Plan Review Details - Permit 22010952
Plan Review Stops For Permit 22010952
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By jleahy Date 2022-06-06 Time 13:56 Rev Time 0.00
Received By jleahy Date 2022-06-06 Time 13:56 Sent To  
Notes
2022-06-06 14:00:24PLAN FOR PAD IS ONLY A COPY, EITHER BRING IN THE
 ORIGINAL PLAN OR DOWN LOAD A VERIFIABLE DIGITAL COPY OF
 THE PLAN..

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2022-03-23 Time 14:24 Sent To  
Notes
2022-03-23 14:28:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE A
 PRODUCT APPROVAL OR SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING. FBC AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By jleahy Date 2022-06-06 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-06-06 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By jleahy Date 2022-02-14 Time 14:34 Rev Time 0.00
Received By jleahy Date 2022-02-14 Time 12:22 Sent To  
Notes
2022-02-14 14:35:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 JAKE LEAHY
 BU1753, BN1165, PX163
 [email protected]
 561-805-6713
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NO WIRE SIZES SHOWN ON RISER DIAGRAM 215.5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-06 Cont ID  
Sent By lmarchan Date 2022-06-06 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2022-05-22 Time 12:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2022-01-26 Time 07:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By jleahy Date 2022-06-06 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-06-06 Time 15:07 Sent To  
Notes
2022-06-06 15:07:53PLAN FOR PAD IS ONLY A COPY, EITHER BRING IN THE
 ORIGINAL PLAN OR DOWN LOAD A VERIFIABLE DIGITAL COPY OF
 THE PLAN..

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By jleahy Date 2022-02-14 Time 14:18 Rev Time 0.00
Received By jleahy Date 2022-02-14 Time 12:22 Sent To  
Notes
2022-03-23 14:23:52THE SITE SPECIFIC GENERATOR PAD DRAWING WILL BE
 REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
2022-02-14 14:32:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 JAKE LEAHY
 BU1753, BN1165, PX163
 [email protected]
 561-805-6713
  
 PLANS NOT SIGNED
  
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1

Review Stop Z ZONING
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By vbroglia Date 2022-05-27 Time 12:50 Rev Time 0.00
Received By vbroglia Date 2022-05-27 Time 12:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By vbroglia Date 2022-02-02 Time 11:35 Rev Time 0.00
Received By vbroglia Date 2022-02-02 Time 11:35 Sent To  
Notes
2022-02-02 11:37:202/2/22 FAILED: GENERATOR MUST BE WITHIN THE PROPERTY
 LINES OF THE BUILDING PERMIT, THE CURRENT PROPOSED
 LOCATATION SHOWS THE GENERATOR OUTSIDE THE PROPERTY
 LINES.
  
 VALENTINA BROGLIA
 [email protected]