Plan Review Details - Permit 22010944
Plan Review Stops For Permit 22010944
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-15 Cont ID  
Sent By rmcdouga Date 2022-07-15 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2022-07-15 Time 11:02 Sent To  
Notes
2022-07-15 11:02:15PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. SUBMIT THE WIND DESIGN ENGINEERING FOR
 THE PREFABRICATED GENERATOR PAD. THE ENGINEER IS
 REQUIRED TO DIGITALLY SIGN AND SEAL THE PREFAB PAD
 DOCUMENTS. [PREFABRICATED GENERATOR PADS ARE REQUIRED
 TO HAVE A PRODUCT APPROVAL OR SITE SPECIFIC
 ENGINEERING. FBC AMENDMENTS 107.2.1]
  
 2) NOT RESOLVED. THE NOTE ON THE SURVEY STILL HAS 5
 FEET FROM OPENINGS. [THE GENERATOR EXHAUST IS REQUIRED
 TO BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A
 BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING
 DOCKS.]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-22 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2022-03-22 Time 17:21 Sent To  
Notes
2022-03-22 17:21:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE A
 PRODUCT APPROVAL OR SITE SPECIFIC ENGINEERING. FBC
 AMENDMENTS 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-06-07 Cont ID  
Sent By fgiaquin Date 2022-06-07 Time 23:10 Rev Time 0.00
Received By fgiaquin Date 2022-06-07 Time 23:05 Sent To  
Notes
2022-06-07 23:10:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED. ONLY
 COMMENT THAT HAS BEEN ADDRESSED IS NOW PLAN IS SIGNED
 BY QUALIFER. ADDRESS PREVIOUS COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By jleahy Date 2022-02-14 Time 11:25 Rev Time 0.00
Received By jleahy Date 2022-02-14 Time 11:22 Sent To  
Notes
2022-02-14 11:29:40FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM DOES NOT SHOW ALL WIRE SIZE, FROM METER
 TO FIRST TRANSFER SWITCH. 215.5
  
 FROM TRANSFER SWITCH TO 200A PANEL #3??? #3 NOT LARGE
 ENOUGH. 310.15(B)(7)(1,2)
  
 NO WIRE SIZES FROM 200A PANEL TO 200A PANEL. 215.5
  
 PLAN NOT SIGNED. PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-15 Cont ID  
Sent By rmcdouga Date 2022-07-15 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2022-05-22 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-22 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2022-01-26 Time 07:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-13 Cont ID  
Sent By rmcdouga Date 2022-06-13 Time 14:44 Rev Time 0.00
Received By rmcdouga Date 2022-06-13 Time 14:44 Sent To  
Notes
2022-06-13 14:45:16THE ENGINEER'S SIGNATURE ON THE PAPER PLANS THAT WERE
 SUBMITTED IS A COPY. ELECTRONICALLY SUBMITTED DRAWINGS
 ARE REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS
 471 & FAC 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By jleahy Date 2022-02-14 Time 11:32 Rev Time 0.00
Received By jleahy Date 2022-02-14 Time 11:22 Sent To  
Notes
2022-03-22 17:23:29THE ENGINEER'S SIGNATURE WILL BE REQUIRED ON SITE
 SPECIFIC GENERATOR PAD DRAWINGS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
2022-02-14 11:32:52PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-27 Cont ID  
Sent By vbroglia Date 2022-05-27 Time 12:55 Rev Time 0.00
Received By vbroglia Date 2022-05-27 Time 12:55 Sent To  
Notes
2022-05-27 12:57:075/27/2022 FAILED
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK
  
 REQUIRED SIDE SETBACK: 5 FEET
 REQUIRED REAR SETBACK: 10 FEET
  
 GENERATOR NEEDS TO BE 6 FEET AWAY FROM REAR PROPERTY
 LINE
  
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-01-31 Cont ID  
Sent By vbroglia Date 2022-01-31 Time 10:59 Rev Time 0.00
Received By vbroglia Date 2022-01-31 Time 10:59 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved