDE RECEPTACLES AS REQUIRED PER NEC 210.52 | | | (E)(1) & (3) | | | 3) UNITS "C&D" DO NOT DETAIL SMOKE ALARMS AS REQUIRED | | | PER FBC RE 2020, 7TH EDITION | | | 4) ELECTRICAL SUB PERMIT STATES WORK AS DEMO ONLY | | | HOWEVER MAIN PERMIT STATES INTERIOR REMODEL. PLEASE | | | CLARIFY AS PER F.BC. [A] 107.2.1 | | | 5) VALUE FOR WORK STATED ON PERMIT APPLICATION | | | ($40,000) APPEARS LOW. PROVIDE A BREAKDOWN OF ALL | | | MATERIALS AND LABOR, OR, AT YOUR DISCRETION, PROVIDE A | | | SIGNED CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB | | | F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-06-06 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-06-06 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-05-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-02 |
Time |
12:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-28 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-15 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-08 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-27 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-06-13 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-06-06 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2022-06-13 16:34:31 | RECEIPT MU-2022-026042 - $11,403.26 PAID | | 2022-06-06 09:25:52 | 6/6/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-02-07 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-02-07 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2022-02-08 07:38:39 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | IMPACT REVIEW DENIED: | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-05 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-05 |
Time |
17:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-16 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-16 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2022-03-16 07:44:40 | PLEASE ADDRESS THE ENERGY CALCULATIONS, AND MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS FOR BOTH STRUCTURES | | | MENTIONED IN 1ST CYCLE PLAN REVIEW COMMENTS BELOW. ALSO | | | SHOW HOW THE DUCT SYSTEMS WILL BE RAN OUTSIDE OF THE | | | FLOOR CEILING ASSEMBLY. THERE SHALL NOT BE A SCREEN AT | | | THE TERMINATION OF THE DRYER VENT. FBC RES M1502.3 | | | | | | | | | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22011100 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | A SEPARATE PERMIT WILL BE REQUIRED FOR THE CONVERTING | | | OF THE GARAGE INTO A DUPLEX. | | | PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH | | | BUILDINGS. FBC EC 101.5.1.1.2 | | | PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR BOTH BUILDINGS. FBC EC R403.7 | | | ARE THERE GOING TO BE HOODS ABOVE THE RANGES IN THESE | | | UNITS? IF SO ARE THEY DUCTED TO THE EXTERIOR? IF SO, | | | PLEASE SHOW THE DUCT AND THE TERMINATION LOCATION ON | | | THE DRAWINGS FOR BOTH BUILDINGS. FBC RES M1503.4 | | | PLEASE SHOW THE DRYER EXHAUST DUCTWORK AND TERMINATION | | | LOCATION FOR BOTH BUILDINGS ON THE DRAWINGS. FBC RES | | | M1502 | | | | | | MAIN HOUSE: | | | A COMPLETE REVIEW FOR THIS MAIN BUILDING CANNOT BE | | | COMPLETED AT THIS TIME. | | | | | | 1) SHEET M-1: PLEASE PROVIDE A DETAIL DRAWING OF THE | | | DUCTWORK AND THE BATH EXHAUST FANS PROTECTION WHEN | | | PENETRATING THE RATED FLOOR CEILING ASSEMBLY. FBC 607 | | | | | | CONVERTED GARAGE: | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-31 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-31 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2022-01-31 09:08:40 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22011100 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | A SEPARATE PERMIT WILL BE REQUIRED FOR THE CONVERTING | | | OF THE GARAGE INTO A DUPLEX. | | | PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH | | | BUILDINGS. FBC EC 101.5.1.1.2 | | | PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR BOTH BUILDINGS. FBC EC R403.7 | | | ARE THERE GOING TO BE HOODS ABOVE THE RANGES IN THESE | | | UNITS? IF SO ARE THEY DUCTED TO THE EXTERIOR? IF SO, | | | PLEASE SHOW THE DUCT AND THE TERMINATION LOCATION ON | | | THE DRAWINGS FOR BOTH BUILDINGS. FBC RES M1503.4 | | | PLEASE SHOW THE DRYER EXHAUST DUCTWORK AND TERMINATION | | | LOCATION FOR BOTH BUILDINGS ON THE DRAWINGS. FBC RES | | | M1502 | | | | | | MAIN HOUSE: | | | A COMPLETE REVIEW FOR THIS MAIN BUILDING CANNOT BE | | | COMPLETED AT THIS TIME. | | | | | | 1) SHEET M-1: PLEASE PROVIDE A DETAIL DRAWING OF THE | | | DUCTWORK AND THE BATH EXHAUST FANS PROTECTION WHEN | | | PENETRATING THE RATED FLOOR CEILING ASSEMBLY. FBC 607 | | | | | | CONVERTED GARAGE: | | | | | | 1) PLEASE SHOW THE LOCATION OF THE DRYER EXHAUST IN THE | | | WALL, PLEASE BE ADVISED IT CANNOT BE INSIDE THE 2 HOUR | | | RATED TENANT SEPARATION WALL UNLESS IT WOULD BE | | | PROTECTED INSIDE OF A SHAFT. FBC 604 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-03 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-03 |
Time |
06:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-16 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-16 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2022-03-16 09:00:38 | 03/16/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. DONE | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | 4. DONE | | | | | | 5. ON SHEET P-1 DETAIL #1; | | | | | | A. WOULD YOU PLEASE SHOW THE VENTING AND SUPPLY FOR THE | | | ISOMETRIC DIAGRAM PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. THE WASHING | | | MACHINE IS NOT VENTED OR SHOWS A P-TRAP IN-WALL PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | B. DONE | | | | | | 6. ON SHEET P-1.1 DETAIL #2; | | | | | | A. THE LAV IS SHOWN IN THE WRONG DIRECTION ON ISOMETRIC | | | FOR BATH #2. WOULD YOU PLEASE CORRECT PER THE WPB | | | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS? | | | | | | B. DONE WITH NEW COMMENT; WASHING MACHINE IS NOT VENTED | | | OR SHOW A P-TRAP IN-WALL PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | C. DONE | | | | | | D. NEW PAGE AND COMMENTS | | | | | | E. DONE | | | | | | | | | ON SHEET P-1.2; | | | | | | A. IN-UNIT C AND D ISOMETRIC DIAGRAM, WASHING MACHINE | | | IS NOT VENTED OR SHOW A P-TRAP IN THE WALL WOULD YOU | | | PLEASE SHOW THE VENTING AND SUPPLY PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL | | | PLUMBING. | | | | | | B. WOULD YOU PLEASE SHOW THE CLEANOUT ON THE ISOMETRIC | | | FOR UNITS A AND B PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | C. ON THE FLAT DRAWING FOR UNITS A AND B, THE LAV, | | | WASHING MACHINE, AND KITCHEN SINKS ARE NOT SHOWN ON THE | | | WALL. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS | | | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS? | | | | | | D. IN-UNIT C, THE BATHROOM WITH TUB, THERE IS A WATER | | | CLOSET AND TUB THAT ARE NOT VENTED CORRECTLY. A DOUBLE | | | WYE IS A FITTING THAT WILL VENT BOTH FIXTURES WITHIN | | | THE BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT PER THE | | | 2020 FBC R3108.1 HORIZONTAL WET VENT PERMITTED. | | | | | | 7. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS | | | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION | | | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW | | | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF | | | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE | | | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER | | | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND | | | THEIR CONNECTION CONTROL PROGRAM. WOULD YOU PLEASE | | | PROVIDE A NOTE ON PAGE A-1 THAT A BACKFLOW DEVICE IN | | | THE FORM OF AN RPZ IS REQUIRED WITH A PERMIT BY A | | | LICENSED CONTRACTOR PER THE WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? | | | | | | 8. ON SHEET LS-2, THE PROPOSED VACUUM BREAKER IS A PVB, | | | AND THE CITY OF WEST PALM BEACH CONSIDERS THIS A | | | COMMERCIAL PROPERTY THAT WILL REQUIRE AN RPZ PER THE | | | CROSS-CONNECTION PROGRAM OF THE CITY OF WPB CROSS | | | CONNECTION PROGRAM. THE IRRIGATION SYSTEM WILL REQUIRE | | | A REDUCED PRESSURE ZONE VALVE PER THE DEGREE OF HAZARD | | | DUE TO HIS BEING A COMMERCIAL PROPERTY PER THE 2020 FBC | | | TABLE R 2902.3 APPLICATION FOR BACKFLOW PREVENTERS. | | | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE | | | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? | | | | | | 9. DONE. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-01-28 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-01-28 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2022-01-28 09:46:10 | 01/28/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER | | | DIAGRAM FOR WATER PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | | | 2. WOULD YOU PLEASE SHOW THE SHUT-OFF VALVE FOR EACH | | | DWELLING ON THE ISOMETRIC PER THE 2020 FBC SEC. R | | | 2903.9.1 SERVICE VALVE. | | | | | | 3. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR | | | SHUTTING OFF WITHOUT MOVING UNITS, 2020 FBC SEC. R | | | 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE | | | SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS | | | PANEL OR SIMILAR REMOVABLE OBSTRUCTION, AND PLEASE SHOW | | | ON THE SIDE. | | | | | | 4. WOULD YOU PLEASE PROVIDE CLEANOUT OUTSIDE OF EACH | | | DWELLING 2020 FBC R 3005.2.1HORIZONTAL DRAINS AND | | | BUILDING DRAINS? | | | | | | 5. ON SHEET P-1 DETAIL #1; | | | | | | A. WOULD YOU PLEASE SHOW THE VENTING AND SUPPLY FOR THE | | | ISOMETRIC DIAGRAM PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | | | B. WOULD YOU PLEASE LABEL ROOMS, W/M, KITCHEN, AND | | | BATHROOMS PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 6. ON SHEET P-1.1 DETAIL #2; | | | | | | A. THE LAV IS SHOWN IN THE WRONG DIRECTION. WOULD YOU | | | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | B. THE LAUNDRY ROOM IS CONNECTED TO THE WATER CLOSET, | | | AND IT SHALL BE DOWNSTREAM OF A BATHROOM GROUP PER THE | | | 2020 FBC SECTION R 3108.1 HORIZONTAL WET VENT | | | PERMITTED. | | | | | | C. THERE ARE TWO SANITARY RISER DIAGRAM DETAIL 1. WOULD | | | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | D. IN-UNIT D ISOMETRIC DIAGRAM, WOULD YOU PLEASE SHOW | | | THE VENTING AND SUPPLY PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | | | E. IN UNIT C, THE ISOMETRIC DIAGRAM SHOWS THE LAUNDRY | | | ROOM IS LABELED AS A WATER CLOSET, AND WOULD YOU PLEASE | | | SHOW THE VENTING AND SUPPLY PER THE WPB AMENDMENTS TO | | | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | | | F. IN THE BATHROOM ON THE SECOND FLOOR NEXT TO THE AC | | | UNIT AND IN-UNIT C BATHROOM WITH TUB, THERE IS A WATER | | | CLOSET AND TUB THAT ARE NOT VENTED CORRECTLY. A DOUBLE | | | WYE IS A FITTING THAT WILL VENT BOTH. WOULD YOU PLEASE | | | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | G. WOULD YOU PLEASE LABEL ROOMS, W/M, KITCHEN, AND | | | BATHROOMS PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 7. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS | | | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION | | | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW | | | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF | | | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE | | | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER | | | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND | | | THEIR CONNECTION CONTROL PROGRAM. | | | | | | 8. THE IRRIGATION SYSTEM WILL REQUIRE A REDUCED | | | PRESSURE ZONE VALVE PER THE DEGREE OF HAZARD DUE TO HIS | | | BEING A COMMERCIAL PROPERTY PER THE 202 FBC TABLE R | | | 2902.3 APPLICATION FOR BACKFLOW PREVENTERS. | | | | | | 9. THE COVER SHEET UNDER-OCCUPANCY CLASSIFICATION SAYS | | | RM, AND THAT CALCIFICATION DOES NOT EXIST IN THE FBC. | | | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE | | | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-05-13 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-05-13 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2022-05-13 07:59:44 | SITE PLAN AND SURVEY DRAWING IN SIGNATURE FOLDER WITH | | | DIGITAL SIGNATURE. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-05-09 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-05-09 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-05-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-02 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-02 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2022-05-02 16:28:02 | 5/2/22 SIGNATURE REVIEW OF PAPER PLANS AND DOCUMENTS | | | PASSED AND ROUTED TO STORAGE.M.P. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-15 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-15 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2022-03-15 13:18:39 | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED. | | | ROUTED TO STORAGE. M.P. 3/15/22 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-27 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-27 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2022-01-27 10:20:49 | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED | | | AND PLANS ROUTED TO STORAGE- CLC. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-06-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-06-03 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-03 12:24:28 | ZONING APPROVED WITH THE FOLLOWING PROVISO(S): | | | | | | 1.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING AND | | | DRIVEWAY/PARKING AREA. | | | | | | 2.) SEE ATTACHED STAMPED SHEETS FOR ZONING APPROVAL. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-05-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-05-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-05-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-10 14:11:35 | PER PHONE CONVERSATION WITH PROPERTY OWNER (JONATHAN), | | | PLANS HAVE BEEN CORRECTED AND REVISED AFTER THIS REVIEW | | | CYCLE WAS OPENED. PER DISCUSSION WITH PROPERTY OWNER, | | | ZONING WILL FAIL REVIEW SO THAT THE REVISED PLANS CAN | | | BE UPLOADED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-03-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-03-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-22 13:19:07 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED. | | | | | | [2/8/2022 REPEAT COMMENT: NOT ADDRESSED. NO UPDATED | | | SIGNED AND SEALED SURVEY PROVIDED IN THE PERMIT | | | RESUBMITTAL.] | | | | | | | | | 2.) CLEARLY SHOW THE SETBACK FROM ALL PROPOSED HARD | | | SURFACES (I.E. STEPS, DRIVEWAY, ETC.) TO THE PROPERTY | | | LINE(S). SETBACK DISTANCES MUST CONFORM TO THE MINIMUM | | | SETBACK REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDRS). | | | | | | [2/8/2022 REPEAT COMMENT: NOT ALL DIMENSIONS HAVE BEEN | | | PROVIDED IN THE PROPOSED SITE PLAN.] | | | | | | | | | 3.) ONLY ONE (1) ACCESS POINT ON 34TH STREET IS | | | PERMITTED. PROPOSED SITE PLAN SHOWS TWO (2) ACCESS | | | POINTS WHICH IS NOT PERMITTED. [ZLDR S.94-312(1)] | | | | | | [2/8/2022 MODIFIED COMMENT: A DRIVEWAY CANNOT EXCEED 20 | | | FT. IN WIDTH. THE PROPOSED SITE PLAN SHOWS THAT THE | | | MAXIMUM ALLOWABLE DRIVEWAY WIDTH HAS BEEN EXCEEDED. | | | | | | | | | 4.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE?S | | | VALUE ($39,177.00) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | [2/8/2022 REPEAT COMMENT: NOT ADDRESSED. A SEPARATE | | | LANDSCAPE PERMIT SUBMITTAL IS REQUIRED. TO DATE, THERE | | | IS NO RECORD OF A LANDSCAPE PERMIT.] | | | | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, | | | DRIVEWAYS, ETC. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ANY CHANGES TO THE PERMIT PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * ZONE: BMUD-TYPE I | | | | | | * REFERENCE: CODE OF ORDINANCES, CH. 18 (BUILDINGS AND | | | BUILDING REGULATIONS) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-02-08 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2022-02-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-02-08 14:26:59 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED. | | | | | | 2.) MORE INFORMATION REQUIRED ON THE HABITABLE SPACE OF | | | EACH UNIT PROPOSED ON THE SUBJECT PROPERTY. UNIT SIZE | | | INFORMATION AND CALCULATIONS NOT PROVIDED IN THE PLANS. | | | | | | 3.) MINIMUM STANDARDS FOR ALL PROPOSED HABITABLE SPACE | | | SHALL BE CONSISTENT WITH CHAPTER 18 (BUILDINGS AND | | | BUILDING REGULATIONS) OF THE CITY?S CODE OF ORDINANCES. | | | | | | 4.) HOW WILL TRASH BE HANDLED FOR THE PROPERTY? PLEASE | | | IDENTIFY THE LOCATION ON SITE FOR TRASH CONTAINERS, | | | ETC. | | | | | | 5.) CLEARLY SHOW THE SETBACK FROM ALL PROPOSED HARD | | | SURFACES (I.E. STEPS, DRIVEWAY, ETC.) TO THE PROPERTY | | | LINE(S). SETBACK DISTANCES MUST CONFORM TO THE MINIMUM | | | SETBACK REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDRS). | | | | | | 6.) ONLY ONE (1) ACCESS POINT ON 34TH STREET IS | | | PERMITTED. PROPOSED SITE PLAN SHOWS TWO (2) ACCESS | | | POINTS WHICH IS NOT PERMITTED. [ZLDR S.94-312(1)] | | | | | | 7.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE?S | | | VALUE ($39,177.00) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, | | | DRIVEWAYS, ETC. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ANY CHANGES TO THE PERMIT PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * ZONE: BMUD-TYPE I | | | | | | * REFERENCE: CODE OF ORDINANCES, CH. 18 (BUILDINGS AND | | | BUILDING REGULATIONS) | | | |
|
|