Plan Review Details - Permit 22010834
Plan Review Stops For Permit 22010834
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-03-02 Cont ID  
Sent By cpuell Date 2022-03-02 Time 16:44 Rev Time 0.00
Received By cpuell Date 2022-03-02 Time 16:44 Sent To  
Notes
2022-03-02 16:45:12I HAVE RETIRED 2302, 2304, 2310 AND 2316 FLORIDA AVE,
 THE NEW PRIMARY ADDRESS IS 2350 FLORIDA AVE. UPDATED
 PERMIT DOCS

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-03-02 Cont ID  
Sent By cpuell Date 2022-03-02 Time 11:56 Rev Time 0.00
Received By cpuell Date 2022-03-02 Time 11:56 Sent To  
Notes
2022-03-02 12:02:56PER CORRESPONDENCE WITH MATT CORSON, ADDRESS ON SITE
 AFFECTED BY THIS PERMIT 2302, 2304, 2310 AND 2316
 FLORIDA AVE. STATED THAT A NEW ADDRESS IS REQUIRED AND
 THAT THE OLD ADDRESSES WOULD BE RETIRED, BASED ON THE
 LOCATION OF THE MAIN ENTRANCE AND THE CITY?S ROAD
 CENTER LINE, I AM PROPOSING THE ADDRESS OF 2350 FLORIDA
 AVE. PLEASE HAVE OWNER CONTACT ME SO THAT WE CAN
 APPROVE AN ADDRESS FOR THE BUILDING, [email protected] OR
 CALL 561-805-6659.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-30 Cont ID  
Sent By cpuell Date 2022-01-30 Time 09:51 Rev Time 0.00
Received By cpuell Date 2022-01-30 Time 09:51 Sent To  
Notes
2022-01-30 09:52:57PLANS APPREAR TO BE INCOMPASSING THE FOLLOWING
 ADDRESSES; 2302, 2304, 2310 AND 2316 FLORIDA AVE, ARE
 THESE SUITES TO BE MERGERD OR IS WORK TO BE DONE TO
 EACH SUITE? PLEASE RESPOND TO [email protected] OR CALL
 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-17 Cont ID  
Sent By rmcphers Date 2022-05-17 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2022-05-17 Time 15:07 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 08:52 Rev Time 0.00
Received By rmcphers Date 2022-04-07 Time 16:03 Sent To  
Notes
2022-04-11 08:53:13PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2022-08-24 Cont ID  
Sent By rmcphers Date 2022-08-24 Time 08:25 Rev Time 0.00
Received By rmcphers Date 2022-08-24 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2022-08-09 Cont ID  
Sent By rmcphers Date 2022-08-09 Time 10:49 Rev Time 0.00
Received By rmcphers Date 2022-08-09 Time 10:49 Sent To  
Notes
2022-08-09 10:50:06BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1.0 HAS BEEN REVISED - REMOVING THE
 ACCESSIBLE RAMP AND ADDING AN ACCESSIBLE LIFT AT THE
 REAR OF THE BUILDING. ALL OTHER DRAWINGS STILL SHOW A
 RAMP NEAR THE ACCESSIBLE PARKING. THE ACCESSIBLE
 ENTRANCE SHOULD BE IN THE FRONT "COMMON ENTRY" AS NOTED
 ON DRAWING A1.0 "ENTRY"
  
 FBC 208.3.1 PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44
 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES
 EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 FBC 202.3.3 BARRIERS AT COMMON OR EMERGENCY ENTRANCES
 AND EXITS.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2022-08-04 Cont ID  
Sent By rmcphers Date 2022-08-04 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2022-08-04 Time 14:08 Sent To  
Notes
2022-08-04 14:18:31BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1.0 HAS BEEN REVISED - REMOVING THE
 ACCESSIBLE RAMP AND ADDING AN ACCESSIBLE LIFT AT THE
 REAR OF THE BUILDING. ALL OTHER DRAWINGS STILL SHOW A
 RAMP NEAR THE ACCESSIBLE PARKING. THE ACCESSIBLE
 ENTRANCE SHOULD BE IN THE FRONT "COMMON ENTRY" AS NOTED
 ON DRAWING A1.0 "ENTRY"
  
 FBC 208.3.1 PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44
 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES
 EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 FBC 202.3.3 BARRIERS AT COMMON OR EMERGENCY ENTRANCES
 AND EXITS.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-07-26 Cont ID  
Sent By rmcphers Date 2022-07-26 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2022-07-26 Time 09:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-18 Cont ID  
Sent By rmcphers Date 2022-07-18 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2022-07-18 Time 14:04 Sent To  
Notes
2022-07-18 14:08:13BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL - FL21892 - PLEASE PROVIDE THE
 FRONT PAGES OF THE FLORIDA PRODUCT APPROVAL. THE FRONT
 PAGES SHOWS IF IT IS APPROVED.
  
