| 2022-02-09 07:24:27 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22011018 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE NOTE ABOVE THE HOOD 1 AND DUCT VELOCITY BOX IS |
| | REFERENCING A SECTION THAT IS NOT IN THE 2020 FBC EC, |
| | PLEASE PROVIDE THE SECTION OF CODE THAT APPLIES. FBC |
| | 107.2.1 |
| | |
| | 2) SECTION C OF THE DRAWING HAS BOTH THE EXHAUST AND |
| | MAKEUP AIR FANS LABELED AS KEF-1. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 3) PLEASE COMPLETE NOTE 9 UNDER THE HEADER TYPE 2 HOOD |
| | SYSTEM GENERAL NOTES, THE DISTANCE IS MISSING FROM THE |
| | NOTE. FBC 107.2.1 |
| | |
| | 4) PLEASE PROVIDE A DETAIL SHOWING THE LOCATION OF THE |
| | EXHAUST AND MAKEUP TERMINATIONS ON THE ROOF MEET THE 10 |
| | FEET CLEARANCE FROM THE ROOFS EDGE. FBC M 304.11 |
| | |
| | 5) THERE ARE REFERENCES OF GREASE DUCT ON THE DRAWING |
| | BUT THE GENERAL NOTES HEADER STATES TYPE 2 HOOD SYSTEM. |
| | IF THERE IS NO GREASE DUCT FOR THIS PROJECT PLEASE |
| | REMOVE THE GREASE DUCT REFERENCES AND DETAILS FOR |
| | CLARITY. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |