| | 22010929 319 CLEMATIS ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. G-0003, G-0004 AND G-0005; 2010 ADA REGULATIONS. |
| | MOST OF THE REQUIREMENTS OF 2020 FLORIDA BUILDING CODE |
| | FOR PLUMBING FIXTURES ARE MET ON THESE PAGES; SOME ARE |
| | ADDRESSED ON I-4002, I-4003, I-4004, I-4005, I-4006, |
| | I-4007, I-4016 AND I-4017 AND MY COMMENTS BELOW ARE |
| | DIRECTED AT THOSE SHEETS AS THE ADA SHEETS DID NOT |
| | ADDRESS THEM. |
| | ...A) PER WPB FBC 107.2.1, PROVIDE NOTE ON ALL SHEETS |
| | LISTED ABOVE STATING "COMPLY WITH 2020 FLORIDA BUILDING |
| | CODE, ACCESSIBILITY, 7TH EDITION" |
| | ...B) ) PER WPB FBC 107.2.1, PROVIDE NOTE ON SHEETS |
| | I-4002, I-4003, I-4004, I-4005, I-4006, I-4007, I-4016 |
| | AND I-4017 STATING "REFER TO G-0003, G-0004 AND G-0005 |
| | FOR ADDITIONAL ACCESSIBILITY REQUIREMENTS." |
| | |
| | 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOMS AND ACCESSIBLE PLUMBING FIXTURES |
| | INDICATING THE FOLLOWING: |
| | ...A) I-4004: PROVIDE TURNING SPACE FOR TRANSFER SHOWER |
| | VESTIBULES (FBC ACC 304.3.1 OR 304.3.2) AND GRAB BAR |
| | HEIGHTS FOR TRANSFER SHOWERS (FBC ACC 609.4). |
| | ...B) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE |
| | FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES |
| | MAXIMUM MEASURED TO THE TOP OF THE SEAT PER FBC ACC |
| | 604.4. |
| | ...C) I-4002, I-2003, I-4016 AND I-4017: PROVIDE THE |
| | KNEE AND TOE CLEARANCES (DIMENSIONS)FOR THE LAVATORIES. |
| | SEE FBC ACC 606.2. |
| | ...D) I-4002, I-2003, I-4016 AND I-4017: PROVIDE ON THE |
| | ELEVATION DETAIL OF THE LAVATORIES IN THE WHEELCHAIR |
| | ACCESSIBLE TOILET COMPARTMENT THE HEIGHTS OF THE SINK |
| | RIMS FROM THE FINISHED FLOORS PER FBC 602.3. AND THE |
| | KNEE AND TOE CLEARANCES- SECS 606.2 & 606.3 FBC ACC. A |
| | ...E) I-4002, I-2003, I-4016 AND I-4017: MIRRORS |
| | LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND PER FBC ACC 603.3. PER WPB FBC 107.2.1 |
| | INDICATE REFLECTING SURFACE. |
| | ...F) I-4002 AND I-4007: PROVIDE CLEAR FLOOR OR GROUND |
| | SPACE FOR PANTRY SINK AND DRINKING FOUNTAIN. COMPLYING |
| | WITH FBC ACC 305. |
| | |
| | 3. DRINKING FOUNTAIN: PROTRUDING OBJECTS 307.2 |
| | PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES |
| | MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE |
| | THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| | HORIZONTALLY INTO THE CIRCULATION PATH. |
| | |
| | 4. DRINKING FOUNTAINS SHALL COMPLY WITH FBC ACC 306, |
| | 307 AND 602 PER FBC ACC 602.1. PER WPB FBC 107.2.1, |
| | PROVIDE DETAIL SHOWING THE FOLLOWING: |
| | ...A) SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND PER FBC ACC 602.4. |
| | ...B) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES MINIMUM AND 43 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| | 602.7. |