 2) PRODUCT APPROVAL - FL20877 - PLEASE PROVIDE THE
 FRONT PAGES OF THE FLORIDA PRODUCT APPROVAL. THE FRONT
 PAGES SHOWS IF IT IS APPROVED.
  
 3) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE ARCHITECT OF RECORD. FBC WPB 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-24 Cont ID  
Sent By rmcphers Date 2022-06-24 Time 16:40 Rev Time 0.00
Received By rmcphers Date 2022-06-24 Time 16:40 Sent To  
Notes
2022-06-24 16:41:30BUILDING ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - NO CHANGES SINCE THE LAST REVIEW
  
 1) DRAWING S0.1 SHOWS THE WIND DESIGN USING ASCE 7-10 -
 SHOULD BE ASCE 7-16 - PER FBC CHAPTER 35
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS.
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC 107.3.4
  
 3) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By rmcphers Date 2022-05-17 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2022-05-17 Time 15:45 Sent To  
Notes
2022-05-17 15:52:36BUILDING ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S0.1 SHOWS THE WIND DESIGN USING ASCE 7-10 -
 SHOULD BE ASCE 7-16 - PER FBC CHAPTER 35
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS.
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC 107.3.4
  
 3) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2022-04-07 Time 16:03 Sent To  
Notes
2022-04-11 09:13:19BUILDING ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ALL DRAWINGS NEED TO BE SIGNED BY THE DESIGNER OF
 THE DRAWING FBC WPB 107.1
  
 2) PLEASE SHOW THE RAMP LANDING DIMENSIONS AT THE TURN
 IN THE RAMP TO COMPLY WITH FBC ACCESSIBILITY
 405.7.4CHANGE IN DIRECTION.
 RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS
 SHALL HAVE A CLEAR LANDING 60 INCHES (1525 MM) MINIMUM
 BY 60 INCHES (1525 MM) MINIMUM.
  
 3) DRAWING S0.1 SHOWS THE DESIGN USE OF ASCE 7-10 -
 SHOULD BE ASCE 7-16 - PER FBC CHAPTER 35
  
 4) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE (18"
 BESIDE THE LATCH SIDE) TO EXIT THE ACCESSIBLE RESTROOM
 FBC ACCESSIBILITY 404.2.4
  
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS DOORS AND
 ROOFING SYSTEMS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 07:57 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By mpeterso Date 2022-05-17 Time 12:35 Rev Time 0.00
Received By mpeterso Date 2022-05-17 Time 12:35 Sent To  
Notes
2022-05-17 12:43:58ELECTRIC REVIEW FAILED
 1) RESPONSE TO COMMENTS STATES A NOTE WAS ADDED TO
 SHEET E-0.01 STATING, GENERATOR, LOW VOLTAGE WIRING,
 FIRE ALARM SYSTEM, ACCESS CONTROL, SITE LIGHTING AND
 SIGNS ARE UNDER A SEPARATE PERMIT. PLEASE ADD THIS NOTE
 AS THIS NOTE CANNOT BE LOCATED ON SHEETS SUBMITTED .
 FBC 107.2
 2) PLEASE CORRECT RISER DIAGRAM TO DETAILTHE REQUIRED
 CONNECTION FOR TEMPORARY SOURCE OF POWER FOR
 MAINTAINANCE AND REPAIR OF THE ALTERNATE SOURCE OF
 POWER AS REQUIRED PER NEC 700.3(F) FOR EMERGENCY
 SYSTEMS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By mpeterso Date 2022-03-16 Time 15:09 Rev Time 0.00
Received By mpeterso Date 2022-03-16 Time 15:09 Sent To  
Notes
2022-03-16 15:10:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL CONDUIT LOCATIONS AND WIRING METHODS
 FOR FIRE PUMP FEEDERS TO ENSURE THEY COMPLY WITH NEC
 695.6
 2) PLEASE PROVIDE NOTES INSTRUCTING COMPLIANCE WITH
 DISCONNECT MARKING AS PER NEC 695.4(B)(3)(C)
 3) PLEASE PROVIDE DETAILS USED FOR INTEGRITY OF
 GENERATOR CONTROL WIRING TO COMPLY WITH NEC 695.14(F)
 4) PLEASE PROVIDE NOTE STATING FIRE PUMP GENERATOR
 OVERLOAD PROTECTION IS SHORT CIRCUIT ONLY, NO OVERLOAD
 PROTECTION
 5) PLEASE PROVIDE NOTES STATING, GENERATOR, LOW VOLTAGE
 WIRING, FIRE ALARM SYSTEM, ACCESS CONTROL, SITE
 LIGHTING AND SIGNS ARE UNDER A SEPARATE PERMIT
 6) PLEASE CHANGE NOMENCLATURE INDICATING DUCT HEATERS
 TO DEHUMIDIFIERS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-08-23 Cont ID  
Sent By rrossano Date 2022-08-23 Time   Rev Time 0.00
Received By rrossano Date 2022-08-23 Time   Sent To  
Notes
2022-08-23 09:46:23PASSED WITH PROVISO:
  
 PERMIT APPROVED EXCLUDING THE CIVIL SITE WORK WHICH
 REQUIRES A SEPARATE ENGINEERING SUBMITTAL.
  
 THANKS,
  
 RICK ROSSANO
 SENIOR PROJECT COORDINATOR
 CITY OF WPB ENGINEERING SERVICES
 OFC: (561) 494-1098
 CELL: (561) 246-9525
 FAX: (561) 494-1116
  
 WHEN CORRESPONDING REGARDING DEVELOPER PROJECTS, PLEASE
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (E-XXXXXXXX, OR Z-XXXXXXXX). ALSO, PLEASE ALWAYS
 PROVIDE ENGINEERING SUBMITTALS ELECTRONICALLY (EMAILED
 PDF OR DOWNLOAD LINK, OR A DISC OR THUMB DRIVE) IN
 TANDEM WITH HARD COPIES. USE THE DROP BOX INSIDE THE
 FIRST FLOOR FRONT DOOR OF CITY HALL MARKED ?ENGINEERING
 DROP BOX?. WHEN DROPPING OFF DOCUMENTS, PLEASE CALL
 BEFORE DOING SO TO COORDINATE RECEIPT OF DOCUMENTS.
  
 ONLINE LINKS FOR ENGINEERING FORMS, PUBLICATIONS AND
 STANDARD DETAILS: HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINE
 ERING/ENGINEERING-FORMS-PERMITS-AND-APPLICATIONS
  
 24 HR. CENTRAL OPS DISPATCH (EMERGENCY RESPONSE FOR
 PUBLIC UTILITIES, PUBLIC WORKS, PARKS, ETC.)
 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-16 Cont ID  
Sent By   Date 2022-06-16 Time   Rev Time 0.00
Received By bdolan Date 2022-06-16 Time 10:34 Sent To  
Notes
2022-06-16 10:37:13FIRE SPRINKLER IS ADDRESSED IN PERMIT #22010883, F/A
 #22051087.
  
 PLAN/DRAWINGS FOR FIRE UNDERGROUND LINE WILL NEED TO BE
 SUBMITTED UNDER SEPERATE PERMIT.
  
 FIRE HAS NO OBJECTION TO THE PROPOSED PROJECT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By   Date 2022-05-16 Time   Rev Time 0.00
Received By bdolan Date 2022-05-16 Time 10:37 Sent To  
Notes
2022-05-16 10:42:53COMMENTS FROM PRIOR REVIEW NOT ADDRESSED.
  
 PLANS STATE BUILDING IS "FULLY SPRINKLERED" WITH FIRE
 ALARM SYSTEM. PLEASE ADDRESS FS AND FA SYSTEMS IN PLAN
 SET. SPECIFIY IF SYSTEMS ARE EXISTING OR NEW INSTALLS.
 IF NEW SYSTEM, PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ALL WORK ON FIRE SPRINKLER OR ALARM SYSTEMS ARE
 REQUIRED TO BE COMPLETED BY A CERTIFIED CONTRACTOR AND
 SHALL COMPLY WITH NFPA STANDARDS. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 WORK ON THE SYSTEM. ALL SPRINKLER AND ALARM SYSTEM WORK
 MUST BE UNDER SEPARATE PERMITS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-16 Cont ID  
Sent By   Date 2022-03-16 Time   Rev Time 0.00
Received By bdolan Date 2022-03-16 Time 09:39 Sent To  
Notes
2022-03-16 09:51:36EXISTING WAREHOUSE HAS A FIRE SPRINKLER SYSTEM IN
 PLACE. PLEASE ADDRESS EXISTING FIRE PROTECTION SYSTEMS
 IN PLAN SET.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-05-17 Cont ID  
Sent By ccole Date 2022-05-17 Time 16:52 Rev Time 0.00
Received By ccole Date 2022-05-17 Time 16:52 Sent To  
Notes
2022-05-17 16:55:00A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE
 GAS GENERATOR. A COMPLETE REVIEW OF THE GAS PIPING AND
 GENERATOR INSTALLATIONS WAS NOT PEFORMED UNDER THIS
 PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-03-14 Cont ID  
Sent By lcrespo Date 2022-03-14 Time 13:43 Rev Time 0.00
Received By lcrespo Date 2022-03-14 Time 13:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-08-12 Cont ID  
Sent By amhamilt Date 2022-08-12 Time 09:15 Rev Time 0.00
Received By amhamilt Date 2022-08-12 Time 09:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-31 Cont ID  
Sent By amhamilt Date 2022-05-31 Time 16:20 Rev Time 0.00
Received By amhamilt Date 2022-05-31 Time 16:20 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-03-29 Cont ID  
Sent By amhamilt Date 2022-03-29 Time 16:07 Rev Time 0.00
Received By amhamilt Date 2022-03-29 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2022-08-24 Cont ID  
Sent By lmarchan Date 2022-08-24 Time 15:23 Rev Time 0.00
Received By lmarchan Date 2022-08-16 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-08-14 Cont ID  
Sent By lmarchan Date 2022-08-14 Time 08:06 Rev Time 0.00
Received By lmarchan Date 2022-08-06 Time 07:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-08-04 Cont ID  
Sent By rmcphers Date 2022-08-04 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2022-07-29 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-07-26 Cont ID  
Sent By rmcphers Date 2022-07-26 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2022-07-20 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-18 Cont ID  
Sent By rmcphers Date 2022-07-18 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2022-07-05 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-05 Cont ID  
Sent By lmarchan Date 2022-07-05 Time 13:49 Rev Time 0.00
Received By lmarchan Date 2022-06-15 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-01 Cont ID  
Sent By aoliver Date 2022-06-01 Time 09:03 Rev Time 0.00
Received By aoliver Date 2022-05-11 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 09:34 Rev Time 0.00
Received By rmcphers Date 2022-03-09 Time 10:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 09:19 Rev Time 0.00
Received By rmcphers Date 2022-04-11 Time 09:19 Sent To  
Notes
2022-04-11 09:20:20NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-23 Cont ID  
Sent By medwards Date 2022-06-23 Time 06:18 Rev Time 0.00
Received By medwards Date 2022-06-23 Time 06:17 Sent To  
Notes
2022-06-23 06:19:07THE GENERATOR WILL REQUIRE A SEPARATE PERMIT AND
 MECHANICAL REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 11:45 Rev Time 0.00
Received By medwards Date 2022-05-23 Time 11:45 Sent To  
Notes
2022-05-23 11:45:392ND CYCLE REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE USE OF THIS SPACE APPEARS TO BE MORE OF AN A-3
 OCCUPANCY. A CHANGE OF USE SHOULD BE INCLUDED IN THIS
 SUBMITTAL. THE OUTDOOR AIR SCHEDULE LISTS THE ART
 GALLERY AS OPEN STORAGE, THE CORRECT USE OF SPACE
 SHOULD BE NAMED MUSEUM/GALLERY. THE USE OF SPACE SHOULD
 BE ACCURATE FOR EACH AREA ON THE DRAWINGS. PLEASE
 REVISE THE DRAWINGS TO REFLECT THE USE OF EACH SPACE IN
 THIS TENANT SPACE. FBC 107.2.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By medwards Date 2022-03-23 Time 10:58 Rev Time 0.00
Received By medwards Date 2022-03-23 Time 10:58 Sent To  
Notes
2022-03-23 10:58:541ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010834
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE AN OCCUPANCY FOR THIS TENANT SPACE.
 PLEASE EXPLAIN WHAT IS GOING TO BE IN THIS SPACE THAT
 WOULD NEED ALL THE DEHUMIDIFIERS. I CANNOT DO A REVIEW
 ON THIS PROJECT UNTIL THE OCCUPANCY IS DECLARED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-07-06 Cont ID  
Sent By rwbrown Date 2022-07-06 Time 12:20 Rev Time 0.00
Received By rwbrown Date 2022-07-06 Time 12:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-06-22 Cont ID  
Sent By rwbrown Date 2022-06-22 Time 06:22 Rev Time 0.00
Received By rwbrown Date 2022-06-22 Time 06:17 Sent To  
Notes
2022-06-22 06:22:221ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 107.3 -- DUE TO A CHANGE IN
 PROCESS, THE BACKFLOW PERMIT IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION -TBD- (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS. BOTH THE BUILDING AND
 LANDSCAPE (IRRIGATION) WILL REQUIRE A BACKFLOW DEVICE.
 YOU CAN CALL 561-822-2240 (BACKFLOW DEPARTMENT) FOR
 REQUIREMENTS ON BACKFLOW DEVICES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By rwbrown Date 2022-05-17 Time 13:36 Rev Time 0.00
Received By rwbrown Date 2022-05-17 Time 13:36 Sent To  
Notes
2022-05-17 13:32:0903/14/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
  
 1. DONE
  
 2. DONE
  
 3. DONE
  
 4. ON SHEET A5.1;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 5. DELETED
  
 6. DONE
  
 7. DONE
  
 8 AND 9. 2017 WPB AMEND - 107.3 -- DUE TO A CHANGE IN
 PROCESS, THE BACKFLOW PERMIT IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION -TBD- (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS. BOTH THE BUILDING AND
 LANDSCAPE (IRRIGATION) WILL REQUIRE A BACKFLOW DEVICE.
 YOU CAN CALL 561-822-2240 (BACKFLOW DEPARTMENT) FOR
 REQUIREMENTS ON BACKFLOW DEVICES.
  
 NOTE: P2, P3 & P4: IT APPEARS THE DEMONSTRATION KITCHEN
 PLANS FOR MORSE LIFE WERE MISTAKENLY UPLOADED WITH THE
 PLAN SETS FOR THIS ART STORAGE/GALLERY PERMIT, AND WILL
 BE LOCKED OUT OF THE REVIEW- SEC. 107.2.1 WPB.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By lcrespo Date 2022-03-14 Time 13:42 Rev Time 0.00
Received By lcrespo Date 2022-03-14 Time 10:33 Sent To  
Notes
2022-03-14 14:29:2703/14/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE SHEET, A1.0 HAS TWO ACCESSIBLE RESTROOMS.
 WOULD YOU PLEASE PROVIDE A DETAIL OF THE RESTROOM
 SHOWING THE CLEAR FLOOR SPACE AND DIMENSIONS FOR THE
 RESTROOM? SHOW THE WATER CLOSET COMPARTMENT, THE CLEAR
 FLOOR SPACE FOR THE LAV, AND INSIDE THE TURNING RADIUS
 PER THE 2020 FBC ACC SEC. 305 CLEAR FLOOR OR GROUND
 SPACE.
  
 2. IN EMPLOYEE AND PUBLIC TOILET ROOMS, THE REQUIRED
 LAVATORY SHALL BE LOCATED IN THE SAME ROOM AS THE
 REQUIRED WATER CLOSET PER THE 2020 FBC ACC. SEC.
 405.3.2 PUBLIC LAVATORIES
  
 3. ON SHEETS A1.0, A1.1, A2.0, AND CIVIL SHOW TWO
 RESTROOMS. WOULD YOU PLEASE LABEL FEMALE AND MALE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. WOULD YOU PLEASE LABEL THE
 RESTROOM THAT REQUIRED A PUBLIC FACILITY TO PROVIDE
 SIGNS THAT DESIGNATE THE SEX PER THE 2020 FBC SECTION P
 403.2?
  
 4. ON SHEET A5.1;
  
 A. ON DETAIL D4, THE REFLECTIVE PART OF THE MIRROR
 NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER THE
 2020 FBC ACC SEC. 603.3.
  
 B. ON D7, SHOW THE ELEVATION OF 34 INCHES FOR THE TOP
 OF LAV PER THE 2020 FBC ACC SEC. 606.3.
  
 C. A DRINKING FOUNTAIN IS A REQUIRED FIXTURE AND SHALL
 BE ACCESSIBLE IN ACCORDANCE WITH 2020 FBC ACC SEC.
 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND DETAILS
 SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING
 FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR SPACE AND
 PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 SPOUT LOCATIONS PER THE 2020 FBC ACC SEC. 306, 307, &
 602.2, COMPLIANCE WITH 2020 FBC ACC SEC. 307.2
 PROTRUSION LIMITS.
  
 5. ON SHEET S1.1, IT SHOWS TWO WATER CLOSETS ON THE
 SOUTH SIDE OF THE ADA RESTROOM. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? IS THIS AN
 EXISTING FOUNDATION, AND IS THERE CUTTING OF FLOORS? IF
 SO, WOULD YOU PROVIDE A DETAIL REPAIR ON A STRUCTURAL
 SHEET PER THE MINIMUM OF TWO DRINKING FOUNTAINS
 REQUIRED PER THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC.
 410.3.
  
 6. ON SHEET P2.01, WOULD YOU PLEASE SHOW THE DRINKING
 FOUNTAIN PER THE FIXTURE CALCULATION ON PAGE A1.1 OF
 TABLE 403.1? NOTE BOTTLE FILLER IS NOT TO REPLACE A
 DRINKING FOUNTAIN. A MINIMUM OF TWO DRINKING FOUNTAINS
 ARE REQUIRED (HIGH AND LOW) PER THE 2020 ACC FBC SEC.
 211.2 AND FBC P SEC. 410.3.
  
