| 2022-07-25 18:45:43 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22011040 |
| | 7/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. THE |
| | REQUESTED RESPONSE TO COMMENTS NARRATIVE WAS NOT |
| | PROVIDED |
| | |
| | 1) FAILED SHEET A101: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES. THE PLAN APPEARS TO SHOW A |
| | BUSINESS OCCUPANCY. PLEASE NOTE THAT DRINKING FOUNTAINS |
| | AND SERVICE SINKS ARE REQUIRED FIXTURES FOR BUSINESS |
| | OCCUPANCIES- SEE TABLE 403.1. FIXTURE CALCULATIONS AND |
| | SERVICE SINK NOT PROVIDED. |
| | |
| | 4) FAILED. A101: INDICATE HOW HOT WATER WILL BE |
| | DELIVERED FROM THE SHOWER FAUCETS IN COMPLIANCE WITH |
| | SEC. 607.1 FBC P. SHOW THE LOCATION OF THE EXISTING |
| | WATER HEATER, OR PROVIDE A NEW WATER HEATER. A NEW |
| | WATER HEATER INSTALLATION WILL REQUIRE AN EQUIPMENT |
| | SCHEDULE ON THE PLAN, AND A MEANS OF CONTROLLING G |
| | THERMAL EXPANSION DETAILED- SECS. 502.1, 607.3 FBC P. |
| | A) PLEASE NOTE THAT A THERMOSTAT CONTROL FOR A WATER |
| | HEATER SHALL NOT SERVE AS THE TEMPERATURE LIMITING |
| | MEANS FOR THE PURPOSES OF COMPLYING WITH THE |
| | REQUIREMENTS OF THIS CODE FOR MAXIMUM ALLOWABLE HOT OR |
| | TEMPERED WATER DELIVERY TEMPERATURE AT FIXTURES. THE |
| | SOURCE OF THE HOT WATER AND TEMPERATURE LIMITING MEANS |
| | ARE NOT SHOWN. |
| | |
| | 5) FAILED. A101: COLD WATER OR TEMPERED WATER SHALL BE |
| | DELIVERED FROM THE LAVATORIES IN COMPLIANCE WITH SEC. |
| | 419.5 FBC P. PLEASE NOTE THAT TEMPERED WATER SHALL BE |
| | SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070- SEC. 607.1.2 FBC P. HOT |
| | WATER, NOT TEMPERED WATER IS BEING SUPPLIED TO THE NEW |
| | LAVATORIES |
| | |
| | 6) FAILED. A101: PROVIDE A PLUMBING FIXTURE SCHEDULE- |
| | SEC. 405 FBC P. NOT PROVIDED |
| | |
| | 7) FAILED. A101: PROVIDE A SLAB REPAIR DETAIL- SEC. |
| | 107.2.1 WPB. NOT PROVIDED. |
| | |
| | 8) FAILED ITEMS A, B, F, G, H, I, & J PROVIDE THE |
| | FOLLOWING DETAILS IN ACCORDANCE WITH SEC. 213.1 FBC |
| | ACCESSIBILITY CODE. |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. NOT PROVIDED. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. NOT PROVIDED. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 THE " MEASUREMENT |
| | IS TO THE FRAME OF THE MIRROR AND NOT THE REFLECTIVE |
| | SURFACE. |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. WATER CLOSET SIDE GRAB NOT |
| | SHOWN. REAR GRAB BAR IS SHOWN BUT MEASURMENTS NOT |
| | PROVIDED. THE 3'0" GRAB BAR HEIGHT MEASUREMENT SHOWN |
| | SHALL BE TO THE TOP OF THE GRIPPING SURFACES. |
| | H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC. |
| | 604.6. NOT PROVIDED. |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. NOT PROVIDED. |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. NOT PROVIDED. |
| | |
| | 9) SHOWERS: FAILED ITEMS A, B, C, D. |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SHOWER- SEC. 608.2.2. PLEASE NOTE THAT THE LOCATION OF |
| | THE SHOWER, SHOWER CONTROLS, AND WATER CLOSET ARE NOT |
| | IN COMPLIANCE WITH SEC. 608.2.2.1 EXCEPTION: A LAVATORY |
| | COMPLYING WITH 606 SHALL BE PERMITTED ON ONE 30-INCH |
| | WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED THAT IT IS |
| | NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE |
| | CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE |
| | CLEARANCE ADJACENT TO THE SHOWER SEAT. CORRECTIONS NOT |
| | PROVIDED. PLEASE NOTE A MINIMUM OF ONE OF THE SHOWERS |
| | SHALL BE ACCESSIBLE PER SEC. 213.3.6 FBC ACC. PLEASE |
| | REVIEW THE FOLLWING FBC ACC CODE SECTION- |
| | |
| | 608.2.2.1 CLEARANCE. |
| | A 30-INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM |
| | CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE |
| | OF THE SHOWER COMPARTMENT. |
| | EXCEPTION: A LAVATORY COMPLYING WITH 606 SHALL BE |
| | PERMITTED ON ONE 30 INCH (760 MM) WIDE MINIMUM SIDE OF |
| | THE CLEARANCE PROVIDED THAT IT IS NOT ON THE SIDE OF |
| | THE CLEARANCE ADJACENT TO THE CONTROLS OR, WHERE |
| | PROVIDED, NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO |
| | THE SHOWER SEAT. |
| | |
| | B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECS. 608.3.2, 609.4. NOT PROVIDED. |
| | |
| | C) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS- |
| | SEC. 608.5.2. NOT PROVIDED. |
| | |
| | D) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. NOT |
| | PROVIDED. |
| | |
| | NEW COMMENTS BASED ON RESUBMITTED A-101 PLAN. |
| | 1) PROVIDE ACCESSIBLE DRINKING FOUNTAIN DETAILS. REFER |
| | TO SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE |
| | DRINKING FOUNTAIN INSTALLATION DETAILS AND ELEVATION |
| | VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, |
| | AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. |
| | CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO |
| | THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE |
| | LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | 2) SANITARY ISOMETRIC: THE DRINKING FOUNTAIN DRAIN |
| | SHALL NOT CONNECT TO THE HORIZONTAL WET VENT FOR THE |
| | BATHROOMS. THE DRINKING FOUNTAINS SHALL BE INDIVIDUALLY |
| | VENTED AND THE DRAIN SHALL CONNECT EITHER UPSTREAM OR |
| | DOWNSTREAM OF THE WET VENT. |
| | |
| | 3) SANITARY ISOMETRIC: REFER TO SEC. 904.1- THE VENT |
| | SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE NOT LESS |
| | THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. PLEASE |
| | SHOW THE LOCATION OF THE REQUIRED VENT. |
| | |
| | 4) SHOWER CURB- THRESHOLDS FOR ACCESSIBLE ROLL IN |
| | SHOWERS SHALL BE MAXIMUM ?-INCH. THE DETAIL SHOWS A |
| | 2-INCH THRESHOLD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |