| Plan Review Stops For Permit 22010952 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-06 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-06 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2022-06-06 14:00:24 | PLAN FOR PAD IS ONLY A COPY, EITHER BRING IN THE | | | ORIGINAL PLAN OR DOWN LOAD A VERIFIABLE DIGITAL COPY OF | | | THE PLAN.. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-23 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-23 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2022-03-23 14:28:27 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE A | | | PRODUCT APPROVAL OR SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING. FBC AMENDMENTS 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-06 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-06 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-14 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-14 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2022-02-14 14:35:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | JAKE LEAHY | | | BU1753, BN1165, PX163 | | | [email protected] | | | 561-805-6713 | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | NO WIRE SIZES SHOWN ON RISER DIAGRAM 215.5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-06-06 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-22 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-23 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-26 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-06 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-06 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2022-06-06 15:07:53 | PLAN FOR PAD IS ONLY A COPY, EITHER BRING IN THE | | | ORIGINAL PLAN OR DOWN LOAD A VERIFIABLE DIGITAL COPY OF | | | THE PLAN.. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-14 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-14 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2022-03-23 14:23:52 | THE SITE SPECIFIC GENERATOR PAD DRAWING WILL BE | | | REQUIRED TO BE SIGNED AND SEALED BY THE ENGINEER. | | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | | YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & | | | FAC 61G15 | | 2022-02-14 14:32:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | JAKE LEAHY | | | BU1753, BN1165, PX163 | | | [email protected] | | | 561-805-6713 | | | | | | PLANS NOT SIGNED | | | | | | ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A | | | DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL | | | CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-05-27 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-05-27 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-05-27 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-02-02 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-02 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-02 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2022-02-02 11:37:20 | 2/2/22 FAILED: GENERATOR MUST BE WITHIN THE PROPERTY | | | LINES OF THE BUILDING PERMIT, THE CURRENT PROPOSED | | | LOCATATION SHOWS THE GENERATOR OUTSIDE THE PROPERTY | | | LINES. | | | | | | VALENTINA BROGLIA | | | [email protected] |
|
|