 7. ON SHEET P4.01, WOULD YOU PLEASE SHOW THE DRINKING
 FOUNTAIN ON ISOMETRIC FOR SANITARY AND WATER AS
 REQUIRED ON COMMENT 2- C PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. THE CIVIL SITE PLAN SHOWS THE BACKFLOWS DEVICES,
 FIRE, AND WATER NEXT TO THE BUILDING, AND THE CITY OF
 WEST PALM BEACH REQUIRED IT TO BE A CERTAIN DISTANCE
 FROM THE METER. PLEASE CONTACT THEM @ 561-822-2244
 LOCATIONS. A SEPARATE PERMIT FOR BACKFLOWS IS REQUIRED
 BY A LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 9. PLEASE NOTE ON THE LANDSCAPE IF USING CITY WATER, A
 BACKFLOW IS REQUIRED AT THE WATER METER AND SHALL HAVE
 A SEPARATE PERMIT, CERTIFICATION BY CITY, AND FINAL
 INSPECTION PER THE WPB CROSS CONNECTION MANUAL PER THE
 WPB A TO FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status N Date 2022-11-17 Cont ID  
Sent By shill Date 2022-11-17 Time 14:23 Rev Time 0.00
Received By shill Date 2022-11-17 Time 14:23 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-07-19 Cont ID  
Sent By rgathrig Date 2022-07-19 Time 17:40 Rev Time 0.00
Received By rgathrig Date 2022-07-19 Time 17:37 Sent To  
Notes
2022-07-19 17:40:03OWNERS SWITCHED FROM PRIVATE PROVIDER TO RESIDENT
 INSPECTOR
 DAVID HUSTAD PE WILL BE DOING THE STRUCTURAL
 INSPECTIONS REQUIRED FOR THIS JOB
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-07-14 Cont ID  
Sent By rgathrig Date 2022-07-14 Time 14:36 Rev Time 0.00
Received By rgathrig Date 2022-07-14 Time 14:36 Sent To  
Notes
2022-07-14 14:38:40PRIVATE PROVIDER REVIEW FAILED.
 RESIDENT INSPECTOR FORMS WERE SUBMITTED THAT WERE
 BLANK.
 WHAT ARE YOUR INTENTIONS. PRIVATE PROVIDER OR RESIDENT
 INSPECTOR?
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By rgathrig Date 2022-06-28 Time 09:38 Rev Time 0.00
Received By rgathrig Date 2022-06-28 Time 09:38 Sent To  
Notes
2022-06-28 09:44:24PRIVATE PROVIDER REVIEW FAILED
 THE NOTICE TO BUILDING OFFICIAL FROM THE OWNER JILL
 BERNSTEIN NAMES DAVID L HUSTAD AS THE PRIVATE PROVIDER
 FOR INSPECTIONS ONLY. MR. HUSTAD IS THE STRUCTURAL
 ENGINEER FOR THIS PROJECT AND HE CANNOT BE THE PRIVATE
 PROVIDER PER FLORIDA STATUTES 553.791 (3)
  
 553.791 (3) A PRIVATE PROVIDER AND ANY DULY AUTHORIZED
 REPRESENTATIVE MAY ONLY PERFORM BUILDING CODE
 INSPECTION
 SERVICES THAT ARE WITHIN THE DISCIPLINES COVERED BY
 THAT PERSON?S LICENSURE OR CERTIFICATION UNDER CHAPTER
 468,
 CHAPTER 471, OR CHAPTER 481, INCLUDING SINGLE-TRADE
 INSPECTIONS. A PRIVATE PROVIDER MAY NOT PROVIDE
 BUILDING CODE
 INSPECTION SERVICES PURSUANT TO THIS SECTION UPON ANY
 BUILDING DESIGNED OR CONSTRUCTED BY THE PRIVATE
 PROVIDER OR
 THE PRIVATE PROVIDER?S FIRM.
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-05-17 Cont ID  
Sent By rmcphers Date 2022-05-17 Time 16:08 Rev Time 0.00
Received By rmcphers Date 2022-05-17 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2022-08-24 Cont ID  
Sent By rmcphers Date 2022-08-24 Time 08:25 Rev Time 0.00
Received By rmcphers Date 2022-08-24 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-08-04 Cont ID  
Sent By rmcphers Date 2022-08-04 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2022-08-04 Time 15:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-07-26 Cont ID  
Sent By rmcphers Date 2022-07-26 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2022-07-26 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-06 Cont ID  
Sent By rwbrown Date 2022-07-06 Time 12:54 Rev Time 0.00
Received By rwbrown Date 2022-07-06 Time 12:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-24 Cont ID  
Sent By rmcphers Date 2022-06-24 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-06-24 Time 16:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-17 Cont ID  
Sent By rmcphers Date 2022-05-17 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2022-05-17 Time 16:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2022-04-11 Time 09:33 Sent To  
Notes
2022-04-11 09:34:26SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ARCHITECTURAL, STRUCTURAL AND CIVIL DRAWINGS DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 8 Status P Date 2022-08-24 Cont ID  
Sent By llouie Date 2022-08-24 Time   Rev Time 0.00
Received By llouie Date 2022-08-24 Time   Sent To  
Notes
2022-08-24 14:53:45* SEPARATE PERMITS REQUIRED FOR: PARKING AREA
 IMPROVEMENTS, LANNDSCAPING.
  