| | ...C) DIMENSIONED KNEE AND TOE SPACE PER FBC ACC 306, |
| | 307. |
| | |
| | 5. PLAN SHEET G-0003/PLUMBING CALCULATIONS: PER FBC PL |
| | TABLE 403.1, A SERVICE SINK IS REQUIRED; EITHER MAKE |
| | PROVISION FOR AND PROVIDE, OR IF EXISTING OUTSIDE OF |
| | SCOPE, NOTE THE SAME. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE NOTE OR CHART OF |
| | REQUIRED MINIMUM SLOPES OF SANITARY DRAIN PIPING |
| | SHOWING COMPLIANCE WITH FBC PL 704.1/TABLE 704.1. |
| | |
| | 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 8. PER FBC PL 604.9 A WATER HAMMER ARRESTOR IS REQUIRED |
| | FOR THE COLD WATER TO THE REFRIGERATOR |
| | |
| | 9. PER WPB FBC 107.2.1, SPECIFY CARRIER FOR WALL HUNG |
| | WATER CLOSETS SHOWING COMPLIANCE WITH FBC PL 405.4.3. |
| | |
| | 10. PLAN SHEET E3.1/PANEL 3A INDICATES A COFFEE MACHINE |
| | AND A CAPPUCCINO MACHINE. IF WATER CONNECTIONS ARE |
| | REQUIRED FOR THESE ITEMS, PER WPB FBC 107.2.1, SHOW ON |
| | DRAWINGS; ADD TO CONNECTION SCHEDULE AND SPECIFY AND |
| | PER FBC PL 608.1.2, SPECIFY AND PROVIDE LEAD FREE |
| | BACKFLOW PREVENTERS. |
| | |
| | 11. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES EZH20 |
| | BI-LEVEL DRINKING FOUNTAIN WITH BOTTLE FILLER. |
| | I-6006/PLUMBING SCHEDULE CALLS EZWS-EDFPBM117K WITH |
| | BI-LEVEL DRINKING FOUNTAIN WITH BOTTLE FILLER. PER WPB |
| | FBC 107.2.1, CLARIFY AND RECONCILE THE TWO DRAWINGS. |
| | |
| | 12. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES SLOAN |
| | ST-2469 WALL HUNG WATER CLOSET WITH REAR SPUD INLET AND |
| | SLOAN CX8158-1.28 CONCEALED FLUSHOMETER. |
| | I-6006/PLUMBING SCHEDULE CALLS FOR THE SAME WATER |
| | CLOSET WITH A MAC FAUCETS ATV-2 EXPOSED FLUSHOMETER FOR |
| | A TOP INLET. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE |
| | THE TWO DRAWINGS. |
| | |
| | 13. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES SLOAN |
| | SU-7019 WALL HUNG URINAL WITH REAR SPUD INLET AND SLOAN |
| | CX8198-0.5 CONCEALED FLUSHOMETER. I-6006/PLUMBING |
| | SCHEDULE CALLS FOR THE URINAL WITH A MAC FAUCETS AUV-2 |
| | EXPOSED FLUSHOMETER WITH A TOP INLET. PER WPB FBC |
| | 107.2.1, CLARIFY AND RECONCILE THE TWO DRAWINGS. |
| | |
| | 14. I-4002, I-2003, I-4016 AND I-4017 ALL INDICATE |
| | EXPOSED FLUSHOMETERS FOR WATER CLOSETS AND URINALS. |
| | I-6006/PLUMBING SCHEDULE CALLS FOR EXPOSED |
| | FLUSHOMETERS; P-6001/PLUMBING FIXTURE SCHEDULE CALLS |
| | FOR CONCEALED FLUSHOMETERS. PER WPB FBC 107.2.1, |
| | CLARIFY AND RECONCILE ALL DRAWINGS. |
| | |
| | 15. P-6001/EWH MOUNTING AND PIPING DETAIL: |
| | ...A) PROVIDE VACUUM BREAKER FOR HOSE BIB PER FBC PL |
| | 608.16.4.2. |
| | ...B) PROVIDE WATER HAMMER ARRESTOR AT SOLENOID VALVE |
| | PER FBC PL 604.9. |
| | ...C) PAN DRAIN DISCHARGES TO FFD-1. PER WPB FBC |
