| Plan Review Stops For Permit 22010831 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-03-26 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-03-26 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-03-05 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-03-05 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2022-03-05 17:39:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301 PROVIDE PRODUCT APPROVALS FOR THE | | | COMPONENTS AND CLADDING (WINDOWS, DOORS, ETC.), | | | REVIEWED BY ARCHITECT, OR SUBMIT A LETTER REQUESTING | | | THAT THESE ITEMS BE DEFERRED. FOR COMPONENTS AND | | | CLADDING REFERRED TO ON THE PLAN THESE ITEMS CANNOT BE | | | DEFERRED. PLEASE SUBMIT THE PRODUT APPROVALS. ARCHITECT | | | REVIEW IS NOT NECESSARY FOR ONES REFERENCED ON THE | | | PLAN. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-03-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-29 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-29 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-02-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-03 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-03 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-04-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-04-05 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-04-05 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-04-05 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2022-04-05 07:01:41 | ADDED BY ACCIDENT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-29 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-17 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-03-05 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-01-24 |
Time |
06:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-22 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-22 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-27 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-27 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2022-01-27 10:50:55 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22010831 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL | | | WORK BEING COMPLETED IN THIS PROJECT. | | | | | | 2) IF THERE IS ANY MECHANICAL WORK BEING COMPLETED | | | UNDER THIS PERMIT IT WOULD REQUIRE A MECHANICAL SUB | | | PERMIT. ON THE APPLICATION SUBMITTED THE MECHANICAL BOX | | | DOES NOT HAVE AN X. | | | | | | 3) PLEASE PROVIDE DETAILS ABOUT THE NEW KITCHEN HOOD | | | ABOVE THE RANGE. IS IT DUCTED TO THE OUTSIDE? WHAT ARE | | | THE CFM?S OF THE EXHAUST FAN IN THE HOOD? IS MAKE UP | | | AIR REQUIRED BASED ON FBC RES M1503.4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-06 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-06 |
Time |
08:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-18 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2022-03-18 11:26:43 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22010831 | | | 3/18/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET ME-1 SANITARY RISER: A) THE EXISTING LAV IS | | | ALSO LABELED WC. B) THE TRAP ARM LENGTH FOR THE | | | EXISTING LAV TO CONNECT TO THE VENT APPEARS TO BE | | | EXCEEDING MAXIMUM DISTANCE OF 6 FT. FOR 1-1/2-INCH TRAP | | | OR 5 FT. FOR 1-1/4- TABLE P3105.1 FBC RES. C) IT | | | APPEARS THAT A HORIZONTAL WET VENT IS THE INTENTION FOR | | | THE TWO BATHS HOWEVER IT IS NOT DRAWN IN COMPLIANCE | | | WITH SECS. P3108.1-P3108.2.1 FBC RES.: EACH FIXTURE | | | DRAIN SHALL CONNECT HORIZONTALLY, AND NOT MORE THAN ONE | | | WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF | | | THE DRY-VENTED FIXTURE DRAIN CONNECTION. PLEASE CONNECT | | | THE EXISTING LAV HORIZONTALLY TO THE 4-INCH DRAIN, AND | | | RELOCATE THE DRY VENT TO THE UPPER LAV DRAIN OR BETWEEN | | | THE TWO DRAINS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-28 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-28 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2022-01-28 14:35:35 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22010831 | | | 1/28/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET ME-1: THE SANITARY RISER DOES NOT SHOW THE NEW | | | SHOWER AND BATHTUB DRAINS AND DOES NOT SHOW THE | | | LAVATORY FIXTURE DRAINS MAKING CONNECTIONS INTO THE | | | EXISTING 4-INCH BUILDING DRAIN- SWEC 107.3.5.3 WPB. | | | PLEASE SEE SEC. P3108 FBC RES FOR WET VENTING | | | COMPLIANCE. | | | | | | 2) ME-1: PLEASE PROVIDE A SCOPE OF WORK NARRATIVE FOR | | | PLUMBING ALTERATIONS- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-06 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-06 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-03-26 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-03-26 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-03-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-03-05 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-03-05 |
Time |
17:40 |
Sent To |
|
|
| Notes |
|
|