 * SEE ATTACHED STAMPED SHEETS IN PERMIT SET FOR ZONING
 APPROVAL.
  
  

Review Stop Z ZONING
Rev No 7 Status P Date 2022-08-09 Cont ID  
Sent By llouie Date 2022-08-09 Time   Rev Time 0.00
Received By llouie Date 2022-08-09 Time   Sent To  
Notes
2022-08-09 12:22:50ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) ALTHOUGH THE SITE PLAN IS NOW IN COMPLIANCE WITH
 THE MINIMUM SETBACK REQUIREMENTS OF THE ZLDRS, PER THE
 BUILDING OFFICIAL, THE ACCESSIBILITY REQUIREMENT IS NOW
 OUT OF COMPLIANCE. IT WAS REQUESTED BY ZONING STAFF
 PRIOR TO THE CHANGES TO ADDRESS ZONING SETBACKS THAT
 THE CONTRACTOR COORDINATE WITH THE BUILDING DEPARTMENT
 ON THE MODIFICATIONS MADE TO ACCESSIBILITY. ALL ISSUES
 MUST BE RESOLVED WITH ALL REVIEWERS PRIOR TO THE
 ISSUANCE OF THE PERMIT.
  
 ** SEE ATTACHED STAMPED SHEETS FOR ZONING APPROVAL. **
  

Review Stop Z ZONING
Rev No 6 Status F Date 2022-08-03 Cont ID  
Sent By llouie Date 2022-08-03 Time   Rev Time 0.00
Received By llouie Date 2022-08-03 Time   Sent To  
Notes
2022-08-03 16:11:04** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR
 ON THE PLANS:
  
 1.) NOT ALL PLAN SHEETS HAVE BEEN CHANGED OUT TO
 REFLECT THE CHANGES MADE TO COMPLY WITH THE ZLDRS (I.E.
 BUILDING ELEVATIONS). THE APPLICANT WAS ASKED ON
 NUMEROUS CALLS TO CHECK THE PLANS FOR CONSISTENCY
 BEFORE RESUBMITTING.
  
  
 NOTES:
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 5 Status F Date 2022-07-25 Cont ID  
Sent By llouie Date 2022-07-25 Time   Rev Time 0.00
Received By llouie Date 2022-07-25 Time   Sent To  
Notes
2022-07-25 15:10:38** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDED SITE PLAN SHOWS THAT THE SETBACK DISTANCE
 OF SOME OF THE NEW/MODIFIED EXTERIOR STAIRS AND RAMPS
 DO NOT MEET THE MINIMUM 5 FT. SETBACK FROM THE PROPERTY
 LINE(S). ANY EXISTING IMPROVEMENT (I.E. EXISTING
 STAIRS/RAMPS) CANNOT BE EXPANDED TO INCREASE A
 NON-CONFORMITY. [ZLDR S.94-145(2) AND S.94-515]
  
 [STAFF RESPONSE: PARTIALLY ADDRESSED. SETBACKS AND
 COMPLIANCE WITH THE ZLDRS HAVE BEEN PROVIDED FOR MOST
 NEW STRUCTURAL ELEMENTS; HOWEVER, THE NEW RAMP LOCATED
 AT THE NORTHWEST CORNER OF THE BUILDING STILL DOES NOT
 MEET THE MINIMUM 5 FT. SETBACK FROM THE PROPERTY
 LINE(S). PLEASE ENSURE THAN ANY CHANGES ARE REFLECTED
 IN ALL PLANS FOR CONSISTENCY.]
  