| | 107.2.1, PROVIDE TRAPPED AND VENTED FFD-1 AND |
| | APPROPRIATE TRAP SEAL PROTECTION AS REQUIRED BY FBC PL |
| | 1002.4.1 |
| | |
| | 16. P-6001/DETAIL3 INDICATES A DISHWASHER. PER WPB FBC |
| | 107.2.1, INDICATE ON PLANS AND PROVIDE A WATER HAMMER |
| | ARRESTOR ON HOT WATER SUPPLY. IF THE DETAIL IS NOT |
| | APPLICABLE, PER WPB FBC 107.2.1, REMOVE IT. |
| | |
| | 17. PER WPB FBC 107.2.1, PROVIDE A DESCRIPTION OF EI-1, |
| | ADD TO PLUMBING FIXTURE SCHEDULE/CONNECTION SCHEDULE. |
| | PROVIDE WATER HAMMER ARRESTOR IF APPLICABLE; SEE FBC PL |
| | 604.9. FBC PL 608.1.2, SPECIFY PROVIDE LEAD FREE |
| | BACKFLOW PREVENTER IF APPLICABLE; SEE FBC PL 608.1 |
| | |
| | 18. IS LEVEL 1 ELEVATED OR SLAB ON GRADE? IF SLAB ON |
| | GRADE, PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR |
| | DETAIL ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE |
| | MINIMUM THICKNESS AND PSI OF THE CONCRETE TO BE |
| | REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER), |
| | MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR |
| | DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT |
| | OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER |
| | WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE |
| | SHALL BE ONSITE FOR FINAL INSPECTION. |
| | |
| | 19. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| | WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING |
| | WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| | |
| | 20. P-6001/DETAIL 5: PER FBC PL 602.2 SHUTOFF VALVES |
| | SHALL BE LOCATED ON THE FIXTURE SUPPLY TO EACH PLUMBING |
| | FIXTURE. THE DETAIL PROVIDED IS ADEQUATE WHEN ONLY ONE |
| | FIXTURE IS INVOLVED. HOWEVER, THE PLANS INDICATE |
| | INSTANCES WHERE MULTIPLE FIXTURES ARE SERVED BY THE |
| | SAME WATER HEATER. PER WPB FBC 107.2.1, ADD NOTE TO |
| | DETAIL STATING THAT WHERE MORE THAN ONE FIXTURE IS |
| | SERVED BY THE WATER HEATER, EACH FIXTURE SHALL HAVE A |
| | DEDICATED SHUTOFF VALVE. |
| | |
| | 21. P-6001/PLUMBING FIXTURE SCHEDULE: PER WPB FBC |
| | 107.2.1, ADD PANTRY SINK TO SCHEDULE. |
| | |
| | 22. P-5001/WATER RISER FOR OFFICE TOILET ROOMS AND |
| | PANTRY SINK: PER WPB FBC 107.2.1, PLEASE CLEARLY |
| | INDICATE THE SIZES OF THE COLD WATER DISTRIBUTION FROM |
| | THE 2 INCH REDUCING TEE THAT SERVES THE PANTRY AND THE |
| | WATER CLOSETS TO THE WATER CLOSETS. IF NECESSARY, |
| | REMOVE THE WATER HEATER FOR CLARITY. |
| | |
| | 23. GENERAL NOTE; SHOULD ANY BACKFLOW PREVENTERS BE |
| | REQUIRED, PER WPB FBC 107.2.1, A SCHEDULE SHALL BE |
| | PROVIDED LISTING FIXTURE OR EQUIPMENT CONNECTED, TYPE |
| | OF DEVICE AND APPLICABLE STANDARD (SEE FBC PL TABLE |
| | 608.1) AND NOTE STATING DEVICES SHALL BE LEAD FREE. |
| | |
| | END OF COMMENTS |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 22010929 319 CLEMATIS ST |
| | |