Plan Review Details - Permit 22011099
Plan Review Stops For Permit 22011099
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By shill Date 2022-06-01 Time 09:51 Rev Time 0.00
Received By shill Date 2022-06-01 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By rmcdouga Date 2022-04-28 Time 06:51 Rev Time 0.00
Received By rmcdouga Date 2022-04-28 Time 06:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 15:14 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-30 Cont ID  
Sent By mpeterso Date 2022-03-30 Time 16:14 Rev Time 0.00
Received By mpeterso Date 2022-03-30 Time 16:14 Sent To  
Notes
2022-03-30 16:17:14ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ELECTRIC LOAD CALCULATION FOR
 EXISTING SERVICE INCLUDING ALL NEW LOADS NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-01 Cont ID  
Sent By shill Date 2022-06-01 Time 09:51 Rev Time 0.00
Received By shill Date 2022-05-04 Time 19:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-28 Cont ID  
Sent By rmcdouga Date 2022-04-28 Time 06:51 Rev Time 0.00
Received By rmcdouga Date 2022-03-09 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 12:17 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 12:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By lcrespo Date 2022-03-10 Time 13:38 Rev Time 0.00
Received By lcrespo Date 2022-03-10 Time 13:27 Sent To  
Notes
2022-03-10 13:38:5003/10/22 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, HEATER, CHLORINATOR, VALVES, AND FILTER. ALL
 SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 15:14 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 15:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By rmcdouga Date 2022-04-28 Time 06:51 Rev Time 0.00
Received By rmcdouga Date 2022-04-28 Time 06:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-17 Cont ID  
Sent By vbroglia Date 2022-03-17 Time 12:23 Rev Time 0.00
Received By vbroglia Date 2022-03-17 Time 12:23 Sent To  
Notes
***NONE***