Plan Review Details - Permit 22010918
Plan Review Stops For Permit 22010918
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-02-04 Cont ID  
Sent By cpuell Date 2022-02-04 Time 14:51 Rev Time 0.00
Received By cpuell Date 2022-02-04 Time 14:51 Sent To  
Notes
2022-02-04 14:53:17ADDRESS APPROPRIATE FOR PROJECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-24 Cont ID  
Sent By pleduc Date 2022-03-24 Time   Rev Time 0.00
Received By pleduc Date 2022-03-24 Time 11:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By pleduc Date 2022-02-07 Time   Rev Time 0.00
Received By pleduc Date 2022-02-07 Time 11:40 Sent To  
Notes
2022-02-07 11:45:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF A FLOOR PLAN SHOWING THE
 EXACT LOCATION OF THE PROPOSED.
  
 PLEASE PROVIDE A FLOOR PLAN WITH SPECIFIC DETAILS.
  
  
 1A) THERE IS NO INDICATION OF PROVIDE FOR FIRE
 SPRINKLER PROTECTION WITHIN THE COOLERS.
  
 FIRE PROTECTION IS REQUIRED TO BE EXTENDED TO WITHIN
 THE COOLERS.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLVE NOTE OF
 ACKNOWLEDGEMENT TO PROVIDE PROTECTION.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 11:19 Rev Time 0.00
Received By medwards Date 2022-04-22 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-19 Cont ID  
Sent By aoliver Date 2022-04-19 Time 07:10 Rev Time 0.00
Received By aoliver Date 2022-03-23 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-15 Cont ID  
Sent By aoliver Date 2022-02-15 Time 08:39 Rev Time 0.00
Received By aoliver Date 2022-02-04 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 11:19 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-29 Cont ID  
Sent By medwards Date 2022-03-29 Time 14:40 Rev Time 0.00
Received By medwards Date 2022-03-29 Time 14:40 Sent To  
Notes
2022-03-29 15:48:28PLEASE SUBMIT THE APPROVED REVISED DRAWING THAT WAS
 SENT TO MY EMAIL ON 3/29/2022.
2022-03-29 14:41:45 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 12:58 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 12:58 Sent To  
Notes
2022-02-14 12:59:161ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010918
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT DRAWINGS SHOWING THE LOCATION OF THESE
 COOLERS IN REFERENCE TO THE TENANT SPACE. PLEASE ALSO
 SHOW WHERE THE CONDENSING UNITS WILL BE LOCATED ALONG
 WITH HOW THEY WILL BE ANCHORED DOWN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 11:19 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 11:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-29 Cont ID  
Sent By medwards Date 2022-03-29 Time 14:43 Rev Time 0.00
Received By medwards Date 2022-03-29 Time 14:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 13:02 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 12:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By eschneid Date 2022-04-18 Time 18:10 Rev Time 0.25
Received By eschneid Date 2022-04-18 Time 17:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-14 Cont ID  
Sent By eschneid Date 2022-02-14 Time 17:23 Rev Time 0.25
Received By eschneid Date 2022-02-14 Time 17:23 Sent To  
Notes
2022-02-14 17:31:45FAILED
  
 1) THE COOLER PLAN SEEMS TO INDICATE THAT THERE IS
 ROOFTOP MECHANICAL EQUIPMENT BEING INSTALLED (ACCU TIE
 DOWN FOR 170 MPH WINDS). IF THERE IS ROOFTOP EQUIPMENT
 PROPOSED:
  
 A. PROVIDE A ROOF PLAN SHOWING WHERE THIS EQUIPMENT
 WILL BE LOCATED. THE APPROVED BUILD-OUT PLAN DOES NOT
 SEEM TO HAVE ROOFTOP EQUIPMENT LOCATED IN PROXIMITY TO
 THE COOLER LOCATIONS AND THUS IT DOES NOT APPEAR THIS
 NEW EQUIPMENT WAS PREVIOUSLY REVIEWED.
  
 B. IF THERE IS NEW ROOFTOP EQUIPMENT, THEN THE FULL
 HEIGHT OF THE EQUIPMENT, INCLUDING ANY MOUNTING STANDS,
 MUST BE PROVIDED AND VERIFICATION THAT THE FULL HEIGHT
 OF THE EQUIPMENT IS SCREENED.
  
 C. IF THERE IS NEW ROOFTOP EQUIPMENT, THE PLANS MUST
 INCLUDE THE CITYPLACE RETAIL APPROVAL STAMP.
  
 2) IF THERE IS NO EXTERIOR EQUIPMENT, THIS PERMIT WOULD
 PASS ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]