  
 NOTES:
  
 *SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PAVING AND
 STRIPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-07-13 Cont ID  
Sent By llouie Date 2022-07-13 Time   Rev Time 0.00
Received By llouie Date 2022-07-13 Time   Sent To  
Notes
2022-07-13 16:27:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDED SITE PLAN SHOWS THAT THE SETBACK DISTANCE
 OF SOME OF THE NEW/MODIFIED EXTERIOR STAIRS AND RAMPS
 DO NOT MEET THE MINIMUM 5 FT. SETBACK FROM THE PROPERTY
 LINE(S). ANY EXISTING IMPROVEMENT (I.E. EXISTING
 STAIRS/RAMPS) CANNOT BE EXPANDED TO INCREASE A
 NON-CONFORMITY. [ZLDR S.94-145(2) AND S.94-515]
  
  
 NOTES:
  
 *SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PAVING AND
 STRIPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-05 Cont ID  
Sent By llouie Date 2022-07-05 Time   Rev Time 0.00
Received By llouie Date 2022-07-05 Time   Sent To  
Notes
2022-07-05 13:46:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED. [3/18/22 REPEAT COMMENT: NOT ADDRESSED. NO
 SURVEY PROVIDED WITH THE PERMIT RESUBMITTAL] [5/18/2022
 REPEAT COMMENT: COMMENT NOT ADDRESSED. NO UPDATED
 SIGNED AND SEALED SURVEY PROVIDED WITH THE
 RESUBMITTAL.]
  
 2.) EXTERIOR IMPROVEMENTS DETECTED. A SITE PLAN,
 SHOWING THE PROPOSED EXTERIOR MODIFICATIONS REQUIRED.
  
 [3/18/22 REPEAT COMMENT: NO SITE PLAN WAS PROVIDED WITH
 THE PERMIT RESUBMITTAL. SITE PLAN MUST PROVIDE ALL
 SETBACK DIMENSION BETWEEN ALL PROPOSED NEW STRUCTURES
 AND PROPERTY LINE(S).] [5/18/2022 REPEAT COMMENT:
 COMMENT NOT ADDRESSED. SITE PLAN SHOWING LOCATION OF
 NEW EXTERIOR IMPROVEMENTS AND SETBACK DISTANCES FROM
 PROPERTY LINES NOT PROVIDED IN THE LATEST RESUBMITTAL.
 THIS IS A CRITICAL DOCUMENT FOR ZONING TO REVIEW. ALL
 NEW EXTERIOR STRUCTURAL ELEMENTS MUST COMPLY WITH THE
 REQUIREMENTS (I.E. SETBACKS) OF THE ZLDRS]
  
  
  
 NOTES:
  
 *SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PAVING AND
 STRIPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-18 Cont ID  
Sent By llouie Date 2022-05-18 Time   Rev Time 0.00
Received By llouie Date 2022-05-18 Time   Sent To  
Notes
2022-05-18 16:32:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED. [3/18/22 REPEAT COMMENT: NOT ADDRESSED. NO
 SURVEY PROVIDED WITH THE PERMIT RESUBMITTAL]
  
 2.) EXTERIOR IMPROVEMENTS DETECTED. A SITE PLAN,
 SHOWING THE PROPOSED EXTERIOR MODIFICATIONS REQUIRED.
 [3/18/22 REPEAT COMMENT: NO SITE PLAN WAS PROVIDED WITH
 THE PERMIT RESUBMITTAL. SITE PLAN MUST PROVIDE ALL
 SETBACK DIMENSION BETWEEN ALL PROPOSED NEW STRUCTURES
 AND PROPERTY LINE(S).]
  
 3.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE?S
 VALUE ($858,147.00) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY. LANDSCAPE AND IRRIGATION PLANS
 MUST BE SUBMITTED AS A SEPARATE PERMIT. LANDSCAPE PLANS
 DETECTED IN THE PERMIT RESUBMITTAL ? PLEASE SUBMIT AS A
 SEPARATE PERMIT.]
  
  
 NOTES:
  
 *SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PAVING AND
 STRIPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-18 Cont ID  
Sent By llouie Date 2022-03-18 Time   Rev Time  
Received By llouie Date 2022-03-18 Time   Sent To  
Notes
2022-03-18 16:56:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED.
  
 2.) EXTERIOR IMPROVEMENTS DETECTED. A SITE PLAN,
 SHOWING THE PROPOSED EXTERIOR MODIFICATIONS REQUIRED.
  
 3.) WHAT IS THE PROPOSED USE OF THE BUILDING/SPACE?
 PLEASE BE SPECIFIC, AS ZONING STAFF NEEDS TO DETERMINE
 IF THE PROPOSED USE IS A PERMITTED USE IN THE GENERAL
 COMMERCIAL (GC) ZONING DISTRICT AT THIS TIME (PLANS
 INDICATE "FLORIDA WAREHOUSE").
  
 4.) PLEASE INDICATE THE LOCATION OF ALL MECHANICAL
 EQUIPMENT IN THE PLANS.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  