Plan Review Details - Permit 22011040
Plan Review Stops For Permit 22011040
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By scwelter Date 2022-05-18 Time 13:53 Rev Time 0.00
Received By scwelter Date 2022-05-18 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 14:10 Sent To  
Notes
2022-08-01 14:52:07ADD RESTROOMS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) APPEARS TO BE A CHANGE OF OCCUPANCY - PLEASE PROVIDE
 A LIFE SAFETY PLAN SHOWING THE OCCUPANT LOAD, EGRESS
 TRAVEL DISTANCE AND WIDTH OF EXIT DOORS. FBC WPB
 107.3.5.1.1
  
 2) PLEASE SHOW THE UNIT DIMENSIONS, SQUARE FOOTAGE. FBC
 WPB 107.2
  
 3) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE DISTANCE
 FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET AND
 SHOWER GRAB BAR HEIGHT TO THE TOP OF THE GRIPPING
 SURFACE - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 5) ACCESSIBLE RESTROOM = PLEASE SHOW THE DIMENSION FOR
 THE TOILET PAPER HOLDER FROM THE FACE OF THE TOILET TO
 THE "CENTER" OF THE TOILET DISPENSER. FBC A 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 6) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER AREA TO
 COMPLY WITH FBC A 608.1 GENERAL.
 SHOWER COMPARTMENTS SHALL COMPLY WITH 608.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By rmcphers Date 2022-04-05 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2022-04-05 Time 13:13 Sent To  
Notes
2022-04-05 13:28:26ADD RESTROOMS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE WALL FRAMING DETAILS - FBC WPB
 107.2.1
  
 2) PLEASE SHOW WALL FINISHES TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR - (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) PLEASE SHOW BASE BOARDS TO COMPLY WITH FBC 1210.2.1
 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
  
 4) DRAWING (A 101) SHOWS A DRAWING INDEX WITH (A 102, A
 103) THESE DRAWINGS ARE NOT PROVIDED.
  
 5) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC
 CHAPTER 6
  
 6) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3
  
 7) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER - FBC WPB
 107.2.1
  
 8) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS AND
 DIMENSIONS (GRAB BAR HEIGHTS, GRAB BAR LOCATIONS,
 TOILET PAPER HOLDER LOCATIONS, MIRROR HEIGHT TO THE
 "REFLECTIVE SURFACE", FIXTURE FLOOR SPACE, DOOR SIZES)
 TO COMPLY WITH FBC ACCESSIBILITY

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-03-26 Cont ID  
Sent By fgiaquin Date 2022-03-26 Time 10:51 Rev Time 0.00
Received By fgiaquin Date 2022-03-26 Time 10:43 Sent To  
Notes
2022-03-26 10:51:11NO ELECTRICAL WORK REVIEWED OR APPROVED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-03-07 Cont ID  
Sent By rrossano Date 2022-03-07 Time   Rev Time  
Received By rrossano Date 2022-03-07 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-03 Cont ID  
Sent By cwalker Date 2022-03-03 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-06 Cont ID  
Sent By aoliver Date 2022-04-06 Time 09:32 Rev Time 0.00
Received By aoliver Date 2022-02-28 Time 09:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By rmcphers Date 2022-04-05 Time 13:31 Rev Time 0.00
Received By rmcphers Date 2022-04-05 Time 13:31 Sent To  
Notes
2022-04-05 13:31:52NO CHANGE OF OCCUPANCY - NO ADDITION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-07-22 Cont ID  
Sent By medwards Date 2022-07-22 Time 13:40 Rev Time 0.00
Received By medwards Date 2022-07-22 Time 13:39 Sent To  
Notes
2022-07-22 13:44:03SEE PREVIOUS REVIEW COMMENT BELOW: PROVIDE THE BATH
 EXHAUST FANS REQUIRED FOR THE BATHROOMS AND SHOW THE
 EXHAUST TERMINATION LOCATION. FMC TABLE 403.3.1.1
  
  
  
  
 PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEMS INSTALLED AT THIS UNIT ALONG WITH A MECHANICAL
 DRAWING SHOWING THE WORK. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-24 Cont ID  
Sent By medwards Date 2022-03-24 Time 07:17 Rev Time 0.00
Received By medwards Date 2022-03-24 Time 07:17 Sent To  
Notes
2022-03-24 07:19:23PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEMS INSTALLED AT THIS UNIT ALONG WITH A MECHANICAL
 DRAWING SHOWING THE WORK. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-07-25 Cont ID  
Sent By ccole Date 2022-07-25 Time 18:44 Rev Time 0.00
Received By ccole Date 2022-07-25 Time 16:10 Sent To  
Notes
2022-07-25 18:45:432ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22011040
 7/25/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. THE
 REQUESTED RESPONSE TO COMMENTS NARRATIVE WAS NOT
 PROVIDED
  
 1) FAILED SHEET A101: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE PLAN APPEARS TO SHOW A
 BUSINESS OCCUPANCY. PLEASE NOTE THAT DRINKING FOUNTAINS
 AND SERVICE SINKS ARE REQUIRED FIXTURES FOR BUSINESS
 OCCUPANCIES- SEE TABLE 403.1. FIXTURE CALCULATIONS AND
 SERVICE SINK NOT PROVIDED.
  
