Plan Review Details - Permit 22011026
Plan Review Stops For Permit 22011026
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-03-03 Cont ID  
Sent By jleahy Date 2022-03-03 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-03-03 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By jleahy Date 2022-02-22 Time 12:02 Rev Time 0.00
Received By jleahy Date 2022-02-22 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 08:35 Rev Time 0.00
Received By jleahy Date 2022-02-03 Time 15:12 Sent To  
Notes
2022-02-04 08:35:54NEED TO SUBMIT SPEC SHEETS FOR LOCKS, CONTOLLER, AND
 CARD READERS. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-17 Cont ID  
Sent By pleduc Date 2022-03-17 Time   Rev Time 0.00
Received By pleduc Date 2022-03-17 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-02-14 Cont ID  
Sent By pleduc Date 2022-02-14 Time   Rev Time 0.00
Received By pleduc Date 2022-02-14 Time 11:29 Sent To  
Notes
2022-02-14 12:05:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PRODUCT SPECIFICATION HAVE BEEN PROVIDED; HOWEVER IT
 IS STILL NOT CLEAR ON WHAT AND WHERE THE CARD READERS
 WILL BE INSTALLED/LOCATED.
  
 PLEASE SHOW THE SPECIFIC LOCATION(S) OF THE CARD
 READERS, INCLUDING ON WHAT SIDE OF THE DOOR OPENING.
  
  
 2) THERE IS NO ACKNOWLEDGEMENT OF COMPLYING WITH NFPA
 101, CH 7, MEANS OF EGRESS, IF APPLICABLE.
  
 PLEASE PROVIDE A NOTE OF ACKNOWEDGEMENT RO COMPLY.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By pleduc Date 2022-02-07 Time   Rev Time 0.00
Received By pleduc Date 2022-02-07 Time 11:15 Sent To  
Notes
2022-02-07 11:35:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF THE SCOPE OF WORK.
  
 SHOULD THIS BE FOR CARD READERS/ACCESS CONTROL, THE
 PRODUCT SHEETS SHALL BE SUBMITTED.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK.
  
  
  
 1A) ALL CARDER READERS/ACCESS CONTROL SHALL COMPLY WITH
 THE REQUIRERMENTS OF NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-17 Cont ID  
Sent By lmarchan Date 2022-03-17 Time 14:13 Rev Time 0.00
Received By lmarchan Date 2022-03-16 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-22 Cont ID  
Sent By jleahy Date 2022-02-22 Time 12:03 Rev Time 0.00
Received By jleahy Date 2022-02-11 Time 12:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-07 Cont ID  
Sent By aoliver Date 2022-02-07 Time 12:02 Rev Time 0.00
Received By aoliver Date 2022-01-28 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 08:36 Rev Time 0.00
Received By jleahy Date 2022-02-04 Time 08:36 Sent To  
Notes
***NONE***