 4) FAILED. A101: INDICATE HOW HOT WATER WILL BE
 DELIVERED FROM THE SHOWER FAUCETS IN COMPLIANCE WITH
 SEC. 607.1 FBC P. SHOW THE LOCATION OF THE EXISTING
 WATER HEATER, OR PROVIDE A NEW WATER HEATER. A NEW
 WATER HEATER INSTALLATION WILL REQUIRE AN EQUIPMENT
 SCHEDULE ON THE PLAN, AND A MEANS OF CONTROLLING G
 THERMAL EXPANSION DETAILED- SECS. 502.1, 607.3 FBC P.
 A) PLEASE NOTE THAT A THERMOSTAT CONTROL FOR A WATER
 HEATER SHALL NOT SERVE AS THE TEMPERATURE LIMITING
 MEANS FOR THE PURPOSES OF COMPLYING WITH THE
 REQUIREMENTS OF THIS CODE FOR MAXIMUM ALLOWABLE HOT OR
 TEMPERED WATER DELIVERY TEMPERATURE AT FIXTURES. THE
 SOURCE OF THE HOT WATER AND TEMPERATURE LIMITING MEANS
 ARE NOT SHOWN.
  
 5) FAILED. A101: COLD WATER OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES IN COMPLIANCE WITH SEC.
 419.5 FBC P. PLEASE NOTE THAT TEMPERED WATER SHALL BE
 SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SEC. 607.1.2 FBC P. HOT
 WATER, NOT TEMPERED WATER IS BEING SUPPLIED TO THE NEW
 LAVATORIES
  
 6) FAILED. A101: PROVIDE A PLUMBING FIXTURE SCHEDULE-
 SEC. 405 FBC P. NOT PROVIDED
  
 7) FAILED. A101: PROVIDE A SLAB REPAIR DETAIL- SEC.
 107.2.1 WPB. NOT PROVIDED.
  
 8) FAILED ITEMS A, B, F, G, H, I, & J PROVIDE THE
 FOLLOWING DETAILS IN ACCORDANCE WITH SEC. 213.1 FBC
 ACCESSIBILITY CODE.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3. NOT PROVIDED.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2. NOT PROVIDED.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3 THE " MEASUREMENT
 IS TO THE FRAME OF THE MIRROR AND NOT THE REFLECTIVE
 SURFACE.
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. WATER CLOSET SIDE GRAB NOT
 SHOWN. REAR GRAB BAR IS SHOWN BUT MEASURMENTS NOT
 PROVIDED. THE 3'0" GRAB BAR HEIGHT MEASUREMENT SHOWN
 SHALL BE TO THE TOP OF THE GRIPPING SURFACES.
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6. NOT PROVIDED.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. NOT PROVIDED.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2. NOT PROVIDED.
  
 9) SHOWERS: FAILED ITEMS A, B, C, D.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.2. PLEASE NOTE THAT THE LOCATION OF
 THE SHOWER, SHOWER CONTROLS, AND WATER CLOSET ARE NOT
 IN COMPLIANCE WITH SEC. 608.2.2.1 EXCEPTION: A LAVATORY
 COMPLYING WITH 606 SHALL BE PERMITTED ON ONE 30-INCH
 WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED THAT IT IS
 NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE
 CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE
 CLEARANCE ADJACENT TO THE SHOWER SEAT. CORRECTIONS NOT
 PROVIDED. PLEASE NOTE A MINIMUM OF ONE OF THE SHOWERS
 SHALL BE ACCESSIBLE PER SEC. 213.3.6 FBC ACC. PLEASE
 REVIEW THE FOLLWING FBC ACC CODE SECTION-
  
 608.2.2.1 CLEARANCE.
 A 30-INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT.
 EXCEPTION: A LAVATORY COMPLYING WITH 606 SHALL BE
 PERMITTED ON ONE 30 INCH (760 MM) WIDE MINIMUM SIDE OF
 THE CLEARANCE PROVIDED THAT IT IS NOT ON THE SIDE OF
 THE CLEARANCE ADJACENT TO THE CONTROLS OR, WHERE
 PROVIDED, NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO
 THE SHOWER SEAT.
  
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECS. 608.3.2, 609.4. NOT PROVIDED.
  
 C) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS-
 SEC. 608.5.2. NOT PROVIDED.
  
 D) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. NOT
 PROVIDED.
  
 NEW COMMENTS BASED ON RESUBMITTED A-101 PLAN.
 1) PROVIDE ACCESSIBLE DRINKING FOUNTAIN DETAILS. REFER
 TO SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE
 DRINKING FOUNTAIN INSTALLATION DETAILS AND ELEVATION
 VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN.
 CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO
 THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 2) SANITARY ISOMETRIC: THE DRINKING FOUNTAIN DRAIN
 SHALL NOT CONNECT TO THE HORIZONTAL WET VENT FOR THE
 BATHROOMS. THE DRINKING FOUNTAINS SHALL BE INDIVIDUALLY
 VENTED AND THE DRAIN SHALL CONNECT EITHER UPSTREAM OR
 DOWNSTREAM OF THE WET VENT.
  
 3) SANITARY ISOMETRIC: REFER TO SEC. 904.1- THE VENT
 SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE NOT LESS
 THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. PLEASE
 SHOW THE LOCATION OF THE REQUIRED VENT.
  
 4) SHOWER CURB- THRESHOLDS FOR ACCESSIBLE ROLL IN
 SHOWERS SHALL BE MAXIMUM ?-INCH. THE DETAIL SHOWS A
 2-INCH THRESHOLD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-24 Cont ID  
Sent By ccole Date 2022-03-24 Time 16:41 Rev Time 0.00
Received By ccole Date 2022-03-24 Time 14:46 Sent To  
Notes
2022-03-24 16:44:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22011040
 3/24/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A101: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES. THE PLAN APPEARS TO SHOW A BUSINESS
 OCCUPANCY. PLEASE NOTE THAT DRINKING FOUNTAINS AND
 SERVICE SINKS ARE REQUIRED FIXTURES FOR BUSINESS
 OCCUPANCIES- SEE TABLE 403.1.
  
 2) A101: LABEL THE BATHROOMS AS MALE, FEMALE, OR
 FAMILY- SECS 403.2, 403.2.1, 403.4 FBC P.
  
 3) PROVIDE A WATER RISER DRAWING- SEC. 107.3.5.1.3 WPB.
  
 4) A101: INDICATE HOW HOT WATER WILL BE DELIVERED FROM
 THE SHOWER FAUCETS IN COMPLIANCE WITH SEC. 607.1 FBC P.
 SHOW THE LOCATION OF THE EXISTING WATER HEATER, OR
 PROVIDE A NEW WATER HEATER. A NEW WATER HEATER
 INSTALLATION WILL REQUIRE AN EQUIPMENT SCHEDULE ON THE
 PLAN, AND A MEANS OF CONTROLLING G THERMAL EXPANSION
 DETAILED- SECS. 502.1, 607.3 FBC P. A) PLEASE NOTE THAT
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  
 5) A101: COLD WATER OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES IN COMPLIANCE WITH SEC.
 419.5 FBC P. PLEASE NOTE THAT TEMPERED WATER SHALL BE
 SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SEC. 607.1.2 FBC P.
  
 6) A101: PROVIDE A PLUMBING FIXTURE SCHEDULE- SEC. 405
 FBC P.
  
 7) A101: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1
 WPB.
  
 8) PROVIDE THE FOLLOWING DETAILS IN ACCORDANCE WITH
 SEC. 213.1 FBC ACCESSIBILITY CODE.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 SHOWERS:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.2. PLEASE NOTE THAT THE LOCATION OF
 THE SHOWER, SHOWER CONTROLS, AND WATER CLOSET ARE NOT
 IN COMPLIANCE WITH SEC. 608.2.2.1 EXCEPTION: A LAVATORY
 COMPLYING WITH 606 SHALL BE PERMITTED ON ONE 30-INCH
 WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED THAT IT IS
 NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE
 CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE
 CLEARANCE ADJACENT TO THE SHOWER SEAT.
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECS. 608.3.2, 609.4.
 C) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS-
 SEC. 608.5.2.
 D) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By rmcphers Date 2022-04-05 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2022-04-05 Time 13:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-04 Cont ID  
Sent By afowlkes Date 2022-03-04 Time 16:23 Rev Time 0.00
Received By afowlkes Date 2022-03-04 Time 16:23 Sent To  
Notes
***NONE***